7SR11 & 7SR12 Performance Specification
©2017 Siemens Protection Devices Limited
Chapter 3 Page 40 of 56
Attribute
Value
IEC DECAYING
[ ]
Tm
R
t
Is
I
res
×
−
=
1
2
,
±
5 % absolute or
±
50 ms,
for char = IEC-NI : R = 9.7
IEC-VI : R = 43.2
IEC-EI : R = 58.2
IEC-LTI : R = 80
t
res
t
res
,
±
1 % or
±
20ms
Repeatability
±
1 % or
±
20ms
Overshoot time
< 40 ms
Disengaging time
< 57 ms
Figure 2.12-1and Figure 2.12-4 show the operate and reset curves for the four IEC IDMTL curves with a time
multiplier of 1.
Figure 2.12-2 and Figure 2.12-3 show the ANSI operate and reset curves. These operate times apply to non-
directional characteristics. Where directional control is applied then the directional element operate time should be
added to give total maximum operating time.
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......