Blocked Close Delay
The close command may be delayed by a
Block Close CB
signal applied to a binary input. This causes the
feature to pause before it issues the CB close command and can be used, for example, to delay CB closure until
the CB energy has reached an acceptable level. If the Block signal has not been removed before the end of the
defined time,
Blocked Close Delay
, the relay will go to the lockout state.
Open CB Delay
The Open CB Delay setting is applicable to CB trip commands received through an
Open CB
binary input or via
the Control Menu. Operation of the
Open CB
binary output is delayed by the
Open CB Delay
setting.
NB: During the open countdown period the operation can be terminated by pressing ‘Cancel’ on the fascia.
Open CB Pulse
The duration of the CB open Command pulse is user settable to allow a range of CBs to be used.
CB Failed to Open is taken from the Circuit Breaker Failure Element.
CB Travel Alarm (DBI)
The
CB Open
and
CB Closed
binary inputs are continually monitored to track the CB Status.
The CB should only ever be in 3 states:
CB Status
CB Open
binary input
CB Closed
binary input
CB is Open
1
0
CB is Closed
0
1
CB is Travelling between the above 2 states
0
0
The Relay goes to Lockout and the
CB Alarm
output is given where the Travelling condition exists for longer than
the
CB Travel Alarm
setting.
An instantaneous
CB Alarm
is given for a 1/1 state – i.e. where the CB indicates it is both Open and Closed at
the same time.
Figure 4.11-1 Logic Diagram: Circuit Breaker Status
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...