Chapter 4 - 7SR120 · Data Communications Definitions
© 2017 Siemens Protection Devices Limited
Chapter 4 - Page 33 of 84
Byte
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Content
2
0
FUN
INF
DPI RT L
RT
H
F# L F# H
0
0
0
ms L
ms
H
Mi
Ho
Event Type 2 Format.
Byte
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Content
4
0
FUN
INF
Meas
0
0
0
0
ms L
ms
H
Mi
Ho
Event Type 4 Format.
4.2.6 EVENTCOUNT
The EVENTCOUNT register contains the current number of events in the relay's event buffer.
On reception this register should be interpreted as a 16 bit integer.
4.2.7 TIME_METER
The TIME_METER register contains the device's time. The time must be read or written in one step;
therefore the quantity should be 4 registers. Failing to do this will result in an exception code 2. The
time format is 8 bytes as follows.
The following table describes the fields in the time.
Key
Description
ms L
Time Stamp Milliseconds low byte.
ms H
Time Stamp Milliseconds high byte.
Mi
Time Stamp Minutes (MSB = invalid, time not set > 23 hours).
Ho
Time Stamp Hours (MSB = Summer time flag).
Da
Time Stamp Days.
Mo
Time Stamp Months.
Ye L
Time Stamp Years low byte.
Ye H
Time Stamp Years high byte (Not Used).
The following table shows the fields in the time as they are returned.
Byte
0
1
2
3
4
5
6
7
Content
ms L ms H
Mi
Ho
Da
Mo
Ye L Ye H
Time Format.
4.2.8 STR32 & STR64
4.2.9 BITSTRING
A Bit-String (or Bit-Array) is a method of compactly storing a number of bits of data. In this instance we store
up to 16 bit values, for example the states of binary inputs, in a single 16 bit register. The first bit value is
stored in the Least Significant Bit (LSB) of the register. The 16
th
value would be in the Most Significant Bit
(MSB). Bit values can only be zero or one. Any unused bits will be set to zero.
BITSTRING & MODBUS
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......