7SR11 & 7SR12 Commissioning and Maintenance Guide
©2017 Siemens Protection Devices Limited
Chapter 6 Page 15 of 72
2.2.2
Inverse Time Overcurrent (51)
It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the
Pickup Config
sub-menu in the
Output Config
menu as this will allow the Pick-up led to operate for the function.
Gradually increase current until Pickup LED operates.
Apply 2x setting current and record operating time,
Apply 5x setting current and record operating time.
Compare to calculated values for operating times.
Gradually reduce current until the element drops off and record the level.
P.U.
D.O.
&
TIMIN
G
TESTS
Ph.
Dir
Char.
Curve
Is
(A)
TM
Operate Current
Operate Time
P.U.
(Amps)
D.O.
(Amps)
Tol
2 x Is
(sec)
5 x Is
(sec)
Tol
I
L1
(I
A
)
I
L2
(I
B
)
I
L3
(I
C
)
Calculated Timing values in seconds for TM =1.0
Curve
2 xIs
5 xIs
IEC-NI
10.03
4.28
IEC-VI
13.50
3.38
IEC-EI
26.67
3.33
IEC-LTI
120.00
30.00
ANSI-MI
3.80
1.69
ANSI-VI
7.03
1.31
ANSI-EI
9.52
1.30
Note that the operate time may be subject to the
Minimum op time
setting for the element and/or may have a
Follower DTL
applied.
2.2.2.1
Element Blocking
The Phase Overcurrent elements can be blocked by Binary Input Inhibit, VT Supervision and Inrush Detector
operation, as well as 79 Autoreclose settings for Inst/Delayed. The Characteristic can be modified by Cold Load
(51-n only) and Voltage Controlled Overcurrent and can be made non-directional by VT Supervision. This
functionality should be checked.
Element
BI Inhibits
VTS action
Inrush Detector
79 Autoreclose
51-1
51-2
51-3
51-4
50-1
50-2
50-3
50-4
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...