7SR220 Technical Manual
Chapter 4 - Page 70 of 96
© 2017 Siemens Protection Devices Limited
Binary Input Points
Static (Steady-State) Object Number:
1 (Packed Format)
Change Event Object Number:
1 (w/o Time)
Static Variation reported when variation 0 requested:
1 (Binary Input w/o status)
or
2 (Binary Input with status)
Change Event Variation reported when variation 0 requested:
1 (Binary Input Change w/o Time)
or
2 (Binary Input Change with Absolute Time)
or
3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class (1,
2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
1036 User Output 27
0,2
2
2
1037 User Output 28
0,2
2
2
1038 User Output 29
0,2
2
2
1039 User Output 30
0,2
2
2
1040 User Output 31
0,2
2
2
1041 User Output 32
0,2
2
2
1061 E/F In
0,2
2
2
1062 SEF In
0,2
2
2
1063 CB DBI
0,2
2
2
1064 CB Travelling
0,2
2
2
1065 Close CB Failed
0,2
2
2
1066 Open CB Failed
0,2
2
2
1067 Start Count Alarm
0,2
2
2
1068 50AFD PhA
0,2
2
2
1069 50AFD PhB
0,2
2
2
1070 50AFD PhC
0,2
2
2
1071 50AFD
0,2
2
2
1072 AFD Zone 1 Flash
0,2
2
2
1073 AFD Zone 1
0,2
2
2
1074 AFD Zone 2 Flash
0,2
2
2
1075 AFD Zone 2
0,2
2
2
1076 AFD Zone 3 Flash
0,2
2
2
1077 AFD Zone 3
0,2
2
2
1078 AFD Zone 4 Flash
0,2
2
2
1079 AFD Zone 4
0,2
2
2
1080 AFD Zone 5 Flash
0,2
2
2
1081 AFD Zone 5
0,2
2
2
1082 AFD Zone 6 Flash
0,2
2
2
1083 AFD Zone 6
0,2
2
2
1084 21LB-3P Fwd
0,2
2
2
1085 21LB-3P Rev
0,2
2
2
1086 21LB-1P Fwd
0,2
2
2
1087 21LB-1P Rev
0,2
2
2
1088 81HBL5
0,2
2
2
5.3.2 Double Bit Input Points
The default double bit input event buffer size is set to allow 100 events.
Double bit inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...