7SR210 & 7SR220 Commissioning & Maintenance Guide
© 2013 Siemens Protection Devices Limited
Page 49 of 82
If the DTL is short, starting from nominal voltage, slowly decrease the applied 3P or VL1 test voltage until the
Pickup LED (temporarily mapped) is lit. Record the operate voltage. The LED should light at setting Volts +/- 5 %.
Slowly increase the input voltage until the LED extinguishes. Record the reset voltage to check the ‘Hysteresis’
setting. If the DTL is long, the operate level level should be checked by applying a voltage of 90 % of setting
voltage. Check Hysteresis by resetting element to the operate level setting plus the hysteresis setting.
Connect the relevant output contact(s) to stop the test set. Step the applied voltage to a level below the setting.
The test set should be stopped at the operate time s/- 5 %
Test inputs VL2 and VL3 by repeating the above if necessary.
When testing is complete reinstate any of the disabled functions.
Where more than one overvoltage (59) elements are being used with different settings, it is convenient to test the
elements with the highest settings first. The elements with lower settings can then be tested without disabling the
higher settings.
If the ‘O/P Phases’ is set to ‘All’, the voltage on all phases must be increased simultaneously. Otherwise the 3
phases should be tested individually. If the DTL setting is short, starting from nominal voltage, slowly increase the
applied 3P or VL1 test voltage until the Pickup LED (temporarily mapped) is lit. The LED should light at setting
Volts +/- 5 % Decrease the input voltage to nominal Volts and the LED will extinguish. Record the reset voltage to
check the ‘Hysteresis’ setting. If the DTL setting is long, the operate level can be checked by applying 100 % of
setting to cause operation followed by setting minus the Hysteresis setting to cause reset.
Connect the relevant output contact(s) to stop the test set. Step the applied voltage to a level above the setting.
The test set should be stopped at the operate time s/- 5 %.
Test inputs VL2 and VL3 by repeating the above if necessary.
Phase
27/59
setting
(Volts)
U/O
DTL
(sec)
Hyst.
D.O.
(calculated)
P.U.
Volts
D.O
Volts
Op. Time
2x Vs (OV)
0.5x Vs (UV)
UV
Guard
Tol
V
1
(V
A
)
V
2
(V
B
)
V
3
(V
C
)
1.1.1.1
Element Blocking
The NPS Overcurrent elements can be blocked by Binary Input Inhibit and VT Supervision. This functionality
should be checked.
Element
BI Inhibits
VT Supervision
27/59-1
27/59-2
27/59-3
27/59-4
When testing is complete reinstate any of the disabled functions.
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...