7SR220 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited
Page 37 of 107
Description
Range
Default
Gn 47-2 Hysteresis
Sets the pickup to drop-off thresholds e.g. 3% picks up at
setting and drops off below 97% of setting
0, 0.1 ... 79.9, 80
3 %
Gn 47-2 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0.5 s
3.8.
Neutral Overvoltage
Description
Range
Default
Gn 59N Voltage Source
Selects voltage source between calculated 3V0 (Vn) or
measured 3V0 through Vx input
Vn, Vx
Vn
3.8.1.
59NIT
Description
Range
Default
Gn 59NIT Element
Selects whether the inverse time neutral over voltage element
is enabled
Disabled, Enabled
Disabled
Gn 59NIT Setting
Pickup level
1, 1.5 ... 99.5, 100
5 V
Gn 59NIT Char
Selects characteristic curve to be IDMTL or DTL
DTL, IDMTL
IDMTL
Gn 59NIT Time Mult (IDMTL)
Time multiplier (applicable to IDMTL curve but not DTL
selection)
0.1, 0.2 ... 139.5, 140
1
Gn 59NIT Delay (DTL)
Delay (applicable only when DTL is selected for characteristic)
0, 0.01 ... 19.99, 20
5 s
Gn 59NIT Reset
Selects between an instantaneous reset characteristic or a
definite time reset
(ANSI) Decaying, 0 ... 59, 60
0 s
3.8.2.
59NDT
Description
Range
Default
Gn 59NDT Element
Selects whether the definite time neutral over voltage element
is enabled
Disabled, Enabled
Disabled
Gn 59NDT Setting
Pickup level
1, 1.5 ... 99.5, 100
5 V
Gn 59NDT Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0.01 s
3.9.
U/O Frequency
Description
Range
Default
Gn 81 U/V Guard Setting
Selects voltage level below which the guard element is
applied.
5, 5.5 ... 199.5, 200
5 V
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...