7SR220 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited
Page 15 of 107
3.4.1.4.
51-4
Description
Range
Default
Gn 51-4 Element
Selects whether the 51-4 IDMTL Overcurrent element is
enabled
Disabled, Enabled
Disabled
Gn 51-4 Dir. Control
Selects whether 51-4 element is non-directional, forward or
reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 51-4 Setting
Pickup level
0.05, 0.06 ... 2.49, 2.5
1 xIn
Gn 51-4 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51-4 Time Mult (IEC/ANSI)
Time multiplier (applicable to IEC and ANSI curves but not
DTL selection)
0.025, 0.03 ... 1.595, 1.6 , 1.7 ...
4.9, 5, 6 ... 100
1
Gn 51-4 Delay (DTL)
Delay (applicable only when DTL is selected for characteristic)
0, 0.01 ... 19.99, 20
5 s
Gn 51-4 Min Operate Time
Minimum operate time of element.
0, 0.01 ... 19.99, 20
0 s
Gn 51-4 Follower DTL
Additional definite time added after characteristic time
0, 0.01 ... 19.99, 20
0 s
Gn 51-4 Reset
Selects between an ANSI decaying reset characteristic or a
definite time reset
(ANSI) Decaying, 0 ... 59, 60
0 s
Gn 51-4 VTS Action
Selects whether 51-4 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
Gn 51-4 Inrush Action
Selects if the 51-4 element is blocked from operating when
2nd Harmonic Inrush Detector operates
Off, Inhibit
Off
Gn 51-4 21LB-3P Action
Selects if operation of the 51-4 element is blocked for defined
load conditions
Off, Inhibit
Inhibit
Gn 51-4 21LB-1P Action
Selects if operation of the 51-4 element is blocked for defined
load conditions
Off, Inhibit
Off
3.4.1.5.
50-1
Description
Range
Default
Gn 50-1 Element
Selects whether the INST/ DTL Overcurrent element is
enabled
Disabled, Enabled
Disabled
Gn 50-1 Dir. Control
Selects whether 50-1 element is non-directional, forward or
reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 50-1 Setting
Pickup level
0.05, 0.06 ... 49.5, 50
1 xIn
Gn 50-1 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
Gn 50-1 VTS Action
Selects whether 50-1 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...