7SR220 Settings Guide
Unrestricted Page 8 of 107
© 2013 Siemens Protection Devices Limited
3.Relay Settings
3.1. System Config
Description
Range
Default
Active Group
Selects which settings group is currently activated
System Frequency
Selects the Power System Frequency from 50 or 60 Hz
50, 60
50Hz
View/Edit Group
Selects which settings group is currently being displayed
Setting Dependencies
When enabled only active settings are displayed and all others
hidden
Disabled, Enabled
Enabled
Favourite Meters Timer
Selects the time delay after which, if no key presses have
been detected, the relay will begin to poll through any screens
which have been selected as favourite instruments
Off, 1, 2, 5, 10, 15, 30, 60
60 min
Backlight timer
Controls when the LCD backlight turns off
Off, 1, 2, 5, 10, 15, 30, 60
5 min
Date
Sets the date, this setting can only be changed on the fascia or
via Relay->Control->Set Time and Date
Time
Sets the time, this setting can only be changed on the fascia or
via Relay->Control->Set Time and Date
Curr Set Display
Select whether the Pickup values are shown in terms of x
Nominal, Primary or Secondary values on the Relay Fascia
xNom, Primary, Secondary
xNom
E/F Curr Set Display
As Above
xNom, Primary, Secondary
xNom
SEF/REF Curr Set Display
As Above
xNom, Primary, Secondary
xNom
Export Power/Lag VAr
Selects the signs required for exporting power and lagging
VArs
+ve/+ve, +ve/-ve, -ve/+ve, -ve/-ve
+ve/+ve
Select Grp Mode
Mode of operation of the group change from status input. Edge
triggered ignores the status input once it has changed to the
relevant group, where as with Level triggered the relay will
only stay in the group it has changed to whilst the status input
is being driven, after which it returns to the previous group.
Edge triggered, Level triggered
Edge triggered
Clock Sync. From BI
Real time clock may be synchronised using a binary input
(See Clock Sync. in Binary Input Menu)
Disabled, Seconds, Minutes
Minutes
Operating Mode
Selects the current operating mode of the relay. This can also
be changed by a binary input mode selection.
Out Of Service, Local, Remote,
Local Or Remote
Local Or Remote
Setting Password
Allows a 4 character alpha code to be entered as the
password. Note that the display shows a password dependant
encrypted code on the second line of the display
(Password)
NONE
Control Password
As Above
(Password)
NONE
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...