7SR120 Technical Manual
Chapter 4 - Page 56 of 84
© 2017 Siemens Protection Devices Limited
5.3 Point List
The tables below identify all the default data points provided by the implementation of the Triangle MicroWorks, Inc.
DNP 3.0 Slave Source Code Library.
This protocol can be set to use any or all of the relays hardware interfaces (USB, Fibre Optic, RS232 and RS485)
where fitted. The relay can communicate simultaneously on all ports regardless of protocol used.
The Station Address of the port being used must be set to a suitable address within the range 0 - 65534 to enable
communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting.
Communication via DNP3 over Ethernet requires external devices. Please refer to the documents TCPIP Catalogue
Sheet and TCPIP Interface Technical Guidance Notes for more information.
The information shown below is the default configuration. This can be modified using the Communications
Configuration Editor tool, refer
5.3.1 Binary Input Points
The default binary input event buffer size is set to allow 100 events.
Binary inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
1 Binary Input 1
0,2
2
2
2 Binary Input 2
0,2
2
2
3 Binary Input 3
0,2
2
2
4 Binary Input 4
0,2
2
2
5 Binary Input 5
0,2
2
2
6 Binary Input 6
0,2
2
2
35 Remote Mode
0,2
2
2
36 Out Of Service Mode
0,2
2
2
37 Local Mode
0,2
2
2
38 Local & Remote
0,2
2
2
40 General Trip
0,2
2
2
41 Trip Circuit Fail
0,2
2
2
42 Start/Pick-up L1
0,2
2
2
43 Start/Pick-up L2
0,2
2
2
44 Start/Pick-up L3
0,2
2
2
45 General Start/Pick-up
0,2
2
2
46 VT Fuse Failure
0,2
2
2
47 Earth Fault Forward/Line
0,2
2
2
48 Earth Fault Reverse/Busbar
0,2
2
2
49 Start/Pick-up N
0,2
2
2
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......