7SR210 & 7SR220 Commissioning & Maintenance Guide
Page 82 of 82
© 2013 Siemens Protection Devices Limited
5.3
Troubleshooting
Table 5-1
Troubleshooting Guide
Observation
Action
Relay does not power up.
Check that the correct auxiliary DC voltage is applied and that the
polarity is correct.
Relay won’t accept the password.
The Password being entered is wrong. Enter correct password.
If correct password has been forgotten, note down the Numeric
Code which is displayed at the Change Password screen e.g.
To retrieve the password, communicate this code to a Siemens
Protection Devices Ltd. representative.
Protection Healthy LED flashes
General failure. Contact a Siemens Protection Devices Ltd.
representative.
LCD screen flashes continuously.
The LCD has many possible error messages which when
displayed will flash continuously. These indicate various processor
card faults.
General failure. Contact a Siemens Protection Devices Ltd.
representative.
Backlight is on but no text can be seen.
Adjust the contrast.
Scrolling text messages are unreadable.
Adjust the contrast.
Relay displays one instrument after
another with no user intervention.
This is normal operation, default instruments are enabled.
Remove all instruments from the default list and only add those
that are required.
Cannot communicate with the relay.
Check that all of the communications settings match those used
by Reydisp Evolution.
Check that the Tx and Rx fibre-optic cables are connected
correctly. (Tx –> Rx and Rx –> Tx).
Check that all cables, modems and fibre-optic cables work
correctly.
Ensure that IEC 60870-5-103 is specified for the connected port
(COM1, COM2, COM3 or COM4).
Relays will not communicate in a ring
network.
Check that the Data Echo setting on all relays is set to ON.
Check that all relays are powered up.
Check that all relays have unique addresses.
Status inputs do not work.
Check that the correct DC voltage is applied and that the polarity
is correct.
Check that the status input settings such as the pick-up and drop-
off timers and the status inversion function are correctly set.
Relay instrument displays show small
currents or voltages even though the
system is dead.
This is normal. The relay is displaying calculation noise. This will
not affect any accuracy claims for the relay.
If the above checklist does not help in correcting the problem please contact the local Siemens office or contact
PTD 24hr Customer Support, Tel: +49 180 524 7000, Fax: +49 180 524 2471, e-mail:
support.energy@siemens.com.
Change password
= 1234567
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...