7SR21 & 7SR22 Performance Specification
Unrestricted Page 50 of 68
© 2013 Siemens Protection Devices Limited
2.20.5 Operate and Reset Level (59NIT)
Attribute
Value
V
op
Operate level
105 %
Vs
,
±
2 % or
±
0.5 V
Reset level
³
95 %
V
op
or
±
0.25 V
Repeatability
±
1 %
Variation
-10 °C to +55 °C
£
5 %
f
nom
- 3 Hz to
f
nom
+ 2 Hz
£
5 %
2.20.6 Operate and Reset Time (59NIT)
Attribute
Value
t
basic
Starter operate time (
³
2
xVs
)
65 ms,
±
20 ms
t
op
Operate
time
char = IDMTL
[ ]
1
M
t
Vs
0
V
3
op
-
=
,
±
5 % or
±
65 ms
char = DTL
t
d
,
±
1 % or
±
40 ms
Reset Time
char = IDMTL
t
res
,
±
5 % or
±
65 ms
char = DTL
t
res
,
±
1 % or
±
40 ms
Repeatability
±
1 % or
±
20 ms
Overshoot time
< 40 ms
Disengaging time
< 50 ms
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...