7SR11 & 7SR12 Applications Guide
©2017 Siemens Protection Devices Limited
Chapter 7 Page 13 of 48
OC/EF Curve Characteristic
Application
IEC Normal Inverse (NI)
ANSI Moderately Inverse (MI)
Generally applied
IEC Very Inverse (VI)
ANSI Very Inverse (VI)
Used with high impedance paths where there is a significant difference
between fault levels at protection points
IEC Extreme Inversely (EI)
ANSI Extremely Inverse (EI)
Grading with Fuses
IEC Long Time Inverse (LTI)
Used to protect transformer earthing resistors having long withstand times
Table 2-1
Application of IDMTL Characteristics
2.1.2
Reset Delay
The increasing use of plastic insulated cables, both conventionally buried and aerial bundled conductors, have
given rise to the number of flashing intermittent faults on distribution systems. At the fault position, the plastic
melts and temporarily reseals the faulty cable for a short time after which the insulation fails again. The same
phenomenon has occurred in compound-filled joint boxes or on ‘clashing’ overhead line conductors. The
repeating occurrence of the fault can cause electromechanical disc relays to “ratchet” up and eventually trip the
faulty circuit if the reset time of the relay is longer than the time between successive faults.
To mimic an electromechanical relay the relay can be user programmed for an IEC/ANSI DECAYING
characteristic when an ANSI operate characteristic is applied. Alternatively a DTL reset (0 to 60 seconds) can be
used with other operate characteristics.
For protection of cable feeders, it is recommended that a 60 second DTL reset be used.
On overhead line networks, particularly where reclosers are incorporated in the protected system, instantaneous
resetting is desirable to ensure that, on multiple shot reclosing schemes, correct grading between the source
relays and the relays associated with the reclosers is maintained.
FAULT
Clashing
conductors or
re-sealing cable
R1
R2
R3
Disc Travel
Electro-mechanical Relay
Time
TRIP
%
of Algorithm
Argus (Inst. Reset)
Time
Argus (DTL Reset)
TRIP
Figure 2.1-3 Reset Delay
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......