7SR210 & 7SR220 Description of Operation
Unrestricted Page 94 of 94
©2018 Siemens Protection Devices Limited
6.7.1
Time Synchronisation - Data Communication Interface
Where the data comms channel(s) is connected the relay can be directly time synchronised using the global time
synchronisation. This can be from a dedicated substation automation system or from ‘Reydisp Evolution’
communications support software.
6.7.2
Time Synchronisation – Binary Input
A binary input can be mapped
Clock Sync from BI
. The seconds or minutes will be rounded up or down to the
nearest value when the BI is energised. This input is leading edge triggered.
6.7.3
Time Synchronisation – IRIG-B (Optional)
A BNC connector on the relay rear provides an isolated IRIG-B time synchronisation port. The IRIG-B input
expects a modulated 3-6 Volt signal and provides time synchronisation to the nearest millisecond.
6.8
Settings Groups
The relay provides eight groups of settings – Group number (Gn) 1 to 8. At any one time only one group of
settings can be ‘active’ – SYSTEM CONFIG>
Active Group
setting.
It is possible to edit one group while the relay operates in accordance with settings from another ‘active’ group
using the
View/Edit Group
setting.
Some settings are independent of the active group setting i.e. they apply to all settings groups. This is indicated
on the top line of the relay LCD – where only the Active Group No. is identified. Where settings are group
dependent this is indicated on the top line of the LCD by both the Active Group No. and the View Group No. being
displayed.
A change of settings group can be achieved either locally at the relay fascia, remotely over the data comms
channel(s) or via a binary input. When using a binary input an alternative settings group is selected only whilst the
input is energised (
Select Grp Mode
: Level triggered
) or latches into the selected group after energisation of the
input (
Select Grp Mode
: Edge triggered
).
6.9
Password Feature
The relay incorporates two levels of password protection – one for settings, the other for control functions.
The programmable password feature enables the user to enter a 4 character alpha numeric code to secure
access to the relay functions. A Password of NONE indicates that a Password has not been set and that the
Password feature is disabled. Where a Relay is delivered with the Password already set, this will be AAAA. The
password must be entered twice as a security measure against accidental changes. Once a password has been
entered then it will be required thereafter to change settings or initiate control commands. Passwords can be de-
activated by using the password to gain access and by entering the password
NONE
. Again this must be entered
twice to de-activate the security system.
As soon as the user attempts to change a setting or initiate control the password is requested before any changes
are allowed. Once the password has been validated, the user is ‘logged on’ and any further changes can be made
without re-entering the password. If no more changes are made within 1 hour then the user will automatically be
‘logged off’, re-enabling the password feature.
The Settings Password prevents unauthorised changes to settings from the front fascia or over the data comms
channel(s). The Control Password prevents unauthorised operation of controls in the relay Control Menu from the
front fascia.
The password validation screen also displays a numerical code. If the password is lost or forgotten, this code
should be communicated to Siemens Protection Devices Ltd. and the password can be retrieved.
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...