7SR220 Settings Guide
Unrestricted Page 102 of 107
© 2013 Siemens Protection Devices Limited
3.14.1.
CB Counters
Description
Range
Default
Gn CB Total Trip Count
Selects whether the CB Total Trip Count counter is enabled
Disabled, Enabled
Disabled
Gn CB Total Trip Count Target
Selects the number of CB trips allowed before CB Total Trip
Count counter output operates
0, 1 ... 9999, 10000
100
Gn CB Total Trip Count Reset
Resets CB Total Trip Count counter
Gn CB Total Trip Manual Open
Selects whether the CB Total Trip Manual Open is enabled
Disabled, Enabled
Disabled
Gn CB Phase Trip Counters
Selects whether the CB Phase Trip Counters is enabled
Disabled, Enabled
Disabled
Gn CB Ph A Trip Count Target
Selects the number of CB trips allowed before CB Ph A Trip
Count counter output operates
0, 1 ... 9999, 10000
100
Gn CB Ph B Trip Count Target
Selects the number of CB trips allowed before CB Ph B Trip
Count counter output operates
0, 1 ... 9999, 10000
100
Gn CB Ph C Trip Count Target
Selects the number of CB trips allowed before CB Ph C Trip
Count counter output operates
0, 1 ... 9999, 10000
100
Gn CB E/F Trip Count Target
Selects the number of CB trips allowed before CB E/F Trip
Count counter output operates
0, 1 ... 9999, 10000
100
Gn CB Delta Trip Count
Selects whether the CB Delta Trip Count counter is enabled
Disabled, Enabled
Disabled
Gn CB Delta Trip Count Target
Selects the number of CB trips allowed before CB Delta Trip
Count counter output operates
0, 1 ... 9999, 10000
100
Gn CB Delta Trip Count Reset
Resets CB Delta Trip Count counter
Gn CB Count To AR Block
Selects whether the CB Count To AR Block counter is enabled
Disabled, Enabled
Disabled
Gn CB Count To AR Block Target
Selects the number of CB trips allowed before CB Count To
AR Block counter output operates. While count is above target
the Autorecloser will only perform 1 x Delayed Shot and
Lockout
0, 1 ... 9999, 10000
100
Gn CB Count To AR Block Reset
Resets CB Count To AR Block counter
Gn CB Freq Ops Count
Selects whether the CB Frequent Operations Counter is
enabled
Disabled, Enabled
Disabled
Gn CB Freq Ops Count Target
Selects the number of CB trips allowed before CB Frequent
Operations Counter output operates. While count is above
target the Autorecloser will only perform 1 x Delayed Shot and
Lockout
0, 1 ... 9999, 10000
10
Gn CB Freq Ops Count Reset
Resets CB Frequent Operations Counter
3.14.2.
I^2T CB Wear
Description
Range
Default
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...