7SR11 & 7SR12 Description Of Operation
Chapter 1 Page 72 of 88 ©2017 Siemens Protection Devices Limited
P
.U
. DELAY
D
.O
. DELAY
T
Counter Value 1
2
Increment
Counter
Equation Output 1
0
1
0
1
For Counter Target = 2
E
n
= 1
Equation
n
P.U. DELAY
D.O. DELAY
Counter
E
n
= 1
Counter
= Target Value
Figure 4-4 Sequence Diagram: Quick Logic PU/DO Timers (Counter Reset Mode Off)
When the count value =
En Counter Target
the output of the counter (En) = 1 and this value is held until the
initiating conditions are removed when En is instantaneously reset.
The output of E
n
is assigned in the OUTPUT CONFIG>OUTPUT MATRIX menu where it can be programmed to
any binary output (O), LED (L) or Virtual Input/Output (V) combination.
Protection functions can be used in Quick Logic by mapping them to a Virtual Input / Output.
Refer to Chapter 7 – Applications Guide for examples of Logic schemes.
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......