7SR210 Settings Guide
Unrestricted Page 8 of 61
© 2018 Siemens Protection Devices Limited
Description
Range
Default
Relay Identifier
An alphanumeric string shown on the LCD normally used to identifier
the circuit the relay is attached to or the relays purpose
(16 Character String)
7SR210
Circuit Identifier
(16 Character String)
3.2. CT/VT Config
Description
Range
Default
Phase Current Input
Selects whether 1 or 5 Amp terminals are being used for phase inputs
1, 5
1 A
Phase CT Ratio Prim
Phase CT ratio to scale primary current instruments
( 6 Character String)
2000 A
Phase CT Ratio Sec
Phase CT ratio to scale secondary current instruments
0.2, 0.21 ... 2, 2.1.....7
1
Earth Current Input
Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs
1, 5
1 A
Earth CT Ratio Prim
Measured Earth CT ratio to scale primary current instruments
( 6 Character String)
2000 A
Earth CT Ratio Sec
Measured Earth CT ratio to scale secondary current instruments
0.2, 0.21 ... 2, 2.1.....7
1
3.3. Function Config
Description
Range
Default
Gn Phase Overcurrent
When set to Disabled, no Phase Overcurrent elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled
Disabled
Gn Cold Load
When set to Disabled, no Cold Load elements will be functional and all associated
settings will be hidden. (The Setting Dependencies setting being set to Disabled
will make all settings visible but will not allow them to operate).
Enabled, Disabled
Disabled
Gn Derived E/F
When set to Disabled, no Derived E/F elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled
Disabled
Gn Measured E/F
When set to Disabled, no Measured E/F elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled
Disabled
Gn Sensitive E/F
When set to Disabled, no Sensitive E/F elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled
Disabled
Gn Restricted E/F
When set to Disabled, no Restricted E/F elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled
Disabled
Gn NPS Overcurrent
When set to Disabled, no NPS Overcurrent elements will be functional and all
associated settings will be hidden. (The Setting Dependencies setting being set to
Disabled will make all settings visible but will not allow them to operate).
Enabled, Disabled
Disabled
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...