7SR220 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited
Page 49 of 107
3.11.5.
Circuit Breaker
Description
Range
Default
Gn Close CB Pulse
Specifies the duration of the circuit breaker close pulse
0, 0.1 ... 19.9, 20
2 s
Gn Reclaim Timer
The period of time after a CB has closed and remained closed
before the reclosure is deemed to be successful and the AR is
re-initialised. If the CB remains open at the end of the reclaim
time then the AR goes to lockout.
0, 1 ... 599, 600
2 s
Gn Minimum LO Delay
0, 1 ... 599, 600
2 s
Gn Reset LO By Timer
Disabled, Enabled
Enabled
Gn CB Control Trip Time
Disabled, Enabled
Enabled
Gn Trip Time Alarm
An alarm is issued when the Trip time is exceeded
0, 0.01 ... 1.99, 2
0.2 s
Gn Trip Time Adjust
Adjustment to take into account any binary input delays for
Trip Time Alarm
0, 0.005 ... 1.995, 2
0.015 s
Gn CB Travel Alarm
Selects the maximum time that the CB should take to either
Open or Close before a failure is recorded.
0.01, 0.02 ... 1.99, 2
1 s
Gn Open CB Pulse
Selects the maximum time of the Open CB pulse. If the CB is
not closed when this timer expires then an alarm will be raised
to signify failure to close.
0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8,
0.9, 1, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6,
1.7, 1.8, 1.9, 2
1 s
Gn CB DBI Delay
Selects the Delay before relay goes to Lockout following a
simultaneous Open and Close condition indication.
0, 0.01, ... 1.1, 1.11 ... 2
0 s
3.11.6.
QUICK LOGIC
Description
Range
Default
Quick Logic
Enable or Disable all logic equations
Disabled, Enabled
Disabled
E1 Equation
Enable or Disable logic equation E1
Disabled, Enabled
Disabled
E1
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation.
= AND operation^ = EXCLUSIVE OR operationE(followed by a
digit) = Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed
by a digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when
function key is pressed
(requires E1 to drive L11 in output
matrix)E1 = F3^L11
(20 Character String)
E1 Pick-up Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400
0 s
E1 Drop-off Delay
Time before equation output resets, after equation nolonger
satisfied
0, 0.01 ... 14300, 14400
0 s
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...