Instruction manual AQ101, AQ101D, AQ110P, AQ01
33 (48
)
7
T
ECHNICAL DATA
7.1
AQ101,
AQ101D,
AQ110P
ARC FLASH PROTECTION RELAYS
7.1.1
M
OUNTING AND INSTALLATION
Panel material:
Panel thickness (min-max):
Metal panel
1.0
–
5
mm / 1/16” –
13/64
”
Panel mounting screw type:
Key size:
Tightening torque (min-max):
ISO 14581-M4x12 galvanized
Torx T20
1.5
–
2.0 Nm / 13
–
18 in-lbs
Grounding nut type:
Key size:
Tightening torque (min-max):
DIN934-M5 galvanized
8
2.5
–
3.0 Nm / 22
–
26 in-lbs
Connectors X1 and X2 type:
Wire cross section (solid and multicore) (min-max):
Minimum stripping length:
Screw tightening torque (min-max):
Phoenix contact MSTB 2,5/15-ST-5,08
0.2
–
2.5 mm2 / 24-12 AWG
7 mm / 0.275“
0.5
–
0.6 Nm / 4.4
–
5.3 in-lbs
Connector X3 (AQ110P only)
Wire cross section (solid and multicore) (min-max):
Minimum stripping length:
Screw tightening torque (min-max):
0.5
–
6.0 mm2 / 20
–
10 AWG
14 mm / 0.55”
0.5
–
0.6 Nm / 4.4
–
5.3 in-lbs
Fiber connectors
Nut tightening torque:
Light finger tightening
7.1.2
O
PERATION TIMES
Tripping time using HSO (AQ110P only):
2 ms*
Tripping time using mechanical relays (T1-T4):
7 ms*
Reset time
Light activation:
Overcurrent measurement (AQ110P only):
1 ms
50 ms
Protection stages active after energization:
50 ms (typically)
*) Total trip time using arc light (L>) or phase/residual overcurrent (I>) and arc light (L>)
Summary of Contents for Arcteq AQ01
Page 1: ...INSTRUCTION MANUAL AQ101 AQ101D AQ110P AQ01 ...
Page 44: ...Instruction manual AQ101 AQ101D AQ110P AQ01 44 48 ...
Page 45: ...Instruction manual AQ101 AQ101D AQ110P AQ01 45 48 ...
Page 46: ...Instruction manual AQ101 AQ101D AQ110P AQ01 46 48 9 2 AX001 CONNECTION FIBER ...
Page 47: ...Instruction manual AQ101 AQ101D AQ110P AQ01 47 48 9 3 AQ01 ARC FLASH SENSOR ...