7SR11 & 7SR12 Commissioning and Maintenance Guide
©2017 Siemens Protection Devices Limited
Chapter 6 Page 12 of 72
It should be considered that where several overlapping elements are used simultaneously, the overall protection
operate time may be dependent on the operation of different individual elements at the various levels of applied
current or voltage. The resulting composite characteristic may be tested by enabling all of the relevant applicable
elements or the element operations can be separated or disabled and tested individually.
All relay settings should be checked before testing begins. It is recommended that the relay settings are extracted
from the relay using Reydisp Evolution software and a copy of these settings is stored for reference during and
after testing. It may be necessary to disable some protection functions during the testing of other functions to
allow unambiguous results to be obtained.
Care must be taken to reset or re-enable any settings that have been temporarily altered during the testing before
the relay can be put into service. At the end of testing the relay settings should be compared to the file extracted
at the start to ensure that errors have not been introduced.
2.1
Phase Directional Polarity Check
If the relay has Directional Overcurrent elements, the common direction polarising can be checked independently
from the individual overcurrent elements and their settings. If
Phase Rotation ACB
is selected in the
CT/VT
Config
menu, this corresponds to negative phase sequence and the Forward and Reverse will be automatically
exchanged by internal relay configuration. The tests below describe normal ABC rotation and the forward/reverse
diection reversal will be experienced for ACB settings unless single phase voltages are inverted. Directions for 3
phase testing will also be reversed unless the three phase supply rotation is reversed. This can be achieved by
swapping any two phase wires, for both current and voltage with a standard ABC test supply. Direction Earth
Fault direction is not affected by the
Phase Rotation
direction.
In the INSTRUMENTS MODE display, indication is provided in the DIRECTIONAL METERS menu which displays
current direction under
P/F Dir
as forward or reverse based on the output states of the directional elements, i.e.
whether they see forward current, reverse current or neither for each pole with respect to the
67 Char Angle
setting in the
Phase Overcurrent
menu. This display and the equivalent Measured and Calculated Earth Fault
direction meters can be used as an aid to commissioning testing.
1.
Check the direction of each pole in turn by connecting to the appropriate terminals. The table below
shows
the polarising quantity for each pole.
Connections for Directional Polarity
Overcurrent pole
Polarising voltage
Phase A
V
BC
Phase B
V
CA
Phase C
V
AB
2.
Inject single phase rated current and apply single phase-phase rated voltage at the Char Angle (MTA) phase
angle setting, to each phase in turn. For each pole, monitor the directional display in the instrument menu
and check that indication of forward current (FWD) is displayed. To achieve the required forward
Characteristic Angle, the phase angle of the current should be greater than that of the polarising voltage by
the angle setting.
3. Repeat all of the above with the current connections reversed. Indication should now be given of reverse
(REV) current flow.
Phase
A
B
C
Forward
FWD
FWD
FWD
Reverse
REV
REV
REV
4.
Apply balanced 3 phase rated voltage and current with Vbc voltage as a 0deg reference and Ia at the
characteristic angle. Increase current phase angle until the ‘Fwd’ indication is extinguished. Record this
angle in the table below (Forward lead DO). Continue to increase/decrease the angle until the instrument
reads ‘Rev’. Record the angle (Reverse lead PU). Reduce the current angle until the ’Rev’ extinguishes
(Reverse lead DO). and the ‘Fwd’ subsequently returns (Forward lead PU), recording the angles. Repeat the
above tests, starting from the Characteristic Angle, but reducing the current phase angle to record the
directional boundaries in the opposite (lag) direction. The recorded angle should be the angle at which the
phase current leads the phase-phase polarising voltage. This measurement is greatly simplified if the
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......