7SR220 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited
Page 31 of 107
Description
Range
Default
Gn 50SEF-4 Dir. Control
Selects whether 50SEF-4 element is non-directional, forward
or reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 50SEF-4 Setting
Pickup level
0.005, 0.006 ... 4.995, 5
0.2 xIn
Gn 50SEF-4 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
Gn 50SEF-4 VTS Action
Selects whether 50SEF-4 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
3.4.7.
Restricted E/F
Description
Range
Default
Gn 64H Element
High impedance restricted earth fault current element
Disabled, Enabled
Disabled
Gn 64H Setting
Pickup level
0.005, 0.006 ... 0.945, 0.95
0.2 xIn
Gn 64H Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
3.4.8.
NPS Overcurrent
3.4.8.1.
46IT
Description
Range
Default
Gn 46IT Element
Selects whether the 46IT IDMTL/DTL negative phase
sequence current element is enabled
Disabled, Enabled
Disabled
Gn 46IT Setting
Pickup level
0.05, 0.06 ... 2.49, 2.5
0.25 xIn
Gn 46IT Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 46IT Time Mult (IEC/ANSI)
Time multiplier (applicable to IEC and ANSI curves but not
DTL selection)
0.025, 0.03 ... 1.595, 1.6 , 1.7 ...
4.9, 5, 6 ... 100
1
Gn 46IT Delay (DTL)
Delay (applicable only when DTL is selected for characteristic)
0, 0.01 ... 19.99, 20
5 s
Gn 46IT Reset
Selects between an ANSI decaying reset characteristic or a
definite time reset
(ANSI) Decaying, 0 ... 59, 60
0 s
3.4.8.2.
46DT
Description
Range
Default
Gn 46DT Element
Selects whether the definite time NPS overvoltage element is
enabled
Disabled, Enabled
Disabled
Gn 46DT Setting
Pickup level
0.05, 0.06 ... 4
0.1 xIn
Gn 46DT Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0.02 s
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...