7SR220 Settings Guide
Unrestricted Page 106 of 107
© 2013 Siemens Protection Devices Limited
3.15.7.
Communications
Description
Range
Default
Station Address
IEC 60870-5-103 Station Address
0, 1 ... 65533, 65534
1
COM1-RS485 Protocol
Selects protocol to use for COM1-RS485
OFF, IEC60870-5-103, MODBUS-
RTU, DNP3
IEC60870-5-103
COM1-RS485 Baud Rate
Sets the communications baud rate for COM1-RS485
75, 110, 150, 300, 600, 1200, 2400,
4800, 9600, 19200, 38400
19200
COM1-RS485 Parity
Selects whether parity information is used
NONE, ODD, EVEN
EVEN
COM1-RS485 Mode
Local, Remote, Local Or Remote
Remote
COM2-USB Protocol
Selects protocol to use for COM2-USB
IEC60870-5-103
IEC60870-5-103
COM2-USB Mode
Local
Local
COM3 Protocol
Selects protocol to use for COM3
OFF, IEC60870-5-103, MODBUS-
RTU, DNP3
IEC60870-5-103
COM3 Baud Rate
Sets the communications baud rate for COM3
75, 110, 150, 300, 600, 1200, 2400,
4800, 9600, 19200, 38400, 57600,
115200
19200
COM3 Parity
Selects whether parity information is used
NONE, ODD, EVEN
EVEN
COM3 Line Idle
Selects the communications line idle sense
LIGHT OFF, LIGHT ON
LIGHT OFF
COM3 Data Echo
Enables echoing of data from RX port to TX port when
operating relays in a Fibre Optic ring configuration
OFF, ON
OFF
COM3 Mode
Local, Remote, Local Or Remote
Remote
COM4 Protocol
Selects protocol to use for COM4
OFF, IEC60870-5-103, MODBUS-
RTU, DNP3
OFF
COM4 Baud Rate
Sets the communications baud rate for COM4
75, 110, 150, 300, 600, 1200, 2400,
4800, 9600, 19200, 38400
19200
COM4 Parity
Selects whether parity information is used
NONE, ODD, EVEN
EVEN
COM4 Line Idle
Selects the communications line idle sense
LIGHT OFF, LIGHT ON
LIGHT OFF
COM4 Data Echo
Enables echoing of data from RX port to TX port when
operating relays in a Fibre Optic ring configuration
OFF, ON
OFF
COM4 Mode
Local, Remote, Local Or Remote
Remote
LAN Protocol
Selects protocol to use for LAN port
OFF, IEC60870-5-103
IEC60870-5-103
DNP3 Unsolicited Events
Allows unsolicited event support in the relay. When Enabled,
unsolicited event transmission can be controlled by the
Master. When Disabled, Master requests are ignored.
Disabled, Enabled
Disabled
DNP3 Destination Address
The address of the master to which unsolicited events will be
sent.
0, 1 ... 65533, 65534
0
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...