Chapter 4 - Data Communications Definitions
© 2017 Siemens Protection Devices Limited
Chapter 4 - Page 81 of 96
Analog Inputs
Static (Steady-State) Object Number:
30
Change Event Object Number:
32
Analog Input Deadband:
34
Static Variation reported when variation 0 requested:
1 (32-Bit Analog Input with Flag)
or
2 (16-Bit Analog Input with Flag)
or
3 (32-Bit Analog Input w/o Flag)
or
4 (16-Bit Analog Input w/o Flag)
or
5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested:
1 (32-Bit Analog Change Event w/o Time)
or
2 (16-Bit Analog Input w/o Time)
or
3 (32-Bit Analog Input with Time)
or
4 (16-Bit Analog Input with Time)
or
5 (Single Precision, floating point Analog Input w/o Time)
or
7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested:
1 (16-Bit)
or
2 (32-Bit)
or
3 (Single Precision, floating point)
Point
Index
59
Description
Active Power C
Default
Change Event
Assigned Class
(1, 2, 3 or none)
0,3
Default
Variation
Static
Object 30
2
Default
Variation
Event
Object 32
4
Default
Multiplier
0.000
Default
Deadband
1000000.000
60 P (3P)
0,3
2
4
0.000
1000000.000
61 Reactive Power A
0,3
2
4
0.000
1000000.000
62 Reactive Power B
0,3
2
4
0.000
1000000.000
63 Reactive Power C
0,3
2
4
0.000
1000000.000
64 Q (3P)
0,3
2
4
0.000
1000000.000
65 Apparent Power A
0,3
2
4
0.000
1000000.000
66 Apparent Power B
0,3
2
4
0.000
1000000.000
67 Apparent Power C
0,3
2
4
0.000
1000000.000
68 S (3P)
0,3
2
4
0.000
1000000.000
71 Power Factor A
0,3
2
4
1000.000
0.100
72 Power Factor B
0,3
2
4
1000.000
0.100
73 Power Factor C
0,3
2
4
1000.000
0.100
74 Power Factor(3P)
0,3
2
4
1000.000
0.100
75 Act Energy Exp
0,3
1
3
1.000
Disabled
76 Act Energy Imp
0,3
1
3
1.000
Disabled
77 React Energy Exp
0,3
1
3
1.000
Disabled
78 React Energy Imp
0,3
1
3
1.000
Disabled
81 Thermal Status Ph A
0,1
4
4
100.000
1.000
82 Thermal Status Ph B
0,1
4
4
100.000
1.000
83 Thermal Status Ph C
0,1
4
4
100.000
1.000
95 Active Setting Group
0,3
2
4
1.000
1.000
99 Vab Secondary
0,3
2
4
10.000
1.000
100 Vbc Secondary
0,3
2
4
10.000
1.000
101 Vca Secondary
0,3
2
4
10.000
1.000
102 Vn Primary
0,3
2
4
0.010
100.000
103 Vn Secondary
0,3
2
4
10.000
1.000
105 Vx Primary
0,3
2
4
0.010
100.000
106 Vx Secondary
0,3
2
4
10.000
1.000
108 I Phase A Max
0,3
2
4
1.000
100.000
109 I Phase B Max
0,3
2
4
1.000
100.000
110 I Phase C Max
0,3
2
4
1.000
100.000
111 P 3P Max
0,3
2
4
0.000
1000000.000
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...