7SR11 & 7SR12 Commissioning and Maintenance Guide
©2017 Siemens Protection Devices Limited
Chapter 6 Page 43 of 72
Phas
e
Is
(Amps)
DTL
(sec)
P.U. Current
Amps
Tolerance
Operate Time
0.5 x Is
Tolerance
I
L1
(I
A
)
I
L2
(I
B
)
I
L3
(I
C
)
I4(I
G
)
2.12.1.1
Element Blocking
The Undercurrent elements can be blocked by Binary Input Inhibit. This functionality should be checked.
Element
BI Inhibits
37-1
37-2
37G-1 or 37SEF-1
37G-2 or 37SEF-2
2.12.1.2
Element Blocking from current guard
The elements can be blocked by undercurrent guard function. This functionality should be checked.
Element
Guard Setting
Blocked
37-1
37-2
Check correct phase indication, trip output, alarm contacts, waveform record.
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......