7SR220 Settings Guide
Unrestricted Page 26 of 107
© 2013 Siemens Protection Devices Limited
Description
Range
Default
Gn 51G-4 Reset
Selects between an ANSI decaying reset characteristic or DTL
reset
(ANSI) Decaying, 0 ... 59, 60
0 s
Gn 51G-4 VTS Action
Selects whether 51G-4 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
Gn 51G-4 Inrush Action
Selects if the 51G-4 element is blocked from operating when
2nd Harmonic Inrush Detector operates
Off, Inhibit
Off
3.4.5.5.
50G-1
Description
Range
Default
Gn 50G-1 Element
Selects whether the DTL measured Earth fault element is
enabled
Disabled, Enabled
Disabled
Gn 50G-1 Dir. Control
Selects whether 50G-1 element is non-directional, forward or
reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 50G-1 Setting
Pickup level
0.005, 0.006 ... 24.95, 25
0.5 xIn
Gn 50G-1 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
Gn 50G-1 VTS Action
Selects whether 50G-1 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
Gn 50G-1 Inrush Action
Selects if the 50G-1 element is blocked from operating when
2nd Harmonic Inrush Detector operates
Off, Inhibit
Off
3.4.5.6.
50G-2
Description
Range
Default
Gn 50G-2 Element
Selects whether the DTL measured Earth fault element is
enabled
Disabled, Enabled
Disabled
Gn 50G-2 Dir. Control
Selects whether 50G-2 element is non-directional, forward or
reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 50G-2 Setting
Pickup level
0.005, 0.006 ... 24.95, 25
0.5 xIn
Gn 50G-2 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
Gn 50G-2 VTS Action
Selects whether 50G-2 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
Gn 50G-2 Inrush Action
Selects if the 50G-2 element is blocked from operating when
2nd Harmonic Inrush Detector operates
Off, Inhibit
Off
3.4.5.7.
50G-3
Description
Range
Default
Gn 50G-3 Element
Selects whether the DTL measured Earth fault element is
enabled
Disabled, Enabled
Disabled
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...