7SR220 Settings Guide
Unrestricted Page 30 of 107
© 2013 Siemens Protection Devices Limited
3.4.6.5.
50SEF-1
Description
Range
Default
Gn 50SEF-1 Element
Selects whether the DTL measured Earth fault element is
enabled
Disabled, Enabled
Disabled
Gn 50SEF-1 Dir. Control
Selects whether 50SEF-1 element is non-directional, forward
or reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 50SEF-1 Setting
Pickup level
0.005, 0.006 ... 4.995, 5
0.2 xIn
Gn 50SEF-1 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
Gn 50SEF-1 VTS Action
Selects whether 50SEF-1 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
3.4.6.6.
50SEF-2
Description
Range
Default
Gn 50SEF-2 Element
Selects whether the DTL measured Earth fault element is
enabled
Disabled, Enabled
Disabled
Gn 50SEF-2 Dir. Control
Selects whether 50SEF-2 element is non-directional, forward
or reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 50SEF-2 Setting
Pickup level
0.005, 0.006 ... 4.995, 5
0.2 xIn
Gn 50SEF-2 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
Gn 50SEF-2 VTS Action
Selects whether 50SEF-2 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
3.4.6.7.
50SEF-3
Description
Range
Default
Gn 50SEF-3 Element
Selects whether the DTL measured Earth fault element is
enabled
Disabled, Enabled
Disabled
Gn 50SEF-3 Dir. Control
Selects whether 50SEF-3 element is non-directional, forward
or reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 50SEF-3 Setting
Pickup level
0.005, 0.006 ... 4.995, 5
0.2 xIn
Gn 50SEF-3 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
Gn 50SEF-3 VTS Action
Selects whether 50SEF-3 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
3.4.6.8.
50SEF-4
Description
Range
Default
Gn 50SEF-4 Element
Selects whether the DTL measured Earth fault element is
enabled
Disabled, Enabled
Disabled
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...