7SR220 Technical Manual
Chapter 4 - Page 16 of 96
© 2017 Siemens Protection Devices Limited
Pin
Relay Function
4
Output 5V 50mA
5
Signal Ground (GND)
6
Output 5V 50mA
7
Linked to 8 (volts free)
8
Linked to 7 (volts free)
9
Output 5V 50mA
Fig. 2-7 RS232 Data Comms Pin Connections
2.7 Optional Rear EN100 Ethernet Module (COM3)
The optional ethernet interface is primarily provided for support of IEC 61850 Protocol. Support for IEC 60870-5-103
is also provided over this interface to allow connection with Reydisp Evolution and Reydisp Manager Software for
interrogation, editing and download of relay settings and other data. Ordering options are available with two RJ45
electrical connectors or with two duplex LC fibre optic connectors.
Setting Name
Range/Options
Default
Setting
Notes
LAN
Protocol
OFF
IEC60870-5-103
IEC60870-5-103
Sets the protocol
used to communicate
on the LAN port.
If this setting is set to off, access to relay data using Reydisp Evolution and Reydisp Manager Software via the
Ethernet interface is not available.
Connections to the optional EN100 Ethernet module are made on the rear underside of the relay.
Connections are made to either RJ45 sockets (electrical) or Duplex LC (fibre optic) connectors. Fibre cables should
be 62.5/125µm (or 50/125µm) multimode with LC connectors.
The two types of EN100 module work slightly differently. The optical version contains an Ethernet switch to control
the two channels. The switch will manage data from either channel as an Ethernet switch would in a network. The
electrical version connects through one channel until it detects a break in the data traffic. After a delay it will swap to
the other channel to try and re-establish communication. Either method can be thought of as providing for redundancy.
While a 61850 session is established, an operator can simultaneously connect to the device via
or a web browser through the EN100 module.
Configuration of 61850 communication is via the
software package.
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...