5. DNP3 Definitions
5.1 Device Profile
The following table provides a “Device Profile Document” in the standard format defined in the DNP 3.0 Subset
Definitions Document. While it is referred to in the DNP 3.0 Subset Definitions as a “Document,” it is in fact a table, and
only a component of a total interoperability guide. The table, in combination with the Implementation Table provided
in Section 5.2 (beginning on page 56), and the Point List Tables provided in Section 5.3 (beginning on page
62), should provide a complete configuration/interoperability guide for communicating with a device implementing
the Triangle MicroWorks, Inc. DNP 3.0 Slave Source Code Library.
DNP V3.0
DEVICE PROFILE DOCUMENT
(Also see the DNP 3.0 Implementation Table in
, beginning on page 56).
Vendor Name:
Siemens Protection Devices Ltd.
Device Name:
7SR220, using the Triangle MicroWorks, Inc. DNP3 Slave Source Code Library, Version 3.
Highest DNP Level Supported:
For Requests:
Level 3
For Responses:
Level 3
Device Function:
Master
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the
complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited quantity), and 17 and 28
(index) are supported. Static object requests sent with qualifiers 07, or 08, will be responded with qualifiers 00 or
01.
Output Event Object 11 is supported.
Maximum Data Link Frame Size (octets):
Transmitted:
256
Received:
256
Maximum Application Fragment Size (octets):
Transmitted:
2048
Received:
2048
Maximum Data Link Re-tries:
None
Fixed (3)
Configurable from 0 to 65535 (Default 3)
Maximum Application Layer Re-tries:
None
Configurable
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable as: Never, Only for multi-frame messages, or Always
Requires Application Layer Confirmation:
Never
Always
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes
Configurable as: “Only when reporting event data”, or “When reporting event data or multi-fragment
messages.”
Timeouts while waiting for:
Data Link Confirm:
None
Fixed at
Variable
Configurable (2sec)
Complete Appl. Fragment:
None
Fixed at
Variable
Configurable
Application Confirm:
None
Fixed at
Variable
Configurable (10sec)
Complete Appl. Response:
None
Fixed at
Variable
Configurable
Others:
Transmission Delay, (Configurable, default 0 sec)
Select/Operate Arm Timeout, (Configurable, default 5 sec)
Need Time Interval, (Configurable, default 30 minutes)
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...