7SR210 & 7SR220 Description of Operation
Unrestricted ©2018 Siemens Protection Devices Limited
Page 91 of 94
6.3.7
Energy Storage
The measured Power is continuously integrated (over a one-second window) to produce 4 Energy quantities: -
·
Active Export Energy (W)
·
Active Import Energy (W)
·
Reactive Export Energy (VAr)
·
Reactive Import Energy (VAr)
The Direction of Energy transfer is set by: SYSTEM CONFIG>
Export Power/Lag VAr
. With both
Export Power
(W) and
Lag VAr
(VAr) set to be
+ve
, the Direction of Energy transfer will follow the IEC convention, as shown in
the figure.
ACTIVE ENERGY IMPORT
(watts reverse)
IEC CONVENTION :
-ve watts
REACTIVE ENERGY IMPORT
(vars reverse)
IEC CONVENTION :
-ve vars
REACTIVE ENERGY EXPORT
(vars forward)
IEC CONVENTION :
+ve vars
POWER FACTOR LEADING
ACTIVE (W) EXPORT
REACTIVE (VAr) IMPORT
POWER FACTOR LAGGING
ACTIVE (W) IMPORT
REACTIVE (VAr) IMPORT
POWER FACTOR LEADING
ACTIVE (W) IMPORT
REACTIVE (VAr) EXPORT
0°
+90°
180°
-90°
POWER FACTOR LAGGING
ACTIVE (W) EXPORT
REACTIVE (VAr) EXPORT
ACTIVE ENERGY EXPORT
(watts forward)
IEC CONVENTION :
+ve watts
Figure 6.3.7-1
Energy Direction Convention
Setting either the
Export Power
(W) or
Lag VAr
(VAr) to be
-ve
, will reverse the Direction of the Energy transfer
for these quantities. So forward VAr will then be reported as Imported Reactive Energy, and forward Watts will be
reported as Exported Active Energy.
When the accumulated Energy quantities reach a set increment, the Relay issues a pulse to the binary outputs:
OUTPUT CONFIG/OUTPUT MATRIX>
Active Exp Pulse
,
Active Imp Pulse
,
Reactive Exp Pulse
and
Reactive
Imp Pulse
.
The Energy increments are set by the settings: DATA STORAGE/ENERGY STORAGE>
Active Exp Energy
Unit
,
Active Imp Energy Unit
,
Reactive Exp Energy Unit
and
Reactive Imp Energy Unit
. These setting also
define the resolution of the stored energy values reported by instruments and communications protocols. The
value is stored in the range 0-999999 which continues from zero automatically when 999999 is reached.
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...