7SR210 & 7SR220 Description of Operation
Unrestricted ©2018 Siemens Protection Devices Limited
Page 87 of 94
Section 6: Other Features
6.1
Data Communications
Two communication ports, COM1 and COM2 are provided. RS485 connections are available on the terminal
blocks at the rear of the relay (COM1). A USB port, COM 2, is provided at the front of the relay for local access
using a PC.
Optionally, additional communication ports are available: -
2x fibre optic with ST connectors and 1x IRIG-B – (COM3 and COM 4),
1x RS485 and 1x IRIG-B – (COM 3),
1x RS232 and IRIG-B – (COM 3),
2x Electrical Ethernet with RJ45 connectors IEC 61850 - (COM 3 and COM 4),
2x Optical Ethernet with Duplex LC 100BaseF connectors IEC 61850 - (COM 3 and COM 4).
Communication is compatible with Modbus-RTU, IEC60870-5-103 FT 1.2, DNP 3.0 and IEC 61850 transmission
and application standards.
For communication with the relay via a PC (personal computer) a user-friendly software package, Reydisp
Evolution, is available to allow transfer of relay settings, waveform records, event records, fault data records,
Instruments/meters and control functions. Reydisp Evolution is compatible with IEC60870-5-103.
Data communications operation is described in detail in the Data Communications Definitions section.
6.2
Maintenance
The following CB maintenance counters are provided:
CB Total Trip Count:
Increments on each trip command issued.
CB Total Trip Manual Open
Selects whether the CB Total Trip Counter is incremented for
Manual Open Operations. If disabled, the CB Total Counter
will only increment for protection trip commands.
CB Delta Trip Count:
Additional counter which can be reset independently of the
Total Trip Counter. This can be used, for example, for
recording trip operations between visits to a substation.
CB Delta Trip Manual Open
Selects whether the CB Delta Trip Counter is incremented for
Manual Open Operations. If disabled, the CB Delta Trip
Counter will only increment for protection trip commands.
CB Count to AR Block: (Only in Auto-reclose
models)
Displays the number of CB trips experienced by the CB
before the AR is blocked. When the target is reached the
relay will only do 1 Delayed Trip to Lockout. An output is
available to reset this value.
CB Count to AR Block Manual Open: (Only in
Auto-reclose models)
Selects whether the CB Count to AR Block is incremented for
Manual Open Operations. If disabled, the CB Count to AR
Block will only increment for protection trip commands.
CB Frequent Ops Count
Logs the number of trip operations in a rolling window period
of one hour. An output is available to reset this counter.
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...