background image

7SR21 & 7SR22 Performance Specification

Unrestricted  Page 12 of 68

© 2013 Siemens Protection Devices Limited

1.2.2.1

Burden

1.2.2.2

Thermal Withstand

Overload Period

Overload Current

Phase and Earth

1 A

5 A

Continuous

3.0

xIn

10 minutes

3.5

xIn

5 minutes

4.0

xIn

3 minutes

5.0

xIn

2 minutes

6.0

xIn

3 seconds

57.7 A

202 A

2 seconds

70.7 A

247 A

1 second

100 A

350 A

1 cycle

700 A

2500 A

1.2.3  AC Voltage

Nominal

Operating Range

Vn

63.5 V, 110 V

40 V rms to 160 V rms

fn

50 Hz, 60 Hz

47 Hz to 62 Hz

1.2.3.1

Burden

Attribute

Value

AC Burden

 0.1 VA at 110 V

Attribute

Value - Phase and Earth

1 A

5 A

AC Burden

 0.1 VA

 0.3 VA

Summary of Contents for Argus 7SR21

Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...

Page 2: ......

Page 3: ...n Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of negligence or any other cause Any and all such liability is disclaimed 2013 Siemens Protection Devices Limited Contents Technical Manual Sections 1 Descript...

Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...

Page 5: ...ystem without the permission of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of n...

Page 6: ...pographical revisions Software Revision History 2011 05 2435H85008R7a 7a 7SR210 2435H85009R7a 7a 7SR220 First Release 2013 01 2435H85008R7c 7b 7SR210 2435H85009R7c 7b 7SR220 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line Check on non AR devices Added 74CCS Close Circuit Supervision 2014 06 2435H85008R7f 7d 7SR210 2435...

Page 7: ...67G 51G 50G 35 3 4 1 Directional Control of Measured Earth Fault Protection 67G 7SR22 35 3 4 2 Instantaneous Measured Earth Fault Protection 50G 36 3 4 3 Time Delayed Measured Earth Fault Protection 51G 37 3 5 Current Protection Sensitive Earth Fault 67SEF 51SEF 50SEF 38 3 5 1 Directional Control of Sensitive Earth Fault Protection 67SEF 7SR22 38 3 5 2 Instantaneous Sensitive Earth Fault Protectio...

Page 8: ...1 60CTS I 7SR21 7SR22 80 5 4 2 60CTS 7SR22 80 5 5 Broken Conductor 46BC 81 5 6 Trip Close Circuit Supervision 74TCS 74CCS 81 5 7 Inrush Restraint 81HBL2 82 5 8 Over Fluxing Detector 81HLB5 83 5 9 Load Blinder 21 84 5 9 1 Load Blinder 21 Three Phase 84 5 9 2 Load Blinder 21 Single Phase 85 Section 6 Other Features 87 6 1 Data Communications 87 6 2 Maintenance 87 6 2 1 I2 t CB Wear 88 6 2 2 Output M...

Page 9: ...ntaneous Element Compensated Networks 40 Figure 3 5 3 1 Logic Diagram 51 SEF Time Delayed Element 42 Figure 3 5 3 2 Logic Diagram 51 SEF Time Delayed Element Compensated Networks 42 Figure 3 6 1 Logic Diagram High Impedance REF 64H 43 Figure 3 7 1 Logic Diagram Cold Load Settings 51c 44 Figure 3 8 1 Logic Diagram Negative Phase Sequence Overcurrent 46NPS 45 Figure 3 9 1 Logic Diagram Undercurrent ...

Page 10: ...82 Figure 5 8 1 Logic Diagram Over Fluxing Detector 81HLB5 83 Figure 5 9 1 1 Logic Diagram Load Blinder Three Phase 84 Figure 5 9 2 1 Logic Diagram Load Blinder Single Phase 85 Figure 5 9 2 2 Load Blinder and Angle 86 Figure 6 3 7 1 Energy Direction Convention 91 LIST OF TABLES Table 1 5 1 Ordering Information 7SR21 Non Directional Overcurrent 9 Table 1 5 2 Ordering Information 7SR22 Directional O...

Page 11: ...t signal Binary Output visible to user Digital signal to from another element List of settings associated with a specific function Appropriate list is TRUE when setting selected Digital signal not visible to user internal to this element IL1 Analogue signal with signal description Common setting for multiple functions c start trip Function Individual functions are enabled when associated control i...

Page 12: ...ernal Resistors Where external resistors are fitted to the circuit these may present a danger of electric shock or burns if touched 1 3 Fibre Optic Communication Where fibre optic communication ports are fitted the lasers are Class 1 devices but recommend they should not be viewed directly Optical power meters should be used to determine the operation or signal level of the device 1 4 Front Cover ...

Page 13: ...nt port RS485 rear port 1 Standard version plus additional rear F O ST connectors x2 and IRIG B 2 Standard version plus additional rear RS485 and IRIG B 3 Standard version plus additional rear RS232 and IRIG B 4 Standard version plus additional rear Electrical Ethernet RJ45 x2 7 7 Standard version plus additional rear Optical Ethernet Duplex x2 8 7 Protocol IEC 60870 5 103 and Modbus RTU user sele...

Page 14: ...7SR210 7SR220 Description of Operation Unrestricted 2018 Siemens Protection Devices Limited Page 10 of 94 Figure 1 5 1 Functional Diagram of 7SR21 Relay ...

Page 15: ...4 27 25 23 BO 15 BO 16 A B C A Screen B Term 14 16 18 20 Rear View Arrangement of terminals and modules Shows contacts internal to relay case assembly Contacts close when the relay chassis is withdrawn from case NOTES BI Binary Input BO Binary Output BO 1 BO 2 9 5 7 BO 3 BO 4 BO 5 BO 6 27 3 1 15 11 13 19 17 23 21 25 26 A Analogue B PSU C Optional I O 1 2 27 28 1 2 1 2 27 28 27 28 Data Comms Option...

Page 16: ...RJ45 x2 7 7 Standard version plus additional rear Optical Ethernet Duplex x2 8 7 Protocol IEC 60870 5 103 and Modbus RTU user selectable 1 IEC 60870 5 103 and Modbus RTU and DNP 3 0 user selectable 2 IEC 60870 5 103 and Modbus RTU and DNP 3 0 user selectable and IEC61850 7 8 7 Spare 0 Protection Function Packages Standard version included in all models C 21FL Fault Locator 21LB Load Blinder 27 591...

Page 17: ...1 HBL 2 5 60 CTS I4 IG I5 ISEF 74 TCS NOTE The use of some functions are mutually exclusive 67 50 51 x4 67 50 51N x4 67 50 51 x4 67 50 51 x4 67 50 51G x4 67 50 51S x4 64 H 27 59 27 59 x4 27 59 x4 27 59 x4 47 x2 81 x6 79 Optional 59N x2 81 HBL 2 5N 37G x2 37S x2 51c 60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c 32S 32 55 21 LB 21 LB 21 LB 51V 21FL 60 VTS 51V 51V F...

Page 18: ... O 1 2 27 28 1 2 1 2 27 28 27 28 Data Comms Optional Rear View Arrangement of terminals and modules B C A Screen B Term 14 16 18 20 Shows contacts internal to relay case assembly Contacts close when the relay chassis is withdrawn from case NOTES BI Binary Input BO Binary Output 21 19 17 23 25 27 3 1 7 5 11 9 15 13 BO 1 BO 2 9 5 7 BO 3 BO 4 BO 5 BO 6 27 3 1 15 11 13 19 17 23 21 25 26 D Optional I O...

Page 19: ...16 8 6 E8 7SR2105 4 39 16 32 E12 7SR2106 4 39 16 16 12 E12 7SR2202 5 4 3 6 8 E6 7SR2203 5 4 13 14 16 E8 7SR2204 5 4 13 14 8 6 E8 7SR2205 5 4 33 14 32 E12 7SR2206 5 4 33 14 16 12 E12 Relays are assembled from the following modules 1 Front Fascia with three fixed function LEDs and ordering options of configurable LEDs Function Keys 2 Processor module 3 Analogue Input module either 4 x Current 6 x Bi...

Page 20: ... main panel earth 2 3 Front Cover With the transparent front cover in place the user only has access to the and TEST RESET buttons via blue push buttons allowing all areas of the menu system to be viewed but preventing setting changes and control actions The only action that is permitted is to reset the Fault Data display latched binary outputs and LEDs by using the TEST RESET 4 button The front c...

Page 21: ...icted 2018 Siemens Protection Devices Limited Page 17 of 94 Figure 2 5 1 7SR21 with 3 8 LEDs in E6 Case Figure 2 5 2 7SR220 with 3 16 LEDs in E8 Case Figure 2 5 3 7SR22 with Function Keys and 3 8 LEDs in E8 Case NOTE Pushbuttons on cover not shown ...

Page 22: ... display backlighting is extinguished when no buttons are pressed for a user defined period A setting within the SYSTEM CONFIG menu allows the timeout to be adjusted from 1 to 60 minutes and Off backlight permanently on Pressing any key will re activate the display The LCD contrast can be adjusted using a flat blade screwdriver to turn the screw located below the contrast symbol Turning the screw ...

Page 23: ... Yellow LEDs illuminate yellow when both red and green are selected PU Green LEDs illuminate green in response to the detection of a condition PU Red LEDs illuminate red in response to the detection of a condition Colour selection is achieved by checking ticking the appropriate box i e red or green To select yellow check both red green boxes Functions are assigned to the LEDs in the OUTPUT CONFIG ...

Page 24: ...rogrammable pushbuttons can be specified These can be configured by the user to initiate selected functions from the Control menu INPUT CONFIG FUNCTION KEY MATRIX Each pushbutton has an associated LED LEDs can be programmed as hand or self reset and can be illuminated as green yellow or red OUTPUT CONFIG LED CONFIG Function keys can be used with Quick Logic ...

Page 25: ...waveform recorder samples and displays voltage input waveforms at 1600 Hz 2 8 Binary Inputs The binary inputs are operated from a suitably rated dc supply Relays are fitted with 3 9 13 19 33 or 39 binary inputs BI The user can assign any binary input to any of the available functions INPUT CONFIG INPUT MATRIX The Power Supply module includes the relay basic I O The module includes 3 x BI and 6 x B...

Page 26: ... actuate the Trip Alert screen where enabled and CB Fail protection when enabled When the relay is withdrawn from the case all normally closed contacts will be open circuited This should be considered in the design of the control and protection circuitry Notes on Pulsed Outputs When operated the output will reset after a user configurable time of up to 60 seconds regardless of the initiating condi...

Page 27: ...he maximum time A Start up Counter Meter is provided to display the number of start ups the relay has performed Once the number of start ups has exceeded a set number an Alarm output can be given Figure 2 11 1 Start up Counter Meter Reset of the counter can be done from the meter or via a binary input or a command Various types of start up are monitored by the relay 1 power on starts auxiliary sup...

Page 28: ...rt followed by the relay Warm Cold or Re Start Figure 2 11 3 Start up Counter Meter Events 2 11 1 Protection Healthy Defective When the relay has an auxiliary DC supply and it has successfully passed its self checking procedure then the front facia Protection Healthy LED is turned on A normally open contact can be used to signal protection healthy When the relay has DC supply and it has successful...

Page 29: ...hase angle by which the polarising voltage must be adjusted such that the directional detector gives maximum sensitivity in the forward operate zone when the current is in phase with it The reverse operate zone is the mirror image of the forward zone Voltage polarisation is achieved for the phase fault elements using the quadrature voltage i e at unity power factor I leads V by 90 Each phase curre...

Page 30: ...s the minimum polarising voltage level Where the measured polarising voltage is below this level no directional output is given and operation of protection elements set as directional will be inhibited This prevents mal operation under fuse failure MCB tripped conditions where noise voltages can be present Figure 3 1 1 1 Logic Diagram Directional Overcurrent Element 67 ...

Page 31: ...ments have transient free operation Where directional elements are present the direction of operation can be set using 50 n Dir Control setting Directional logic is provided independently for each 50 n element Operation of the instantaneous overcurrent elements can be inhibited from Inhibit 50 n A binary input virtual input function key or remote data Comms 79 P F Inst Trips 50 n When delayed trip...

Page 32: ... is used instead The 51 n Reset setting can apply a definite time delayed reset or when configured as an ANSI characteristic an ANSI DECAYING reset If ANSI DECAYING reset is selected for an IEC characteristic the reset will be instantaneous The reset mode is significant where the characteristic has reset before issuing a trip output see Applications Guide A minimum operate time for the characteris...

Page 33: ...n L2 Dir En L3 Dir En IL1 Fwd IL1 Rev IL2 Fwd IL2 Rev IL3 Fwd IL3 Rev 1 1 1 Non Dir 51 n VTS Action Off Inhibit 60VTS 51 n Min Operate Time IL1 IL2 IL3 50 51 Measurement See Voltage Controlled Overcurrent 51V L1 81HBL2 51c 51 n Inrush Action Off Inhibit L3 L2 L1 L2 81HBL2 L3 81HBL2 c Pickup trip c Pickup trip c Pickup trip Inhibit 51 n 51 n Element Enabled Disabled 79 P F Inst Trips 51 n 79 P F Pr...

Page 34: ...ckup current setting 51 n Multiplier is applied to each phase independently when its control phase phase voltage falls below VCO Setting The voltage levels used for each phase over current element are shown in the table below Relays with a Ph N connection automatically calculate the correct Ph Ph control voltage Current Element Control Voltage IL1 V12 IL2 V23 IL3 V31 The Voltage Controlled Overcur...

Page 35: ...e is the mirror image of the forward zone The derived directional earth fault elements can use either zero phase sequence ZPS or negative phase sequence NPS polarising This is selected using the 67N Polarising Quantity setting Whenever a zero sequence voltage is available a five limb VT that can provide a zero sequence path or an open delta VT connection the earth fault element can use zero sequen...

Page 36: ...ements are provided in the 7SR22 relay e g giving the option of using two elements set to forward and two to reverse Each instantaneous element has independent settings for pick up current 50N n Setting and a follower time delay 50N n Delay The instantaneous elements have transient free operation Where directional elements are present the direction of operation can be set using 50N n Dir Control s...

Page 37: ...l A number of shaped characteristics are provided An inverse definite minimum time IDMT characteristic is selected from IEC and ANSI curves using 51N n Char A time multiplier is applied to the characteristic curves using the 51N n Time Mult setting Alternatively a definite time lag delay DTL can be chosen using 51N n Char When Delay DTL is selected the time multiplier is not applied and the 51N n ...

Page 38: ...binary or virtual input function key or remote data Comms 79 E F Inst Trips 51N n When delayed trips only are allowed in the auto reclose sequence 79 E F Prot n Trip n Delayed 51N n Inrush Action Inhibit Operation of the current inrush detector function 51N n VTSAction Inhibit Operation of the VT Supervision function 7SR22 Figure 3 3 3 1 Logic Diagram Derived Time Delayed Earth Fault Protection ...

Page 39: ...e is the phase angle by which the polarising voltage must be adjusted such that the directional detector gives maximum sensitivity in the forward operate zone when the current is in phase with it The reverse operate zone is the mirror image of the forward zone The measured directional earth fault elements use zero phase sequence ZPS polarising Voltage polarisation is achieved for the earth fault e...

Page 40: ...elements have transient free operation Where directional elements are present the direction of operation can be set using 50G n Dir Control setting Directional logic is provided independently for each 50G n element Operation of the instantaneous measured earth fault elements can be inhibited from Inhibit 50G n A binary or virtual input function key or remote data Comms 79 E F Inst Trips 50G n When...

Page 41: ...ANSI characteristic an ANSI DECAYING reset If ANSI DECAYING reset is selected for an IEC characteristic the reset will be instantaneous The reset mode is significant where the characteristic has reset before issuing a trip output see Applications Guide A minimum operate time for the characteristic can be set using 51G n Min Operate Time setting A fixed additional operate time can be added to the c...

Page 42: ...achieved for the earth fault elements by comparison of the appropriate current with its equivalent voltage I0 V0 The characteristic angle can be user programmed to any angle between 95 and 95 using the 67SEF Char Angle setting The voltage is the reference phasor Vref and the 67SEF Char Angle setting is added to this to adjust the forward and reverse zones The centre of the forward zone is set by V...

Page 43: ...tional logic is provided independently for each 50SEF n element Operation of the instantaneous earth fault elements can be inhibited from Inhibit 50SEF n A binary or virtual input function key or remote data Comms 79 SEF Inst Trips 50SEF n When delayed trips only are allowed in the auto reclose sequence 79 SEF Prot n Trip n Delayed 50SEF n VTSAction Inhibit Operation of the VT Supervision function...

Page 44: ...ption of Operation Unrestricted Page 40 of 94 2018 Siemens Protection Devices Limited Figure 3 5 2 1 Logic Diagram 50 SEF Instantaneous Element Figure 3 5 2 2 Logic Diagram 50 SEF Instantaneous Element Compensated Networks ...

Page 45: ...nificant where the characteristic has reset before issuing a trip output see Applications Guide A minimum operate time for the characteristic can be set using 51SEF n Min Operate Time setting A fixed additional operate time can be added to the characteristic using 51SEF n Follower DTL setting Where directional elements are present the direction of operation can be set using 51SEF n Dir Control set...

Page 46: ...iption of Operation Unrestricted Page 42 of 94 2018 Siemens Protection Devices Limited Figure 3 5 3 1 Logic Diagram 51 SEF Time Delayed Element Figure 3 5 3 2 Logic Diagram 51 SEF Time Delayed Element Compensated Networks ...

Page 47: ...parallel An external stabilising resistor must be connected in series with this input to ensure that this element provides a high impedance path 64H Current Setting sets the pick up current level An output is given after elapse of the 64H Delay setting External components a series stabilising resistor and a non linear resistor are used with this function See Applications Guide for advice in specif...

Page 48: ...ced Current Time setting During cold load settings conditions any directional settings applied in the Phase Overcurrent menu are still applicable A CB Don t Believe It DBI condition is not acted on causing the element to remain operating in accordance with the relevant 51 n settings Where the Reduced Current setting is set to OFF reversion to 51 n settings will only occur at the end of the Drop Of...

Page 49: ...MT characteristic is selected from IEC and ANSI curves using 46IT Char A time multiplier is applied to the characteristic curves using the 46IT Time Mult setting Alternatively a definite time lag delay DTL can be chosen using 46ITChar When Delay DTL is selected the time multiplier is not applied and the 46IT Delay DTL setting is used instead The 46IT Reset setting can apply a definite time delayed...

Page 50: ...urrent timing element 37 n Setting sets the pick up current An output is given after elapse of the 37 n Delay setting Operation of the under current elements can be inhibited from Inhibit 37 n A binary or virtual input function key or remote data Comms Figure 3 9 1 Logic Diagram Undercurrent Detector 37 37G 37SEF 3 10 Current Protection Under Current Guarded 37 A level detector 37 n U I Guard Sett...

Page 51: ...ds a specified percentage of the protected equipment s thermal capacity 49 Capacity Alarm setting For the heating curve Where q thermal state at time t I measured thermal current Iq 49 Overload setting or k IB The final steady state thermal condition can be predicted for any steady state value of input current where t t Where qF final thermal state before disconnection of device 49 Overload Settin...

Page 52: ...7SR210 7SR220 Description of Operation Unrestricted Page 48 of 94 2018 Siemens Protection Devices Limited Figure 3 11 1Logic Diagram Thermal Overload Protection 49S ...

Page 53: ... the relays via the 7XG31xx series of equipment being connected to the binary inputs Should the sensor operate when the current is above the 50AFD Setting then an output signal will be initiated Refer to 7XG31 documentation for further details Enabled Disabled 50AFD Setting c IA IB IC 50AFD Arc Detector Binary Input AFD Zone 1 AFD Zone 1 Flash AFD Zone 6 Flash AFD Zone 6 AFD Zone 1 Flash AFD Zone ...

Page 54: ...7 59 Vx Setting sets the pick up voltage level for the element The sense of the element undervoltage or overvoltage is set by the 27 59 n Operation 27 59 Vx Operation setting The 27 59 n O P Phases setting determines whether the time delay is initiated for operation of any phase or only when all phases have detected the appropriate voltage condition An output is given after elapse of the 27 59 n D...

Page 55: ... from the three input voltages VL1 VL2 and VL3 Two elements are provided in the 7SR22 relay 47 n Setting sets the pick up voltage level for the element The 47 n Hysteresis setting allows the user to vary the pick up drop off ratio for the element An output is given after elapse of the 47 n Delay setting Operation of the negative phase sequence voltage elements can be inhibited from Inhibit 47 n A ...

Page 56: ...haracteristic curves using the 59NIT Time Mult setting M Alternatively a definite time lag delay DTL can be chosen using 59NITChar When Delay DTL is selected the time multiplier is not applied and the 59NIT Delay DTL setting is used instead An instantaneous or definite time delayed reset can be applied using the 59NIT Reset setting The second element has a DTL characteristic The Neutral Definite T...

Page 57: ...r over frequency is set by the 81 n Operation setting 81 n Setting sets the pick up voltage level for the element An output is given after elapse of the 81 n Delay setting The 81 n Hysteresis setting allows the user to vary the pick up drop off ratio for the element Operation of the under over frequency elements can be inhibited from Inhibit 81 n A binary or virtual input function key or remote da...

Page 58: ...ower pick up level or on the total power of all three phases An output is given after elapse of the Gn 32 n Delay setting Operation of the under over power elements can be inhibited when The measured current is below the Gn 32 n U C Guard setting A VT Fail condition is detected Inhibit 32 n A binary or virtual input V1 IL1 V2 V3 IL3 IL2 Enabled Enabled En Inhibit VT Fail W VAr W VAr W VAr W VAr Gn...

Page 59: ...measured Gn 32S n Setting sets the pick up power level for the element Under power or over power operation can be set by the Gn 32S n Operation setting An output is given after elapse of the Gn 32S n Delay setting Operation of the under over power elements can be inhibited when The measured current is below the Gn 32S U C Guard setting A VT Fail condition is detected Inhibit 32S n A binary or virt...

Page 60: ... operation can be set by the Gn 55 n Operation setting Gn 55 n 1ph 3ph Power allows the settings to be based on any one phase power factor or the average power factor of all three phases An output is given after elapse of the Gn 55 n Delay setting Operation of the power factor elements can be inhibited when The measured current is below the Gn 55 U C Guard setting A VT Fail condition is detected I...

Page 61: ...eclose will be Out of Service Knowledge of the CB position status is integral to the auto reclose functionality CB auxiliary switches must be connected to CB Closed and CB Open binary inputs A circuit breaker s service status is determined by its position i e from the binary inputs programmed CB Open and CB Closed The circuit breaker is defined as being in service when it is closed The circuit mem...

Page 62: ...nctionality need to be wired to the binary inputs Functions which can be mapped to these binary inputs include 79 Out edge triggered 79 In edge triggered CB Closed CB Open 79 Ext Trip 79 Ext Pickup 79 Block Reclose Block Close CB Close CB 79 Trip Reclose 79 Trip Lockout 79 Line Check Hot Line In Hot Line Out Outputs Outputs are fully programmable to either binary outputs or LEDs Programmable outpu...

Page 63: ...t The AR function recognizes developing faults and as the shot count advances automatically applies the correct type of Protection and associated Dead time for that fault type at that point in the sequence A typical sequence would consist of two Inst trips followed by at least one Delayed trip This sequence enables transient faults to be cleared quickly by the Inst trip s and permanent fault to be...

Page 64: ...lay sets the time Reclose Block is allowed to be raised if this time delay expires the Relay will go to Lockout If Reclose Block is cleared before this time expires then the CB Close pulse will be issued at that point in time Dead Time Reclose Blocked Delay Lockout 79 Sequence Fail Timer Sets the time that AutoReclose start can be primed Where this time expires before all the DAR start signals are...

Page 65: ...and is received while a Manual Close operation is in progress the feature is immediately locked out Once the Lockout condition has been reached it will be maintained until reset The following will reset lockout By a Manual Close command from fascia comms or Close CB binary input By a 79 Reset Lockout binary input provided there is no signal present that will cause Lockout At the end of the 79 Mini...

Page 66: ...n Trip5 The fifth and last protection Trip in the P F sequence can be set to either Inst or Delayed 79 P F HighSet Trips to Lockout Sets the number of allowed HighSet trips The relay will go to Lockout on the last HighSet Trip This function can be used to limit the duration and number of high current trips that the Circuit Breaker is required to perform if the fault is permanent and close to the C...

Page 67: ...hich can be mapped to a Binary output to Block an External Protection s fourth Trip Output 79 P F Deadtime 4 Sets the fourth Reclose Delay Deadtime in the External sequence 79 P F Prot n Trip5 Not Blocked Blocked Blocked raises an output which can be mapped to a Binary output to Block an External Protection s fifth Trip Output 79 P F Extern Trips to Lockout Sets the number of allowed External prot...

Page 68: ...7SR210 7SR220 Description of Operation Unrestricted Page 64 of 94 2018 Siemens Protection Devices Limited Figure 4 7 1 Basic Auto Reclose Sequence Diagram ...

Page 69: ...s zero will the close command be issued and related functionality initiated Blocked Close Delay The close command may be delayed by a Block Close CB signal applied to a binary input This causes the feature to pause before it issues the CB close command and can be used for example to delay CB closure until the CB energy has reached an acceptable level If the Block signal has not been removed before...

Page 70: ...proceed when the Busbar voltage is live and the Line is dead 79 Dead Line Dead Bar Close when set to Enabled allows AR to proceed when the Line voltage and the Busbar voltage are dead Manual Close DLDB when set to Enabled allows MC to proceed when the Line voltage and the Busbar voltage are dead 79 Check Sync Close when set to Enabled allows AR to proceed when both the Line and Busbar are consider...

Page 71: ...trates the voltage detector operation Note the area between the dead and live zones is not indeterminate When any voltage is applied to the relay it will ramp up the software RMS algorithm and always pass through the dead zone first A wide range is provided for live and dead voltage detector levels but the live and dead zones must not overlap Figure 4 9 3 1 Voltage Detector Operation Under voltage...

Page 72: ... the slip timer setting If either the phase angle or the voltage elements fall outside of their limits the slip timer is reset If they subsequently come back in then the slip timer has to time out before an output is given This ensures that a close output will not be given if there is a transient disturbance on the system due to e g some remote switching operations 25 Line Undervolts if enabled th...

Page 73: ... indication The mapped LED will stay on for a minimum time or can be latched using non self reset LEDs If the 25 DAR Split Mode setting has been set to COZ the Close On Zero function is started The 25 COZ In Progress can be mapped to an output relay or led for alarm indication If the 25 DAR Split Mode has been set to LO then a 25 System Split LO output is given which can be mapped to an output rel...

Page 74: ...oltage has to be above the line under voltage setting value and also above 5V for an output to be given 25 Bus Undervolts if Enabled the bus voltage has to be above the line under voltage setting value and also above 5V for an output to be given 25 Volt Differential if Enabled the difference between the line and bus voltages has to be less than the V detector setting value for an output to be give...

Page 75: ...the 25 Check Synchronising Voltage monitoring elements but operate in the same way Voltage detectors are provided for each phase input A B C X and inputs Y Z when fitted If the voltage on the respective input is below a set threshold level they can be considered to be dead If the voltages are above a voltage setting they are classed as live Independent voltage detectors are provided for both line ...

Page 76: ...uring the close countdown period the operation can be terminated by pressing Cancel on the fascia Close CB Pulse The duration of the CB Close Pulse is settable to allow a range of CBs to be used The Close pulse will be terminated if any protection pick up operates or a trip occurs This is to prevent Close and Trip Command pulses existing simultaneously A 79 Close On Fault Output is given if a pick...

Page 77: ...yed by the Open CB Delay setting NB During the open countdown period the operation can be terminated by pressing Cancel on the fascia Open CB Pulse The duration of the CB open Command pulse is user settable to allow a range of CBs to be used CB Failed to Open is taken from the Circuit Breaker Failure Element CB Travel Alarm DBI The CB Open and CB Closed binary inputs are continually monitored to t...

Page 78: ...Fault detection This function is used to increase safety when personnel are working in the vicinity of live primary equipment When Hot Line is enabled pickup of any 50 51 50G 51G 50SEF or 51SEF element will cause an instantaneous trip bypassing any time delay setting of the element Any auto reclose sequence will be inhibited and Auto reclose Lockout will be raised This feature is not triggered by ...

Page 79: ...1 Virtual I O energised 0 Virtual I O de energised Example Showing Use of Nomenclature E1 I1 F1 O2 L1 Equation 1 Binary Input 1 XOR Function Key 1 AND NOT Binary Output 2 OR LED 1 When the equation is satisfied 1 it is routed through a pick up timer En Pickup Delay a drop off timer En Dropoff Delay and a counter which instantaneously picks up and increments towards its target En Counter Target The...

Page 80: ...arget the output of the counter En 1 and this value is held until the initiating conditions are removed when En is instantaneously reset The output of En is assigned in the OUTPUT CONFIG OUTPUT MATRIX menu where it can be programmed to any binary output O LED L or Virtual Input Output V combination Protection functions can be used in Quick Logic by mapping them to a Virtual Input Output Refer to A...

Page 81: ... A binary or virtual input assigned to 50BF Mech Trip MENU INPUT CONFIG INPUT MATRIX 50BF Mech Trip CB Fail outputs will be issued providing any of the 3 phase currents are above the 50BF Setting or the current in the fourth CT is above 50BF I4 for longer than the 50BF n Delay setting or for a mechanical protection trip the circuit breaker is still closed when the 50BF n Delay setting has expired ...

Page 82: ...Detection Under normal load conditions rated PPS voltage would be expected along with a PPS load current within the circuit rating Where PPS load current is detected without corresponding PPS voltage this could indicate a three phase VT failure To ensure these conditions are not caused by a 3 phase fault the PPS current must also be below the fault level The element has a 60VTS VPPS setting an 60V...

Page 83: ...ansformer is utilised to provide an additional monitoring function to check the validity of the measured line and busbar voltages When the circuit breaker is closed both voltages should be either Live or Dead If the Bus voltage indicates that the VT is Dead but the corresponding Line voltage is Live this raises the Bus VT Fail output A time delay setting is provided to avoid spurious operations du...

Page 84: ...ed Inhibit 60CTS 60CTS I Pick UP 60CTS I Operated Figure 5 4 1 1 Logic Diagram CT Supervision Function 60CTS I 7SR21 7SR22 5 4 2 60CTS 7SR22 Normally the presence of negative phase sequence NPS current in a power system is accompanied by NPS voltage The presence of NPS current without NPS voltage is used to indicate a current transformer failure The element has a setting for NPS current level 60CT...

Page 85: ...s are identical in operation and independent from each other allowing three trip and three close circuits to be monitored One or more binary inputs can be mapped to 74TCS n The inputs are connected into the trip circuit such that at least one input is energised when the trip circuit wiring is intact If all mapped inputs become de energised due to a break in the trip circuit wiring or loss of suppl...

Page 86: ...ing transformer magnetising inrush conditions The 81HBL2 Bias setting allows the user to select between Phase Sum and Cross methods of measurement Phase Each phase is inhibited separately Sum With this method the square root of the sum of the squares of the second harmonic in each phase is compared to each operate current individually Cross All phases are inhibited when any phase detects an inrush...

Page 87: ... magnetising inrush conditions The 81HBL5 Bias setting allows the user to select between Phase Sum and Cross methods of measurement Phase Each phase is inhibited separately Sum The inrush current from each phase is summated and compared to each operate current individually Cross All phases are inhibited when any phase detects an inrush condition An output is given where the measured fifth harmonic...

Page 88: ... 21LB 3P IPPS sets the level of negative phase sequence current Operation of the element can be inhibited from Inhibit LB A binary input virtual input function key or remote data communications The design of Load Blinder 3Ph makes consideration that protection blocking should be issued only during definable allowable system power flow conditions i e an overcurrent blocking signal can only be issue...

Page 89: ...ividual overcurrent settings per phase Only the under voltage threshold Blinder V block can block the function Distributed generation can cause power flow in reverse direction to normal system operation Load Impedance Blinders are used to block overcurrent operation for loads above a particular level and angle A Blinder is an impedance sensing element with a straight line characteristic when plott...

Page 90: ...t relay so that tripping does not occur for load current levels with a P F 0 94 to Unity R X Phase Fault Block Zone Load Impedance b a Nominal Impedance Z 1p u VL 3 x I c R X Vpps value Point 1 Point 2 Point 3 Point 4 0 360 Trip Level I Vs Z Operate Zone a 21LB 3P Impedance setting b 21LB 3P Angle ve setting c 21LB 3P Angle ve setting Point 6 Point 5 Fwd Block Zone Load Impedance b a c Point 7 Poi...

Page 91: ... detail in the Data Communications Definitions section 6 2 Maintenance The following CB maintenance counters are provided CB Total Trip Count Increments on each trip command issued CB Total Trip Manual Open Selects whether the CB Total Trip Counter is incremented for Manual Open Operations If disabled the CB Total Counter will only increment for protection trip commands CB Delta Trip Count Additio...

Page 92: ...rrent during faults The I2 t value at the time of trip is added to the previously stored value and an alarm is given when any one of the three phase running counts exceeds the set Alarm limit The t value is the time between CB contacts separation when an arc is formed Separation Time and the CB Clearance time The I2 t value can also triggered and reset from a binary input or command 6 2 2 Output M...

Page 93: ...nt number can also be changed The events are selected and edited using the Reydisp software tool 6 3 3 Waveform Records Waveform records provide a trace of the instantaneous magnitude of each analogue input channel and the status of each binary channel i e each binary input binary output virtual I O and LED against time for the duration of the record The values are recorded at every digital sampli...

Page 94: ...at a user defined rate e g 35 days 5 minute intervals and 1 year 1 hour intervals Maximum minimum and mean values of line current voltage and power where applicable are available as instruments which can be read in the relay INSTRUMENTS MENU or via Reydisp Evolution In the menu DATA STORAGE DEMAND DATA LOG The Data Log Period setting is used to define the period between stored samples The Gn Deman...

Page 95: ... W IMPORT REACTIVE VAr EXPORT 0 90 180 90 POWER FACTOR LAGGING ACTIVE W EXPORT REACTIVE VAr EXPORT ACTIVE ENERGY EXPORT watts forward IEC CONVENTION ve watts Figure 6 3 7 1 Energy Direction Convention Setting either the Export Power W or Lag VAr VAr to be ve will reverse the Direction of the Energy transfer for these quantities So forward VAr will then be reported as Imported Reactive Energy and f...

Page 96: ... network simultaneously on different phases of the same circuit which will appear as a phase to phase fault This is known as a Cross Country fault In these cases the measured impedance cannot give an accurate estimate of the fault condition The 7SR22 relay provides detection of this condition using the measured zero sequence voltage to positive sequence voltage ratio U0 U1 to allow the possible cr...

Page 97: ...nabled Enabled Enabled Fault Information Enabled Enabled Enabled Setting Information Enabled Enabled Enabled 6 6 Control Mode This mode provides convenient access to commonly used relay control and test functions When any of the items listed in the Control Mode list are selected control is initiated by pressing the ENTER key The user is prompted to confirm the action again by pressing the ENTER ke...

Page 98: ...inary input When using a binary input an alternative settings group is selected only whilst the input is energised Select Grp Mode Level triggered or latches into the selected group after energisation of the input Select Grp Mode Edge triggered 6 9 Password Feature The relay incorporates two levels of password protection one for settings the other for control functions The programmable password fe...

Page 99: ... permission of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of negligence or any ...

Page 100: ...History 2011 05 2435H85008R7a 7a 7SR210 2435H85009R7a 7a 7SR220 First Release 2013 01 2435H85008R7c 7b 7SR210 2435H85009R7c 7b 7SR220 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line Check on non AR devices Added 74CCS Close Circuit Supervision 2014 06 2435H85008R7f 7d 7SR210 2435H85009R7f 7d 7SR220 Added Fault Locator ...

Page 101: ... 12 2 1 7 Configuring Relay Data Communication 12 2 1 8 Connecting to the Relay via Reydisp Evolution 14 List of Figures Figure 1 1 1 Menu Navigation 4 Figure 1 1 2 Fascia Contrast symbol 4 Figure 1 1 3 Relay Fascia Please note fascia may differ from illustration 5 Figure 1 2 1 1 Relay Identifier Screen 6 Figure 1 2 1 2 Typical Menu Structure for 7SR21 relay 7 Figure 1 2 1 3 Typical Menu Structure...

Page 102: ... current voltage etc Fault Data Mode allows the user to view the type and data of any fault that the relay has detected Control Mode allows the user to control external plant under the relays control for example the CB if allowed via the control mode password Event Data Mode allows the user to view the events which have occured within the relay The menus can be viewed via the LCD by pressing the a...

Page 103: ...7SR210 7SR220 Configuration Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 1 Figure 1 1 3 Relay Fascia Please note fascia may differ from illustration ...

Page 104: ...ay the relays instrumentation and Fault data and to reset the output relays and LED s The five push buttons have the following functions READ DOWN READ UP Used to navigate the menu structure ENTER The ENTER push button is used to initiate and accept setting changes When a setting is displayed pressing the ENTER key will enter the edit mode the setting will flash and can now be changed using the or...

Page 105: ...SERVICE AR TRIP RECLOSE AR TRIP LOCKOUT E F IN HOTLINE WORKING OUT INST PROT N IN IN I OUT CONFIRM ACTION CONFIRM ACTION IN I OUT IN I OUT IN I OUT FAVOURITE METERS CURRENT METERS THERMAL METERS AUTORECLOSE METERS MAINTENANCE METERS GENERAL ALARM METERS BINARY INPUT METERS BINARY OUTPUT METERS VIRTUAL METERS MISCELLANEOUS METERS 7SR21 ARGUS ENTER to CONTROL NUMBER OF FAULTS COMMUNICATIONS MANUAL C...

Page 106: ...UTPUT MATRIX BINARY OUTPUT CONFIG LED CONFIG PICKUP CONFIG CB COUNTERS I 2T CB WEAR NEUTRAL OVERVOLTAGE CONTROL MODE CB TRAVELLING CLOSE I OPEN AR OUT OF SERVICE AR TRIP RECLOSE AR TRIP LOCKOUT E F IN HOTLINE WORKING OUT INST PROT N IN IN I OUT CONFIRM ACTION CONFIRM ACTION IN I OUT IN I OUT IN I OUT FAVOURITE METERS CURRENT METERS VOLTAGE METERS FREQUENCY METERS POWER METERS ENERGY METERS THERMAL...

Page 107: ...site www energy siemens com and found under the submenu Software This software requires windows 2000 service pack 4 or above or windows XP with service pack 2 or above 2 1 Physical Connection The relay can be connected to Reydisp Evolution via any of the communication ports on the relay Suitable communication Interface cable and converters are required depending which port is being used 2 1 1 FRON...

Page 108: ... connection to a PC 2 1 3 OPTIONAL REAR FIBRE OPTIC CONNECTION Figure 2 1 3 1 Additional Optional rear fibre optic connection to a PC Sigma devices have a 25 pin female D connector with the following pin out Pin Function 2 Transmit Data 3 Received Data 4 Request to Send 5 Clear to Send 6 Data set ready 7 Signal Ground 8 Received Line Signal Detector 20 Data Terminal Ready ...

Page 109: ...nal Optional rear RS485 IRIG B connection to a PC 2 1 5 OPTIONAL REAR RS232 IRIG B CONNECTION Figure 2 1 5 1 Additional Optional rear RS232 IRG B connection to a PC Pin Function 1 Carrier Direct CD 2 Receive Data RXD 3 Transmit Data TXD 4 Data Terminal Ready DTR 5 Signal Ground GND 6 Data set ready DSR 7 Request to send RTS 8 Clear to Send CTS 9 Ring Indicator RI ...

Page 110: ...Green LED Physical Link Off No link On Link present Yellow LED Activity Off No traffic On flashing Traffic Figure 2 1 6 1 EN100 Ethernet Module 2 1 7 CONFIGURING RELAY DATA COMMUNICATION Using the keys on the relay fascia scroll down the settings menu s into the communications menu and change the settings for the communication port used on the relay All of the below settings may not be available i...

Page 111: ...rate via Connection Manager Setting COM2 USB Parity NONE ODD EVEN EVEN COM3 Protocol OFF IEC60870 5 103 MODBUS RTU DNP3 0 IEC6 0870 5 103 COM3 This is an optional rear mounted connection COM3 Baud Rate 75 110 150 300 600 1200 2400 4800 9600 19200 38400 57600 115200 57600 COM3 Parity NONE ODD EVEN EVEN COM3 Line Idle LIGHT ON LIGHT OFF LIGHT OFF COM3 Data echo ON OFF OFF COM4 Protocol OFF IEC60870 ...

Page 112: ...ll display all available communication ports With the preferred port highlighted select the Properties option and ensure the baud rate and parity match that selected in the relay Data Comms settings Select Connect to initiate the relay PC connection Figure 2 1 8 1 PC Comm Port Selection Via the Relay Set Address Address set the relay address 1 254 or alternatively search for connected devices usin...

Page 113: ... without the permission of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of neglig...

Page 114: ...Typographical revisions and format 2017 08 Typographical revisions and added data Updated in line with software release 2017 12 Typographical revisions and added data Software Revision History 2011 05 2435H85008R7a 7a 7SR210 First Release 2013 01 2435H85008R7c 7b 7SR210 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line C...

Page 115: ...ram 4 2 Menu Structure 5 1 Relay Instrumentation 6 1 1 Favourite Meters 6 1 2 Current Meters 6 1 3 Thermal Meters 8 1 4 Auto Reclose Meters 8 1 5 Maintenance Meters 8 1 6 General Alarm Meters 9 1 7 Demand Meters 9 1 8 Binary Input Meters 10 1 9 Binary Output Meters 11 1 10 Virtual Meters 11 1 11 Communication Meters 11 1 12 Miscellaneous Meters 12 1 13 Quick Logic Meters 12 ...

Page 116: ...7SR210 Instrumentation Guide Unrestricted Page 4 of 12 2018 Siemens Protection Devices Limited 1 Function Diagram ...

Page 117: ...7SR210 Instrumentation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 12 2 Menu Structure ...

Page 118: ...s Instrument Description CURRENT METERS to view This is the sub group that includes all the meters that are associated with Current TEST RESET allows access to this sub group Primary Current Ia 0 00A Ib 0 00A Ic 0 00A Displays the 3 phase currents Primary RMS values Secondary Current Ia 0 00A Ib 0 00A Ic 0 00A Displays the 3 phase currents Secondary RMS values Nom Current Ia 0 00xIn o Ib 0 00xIn o...

Page 119: ...Instrument Description 5th Harmonic Current Ia 0 00xIn Ib 0 00xIn Ic 0 00xIn Displays the 3 phase currents 5 th Harmonic components Nominal RMS values Last Trip P F Ia 0 00A Ib 0 00A Ic 0 00A Displays the Last Trip Fault Current Last Trip E F In 0 00A Ig 0 00A Displays the Last Trip Fault Current ...

Page 120: ...tus Out Of Service Close Shot 0 Status of the autoreclose 1 5 Maintenance Meters Instrument Description MAINTENANCE METERS to view This is the sub group that includes all the meters that are associated with Maintenance TEST RESET allows access to this sub group CB Total Trips Count 0 Target 100 Displays the number of CB trips experienced by the CB CB Phase A Trips Count 0 Target 100 Displays the n...

Page 121: ...s the current measure of circuit breaker wear remaining CB Trip Time 0 0ms Displays the trip time for the circuit breaker 1 6 General Alarm Meters Instrument Description GENERAL ALARM METERS to view This is the sub group that includes all the meters that are associated with the Binary inputs TEST RESET allows access to this sub group General Alarms ALARM 1 Cleared Displays the state of General Ala...

Page 122: ...hows the Max Min and Mean for Power Q 3P Demand Power S 3P Demand Max 0 00VA Min 0 00VA Mean 0 00VA Shows the Max Min and Mean for Power S 3P Demand 1 8 Binary Input Meters Instrument Description BINARY INPUT METERS to view This is the sub group that includes all the meters that are associated with the Binary inputs TEST RESET allows access to this sub group BI 1 8 BI 9 16 BI 17 24 BI 25 32 BI 33 ...

Page 123: ...e of the virtual status inputs in the relay TEST RESET allows access to this sub group V 1 8 V 9 16 Displays the state of Virtual Outputs 1 to 16 The number of virtual inputs will vary depending on model 1 11 Communication Meters Instrument Description COMMUNICATION METERS to view This is the sub group that includes all the meters that are associated with Communications ports TEST RESET allows acc...

Page 124: ...elay Event Recs 0 Data Log Recs 0 Settings Group 1 This meter displays the number of Event Records Data Log Records and the Active Settings Group number stored in the relay 1 13 Quick Logic Meters Instrument Description QUICK LOGIC METERS to view This is the sub group that includes all the meters that are associated with QuickLogic TEST RESET allows access to this sub group E 1 8 E 9 16 Shows the ...

Page 125: ...tem without the permission of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of neg...

Page 126: ...added data Updated in line with software release 2017 12 Typographical revisions and added data Software Revision History 2011 05 2435H85008R7a 7a 7SR210 First Release 2013 01 2435H85008R7c 7b 7SR210 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line Check on non AR devices Added 74CCS Close Circuit Supervision 2014 06 24...

Page 127: ... 50 2 11 3 4 2 Cold Load 11 3 4 3 Derived E F 12 3 4 3 1 51N 1 12 3 4 3 2 51N 2 13 3 4 3 3 50N 1 13 3 4 3 4 50N 2 13 3 4 4 Measured E F 14 3 4 4 1 51G 1 14 3 4 4 2 51G 2 14 3 4 4 3 50G 1 15 3 4 4 4 50G 2 15 3 4 5 Sensitive E F 15 3 4 5 1 51SEF 1 15 3 4 5 2 51SEF 2 16 3 4 5 3 50SEF 1 16 3 4 5 4 50SEF 2 16 3 4 6 Restricted E F 17 3 4 7 NPS Overcurrent 17 3 4 7 1 46IT 17 3 4 7 2 46DT 17 3 4 8 Under C...

Page 128: ...24 3 6 2 4 Extern Shots 24 3 6 3 Manual Close 24 3 6 4 Circuit Breaker 25 3 6 5 QUICK LOGIC 25 3 7 Input Config 33 3 7 1 Input Matrix 33 3 7 2 Binary Input Config 40 3 7 3 General Alarms 41 3 8 Output Config 42 3 8 1 Output Matrix 42 3 8 2 Binary Output Config 55 3 8 3 LED Config 56 3 8 4 Pickup Config 56 3 9 CB Maintenance 57 3 9 1 CB Counters 57 3 9 2 I 2T CB Wear 58 3 9 3 START COUNT 58 3 10 Da...

Page 129: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 61 1 Function Diagram ...

Page 130: ...7SR210 Settings Guide Unrestricted Page 6 of 61 2018 Siemens Protection Devices Limited 2 Menu Structure ...

Page 131: ... the Relay Fascia xNom Primary Secondary xNom E F Curr Set Display As Above xNom Primary Secondary xNom Select Grp Mode Mode of operation of the group change from status input Edge triggered ignores the status input once it has changed to the relevant group where as with Level triggered the relay will only stay in the group it has changed to whilst the status input is being driven after which it r...

Page 132: ...nctional and all associated settings will be hidden The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate Enabled Disabled Disabled Gn Derived E F When set to Disabled no Derived E F elements will be functional and all associated settings will be hidden The Setting Dependencies setting being set to Disabled will make all settings v...

Page 133: ...Cct Supervision When set to Disabled no Trip Cct Supervision elements will be functional and all associated settings will be hidden The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate Enabled Disabled Disabled Gn Close Cct Supervision When set to Disabled no Close Cct Supervision elements will be functional and all associated set...

Page 134: ...me of element 0 0 01 19 99 20 0 s Gn 51 1 Follower DTL Additional definite time added after characteristic time 0 0 01 19 99 20 0 s Gn 51 1 Reset Selects between an ANSI decaying reset characteristic or a definite time reset ANSI Decaying 0 59 60 0 s Gn 51 1 Inrush Action Selects if the 51 1 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 1 2 51 2 D...

Page 135: ...led Disabled Gn 50 2 Setting Pickup level 0 05 0 06 49 5 50 1 xIn Gn 50 2 Delay Sets operate delay time 0 0 01 14300 14400 0 s Gn 50 2 Inrush Action Selects if the 50 2 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 2 Cold Load Description Range Default Cold Load Selects whether the Cold Load element is enabled Disabled Enabled Disabled Pick up Tim...

Page 136: ...operates 0 0 01 19 99 20 5 s Gn 51c 2 Min Operate Time 51 2 element parameter used when Cold Load operates 0 0 01 19 99 20 0 s Gn 51c 2 Follower DTL 51 2 element parameter used when Cold Load operates 0 0 01 19 99 20 0 s Gn 51c 2 Reset 51 2 element parameter used when Cold Load operates ANSI Decaying 0 59 60 0 s 3 4 3 Derived E F 3 4 3 1 51N 1 Description Range Default Gn 51N 1 Element Selects whe...

Page 137: ...DTL Additional definite time added after characteristic time 0 0 01 19 99 20 0 s Gn 51N 2 Reset Selects between an ANSI decaying reset characteristic or a definite time reset ANSI Decaying 0 59 60 0 s Gn 51N 2 Inrush Action Selects if the 51N 2 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 3 3 50N 1 Description Range Default Gn 50N 1 Element Selec...

Page 138: ...onal definite time added after characteristic time 0 0 01 19 99 20 0 s Gn 51G 1 Reset Selects between an ANSI decaying reset characteristic or DTL reset ANSI Decaying 0 59 60 0 s Gn 51G 1 Inrush Action Selects if the 51G 1 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 4 2 51G 2 Description Range Default Gn 51G 2 Element Selects whether the 51G 2 I...

Page 139: ... 0 005 0 006 24 95 25 0 5 xIn Gn 50G 2 Delay Sets operate delay time 0 0 01 14300 14400 0 s Gn 50G 2 Inrush Action Selects if the 50G 2 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 5 Sensitive E F 3 4 5 1 51SEF 1 Description Range Default Gn 51SEF 1 Element Selects whether the 51SEF 1 IDMTL Sensitive Earth Fault element is enabled Disabled Enable...

Page 140: ... 2 Delay DTL Delay applicable only when DTL is selected for characteristic 0 0 01 19 99 20 5 s Gn 51SEF 2 Min Operate Time Minimum operate time of element 0 0 01 19 99 20 0 s Gn 51SEF 2 Follower DTL Additional definite time added after characteristic time 0 0 01 19 99 20 0 s Gn 51SEF 2 Reset Selects between an ANSI decaying reset characteristic or DTL reset ANSI Decaying 0 59 60 0 s 3 4 5 3 50SEF ...

Page 141: ...2 5 0 25 xIn Gn 46IT Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL DTL IEC NI IEC VI IEC EI IEC LTI ANSI MI ANSI VI ANSI EI IEC NI Gn 46IT Time Mult IEC ANSI Time multiplier applicable to IEC and ANSI curves but not DTL selection 0 025 0 03 1 595 1 6 1 7 4 9 5 6 100 1 Gn 46IT Delay DTL Delay applicable only when DTL is selected for characteristic 0 0 01 19 99 20 5 s Gn 46IT Rese...

Page 142: ... 2 Description Range Default Gn 37 2 Element Phase under current element 37 2 Disabled Enabled Disabled Gn 37 2 Setting Pickup level 0 05 0 1 4 95 5 0 25 xIn Gn 37 2 Delay Sets operate delay time 0 0 01 14300 14400 0 s 3 4 8 3 37G 1 Description Range Default Gn 37G 1 Element Disabled Enabled Disabled Gn 37G 1 Setting 0 005 0 006 4 995 5 0 2 xIn Gn 37G 1 Delay 0 0 01 14300 14400 0 s 3 4 8 4 37G 2 D...

Page 143: ...ash Detector element is enabled Disabled Enabled Disabled Gn 50AFD Setting Pickup level 1 2 10 2 xIn 3 5 Supervision 3 5 1 CB Fail Description Range Default Gn 50BF Element Selects whether the Circuit Breaker Fail element is enabled Disabled Enabled Disabled Gn 50BF Setting Breaker Fail Current Pickup level If the current falls below this level then the CB is deemed to have opened and the element ...

Page 144: ... 2 is enabled Disabled Enabled Disabled Gn 74TCS 2 Delay Time delay before trip circuit supervision operates 0 0 02 59 98 60 0 4 s Gn 74TCS 3 Selects whether the trip circuit supervision element 74TCS 3 is enabled Disabled Enabled Disabled Gn 74TCS 3 Delay Time delay before trip circuit supervision operates 0 0 02 59 98 60 0 4 s 3 5 5 Close CCT Supervision Description Range Default Gn 74CCS 1 Sele...

Page 145: ...elements can cause only Delayed protection to be used Combination of 51N 1 51N 2 50N 1 50N 2 51G 1 51G 2 50G 1 50G 2 Gn 79 SEF Inst Trips Selects which sensitive earth fault protection elements are classed as Instantaneous elements and start an autoreclose sequence These will be blocked from operating during Delayed autoreclose sequences See autoreclose section of manual for detail of what element...

Page 146: ... Trip starter conditions have not been cleared after Sequence Fail Time 0 1 599 600 60 s Gn 79 Sequence Co ord Selects whether Sequence co ordination functionality is used or not Disabled Enabled Enabled Gn 79 Cold Load Action Selects whether the relay will perform Delayed Trips or not when Cold Load is active Off Delayed Off 3 6 2 1 P F Shots Description Range Default Gn 79 P F Prot n Trip 1 Sele...

Page 147: ...d 0 0 1 14300 14400 5 s Gn 79 E F Prot n Trip 2 Selects whether the second earth fault trip is Instantaneous Fast or Delayed When set to Delayed all E F Inst Trips will be Inhibited for this shot Inst Delayed Inst Gn 79 E F Deadtime 2 Time period between the fault being cleared and the close pulse being issued 0 0 1 14300 14400 5 s Gn 79 E F Prot n Trip 3 Selects whether the third earth fault trip...

Page 148: ...itive earth fault trip is Instantaneous or Delayed When set to Delayed all SEF Inst Trips will be Inhibited for this shot Inst Delayed Delayed Gn 79 SEF Deadtime 4 Time period between the fault being cleared and the close pulse being issued 0 0 1 14300 14400 5 s Gn 79 SEF Prot n Trip 5 Selects whether the fifth sensitive earth fault trip is Instantaneous or Delayed When set to Delayed all SEF Inst...

Page 149: ...er a CB has closed and remained closed before the reclosure is deemed to be successful and the AR is re initialised If the CB remains open at the end of the reclaim time then the AR goes to lockout 0 1 599 600 2 s Gn Minimum LO Delay 0 1 599 600 2 s Gn Reset LO By Timer Disabled Enabled Enabled Gn Trip Time Alarm An alarm is issued when the Trip time is exceeded 0 0 01 1 99 2 0 2 s Gn Trip Time Ad...

Page 150: ... NOT operation AND operation EXCLUSIVE OR operationE followed by a digit Equation numberF Followed by a digit Function Key numberI Followed by a digit Binary Input numberL Followed by a digit LED numberO Followed by a digit output relay numberV Followed by a digit Virtual Input Output number ExamplesMake a function key LED toggle when function key is pressed requires E1 to drive L11 in output matr...

Page 151: ...Pickup Delay Time before equation output operates after equation satisfied 0 0 01 14300 14400 0 s E4 Dropoff Delay Time before equation output resets after equation nolonger satisfied 0 0 01 14300 14400 0 s E4 Counter Target Select number of times equation must be satisfied before equation output operates 1 2 998 999 1 E4 Counter Reset Mode Select type of counter reset mode Off Multi shot Single s...

Page 152: ...ore equation output operates 1 2 998 999 1 E6 Counter Reset Mode Select type of counter reset mode Off Multi shot Single shot Off E6 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E7 Equation Enable or Disable logic equation E7 Disabled Enabled Disabled E7 Specify logic equations of the form En Operand Operator Operand using the following 0123456789 Digit Parenthesis NOT opera...

Page 153: ...OT operation AND operation EXCLUSIVE OR operationE followed by a digit Equation numberF Followed by a digit Function Key numberI Followed by a digit Binary Input numberL Followed by a digit LED numberO Followed by a digit output relay numberV Followed by a digit Virtual Input Output number ExamplesMake a function key LED toggle when function key is pressed requires E1 to drive L11 in output matrix...

Page 154: ...ickup Delay Time before equation output operates after equation satisfied 0 0 01 14300 14400 0 s E11 Dropoff Delay Time before equation output resets after equation nolonger satisfied 0 0 01 14300 14400 0 s E11 Counter Target Select number of times equation must be satisfied before equation output operates 1 2 998 999 1 E11 Counter Reset Mode Select type of counter reset mode Off Multi shot Single...

Page 155: ...e equation output operates 1 2 998 999 1 E13 Counter Reset Mode Select type of counter reset mode Off Multi shot Single shot Off E13 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E14 Equation Enable or Disable logic equation E14 Disabled Enabled Disabled E14 Specify logic equations of the form En Operand Operator Operand using the following 0123456789 Digit Parenthesis NOT op...

Page 156: ...ounter reset mode Off Multi shot Single shot Off E15 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E16 Equation Enable or Disable logic equation E16 Disabled Enabled Disabled E16 Specify logic equations of the form En Operand Operator Operand using the following 0123456789 Digit Parenthesis NOT operation AND operation EXCLUSIVE OR operationE followed by a digit Equation numbe...

Page 157: ...cts which inputs inhibit the 51N 2 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 50N 1 Selects which inputs inhibit the 50N 1 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 50N 2 Selects which inputs inhibit the 50N 2 element Combination of BI1 BI2 ...

Page 158: ...4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 37 2 Selects which inputs inhibit the 37 2 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 37G 1 Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 37G 2 Combination of BI1 BI2 B...

Page 159: ...7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 50BF Ext Trip Selects which inputs can also start the 50BF element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Reset CB Total Trip Selects which inputs Reset the CB Total Trip count Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V...

Page 160: ...which inputs will activate the General Alarm 8 text Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 General Alarm 9 Selects which inputs will activate the General Alarm 9 text Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 General Alarm 10 Selects which inputs will activate the Gene...

Page 161: ...elements required to start an Auto reclose sequence Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 79 Block Reclose Selects which inputs will block the Auto recloser Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 79 Reset Lockout Selects which inputs will force the Auto recloser in...

Page 162: ...V12 V13 V14 V15 V16 Select Group 2 Switches active setting group to group 2 Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Select Group 3 Switches active setting group to group 3 Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Select Group 4 Switches active setting group to group 4 ...

Page 163: ... BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Reset LEDs O Ps Selects which inputs will reset the latched LEDs and binary outputs Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inverted Inputs Selects which inputs will be inverted Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 Enabl...

Page 164: ...Delay Delay on dropoff of DC Binary Input 1 0 0 005 14300 14400 0 s BI 39 Pick up Delay Delay on pickup of DC Binary Input 9 0 0 005 14300 14400 0 02 s BI 39 Drop off Delay Delay on dropoff of DC Binary Input 9 0 0 005 14300 14400 0 s Enabled In Local Selects which inputs are enabled when the relay is in Operating Mode Local or Local Or Remote Combination of 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 Ena...

Page 165: ...splayed for General Alarm 9 16 Character String ALARM 9 General Alarm 10 Defines the text to be displayed for General Alarm 10 16 Character String ALARM 10 General Alarm 11 Defines the text to be displayed for General Alarm 11 16 Character String ALARM 11 General Alarm 12 Defines the text to be displayed for General Alarm 11 16 Character String ALARM 12 General Alarm 13 Defines the text to be disp...

Page 166: ...ng Grp 3 Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Active Setting Grp 4 Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Active Setting...

Page 167: ...7 V8 V9 V10 V11 V12 V13 V14 V15 V16 L4 50N 1 50N 1 INST DTL derived Earth Fault operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 L4 50N 2 50N 2 INST DTL derived Earth Fault operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 L4 51G...

Page 168: ...TL NPS Overcurrent operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 46DT INST DTL NPS Overcurrent operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 37 1 37 1 Under Current operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L...

Page 169: ...O10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 74CCS 2 Close Circuit 2 fail operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 74CCS 3 Close Circuit 3 fail operated Combination of BO1 B...

Page 170: ...eded Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 CB Ph A Trip Count Total CB Ph A trip count exceeded Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 CB Ph B Trip Count Total CB Ph B trip ...

Page 171: ...r is in the closed position Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Close CB Blocked Indicates that the Close CB control is blocked by its interlocking logic Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 CB Alarm Indicates the CB is e...

Page 172: ...13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 50AFD PhA Arc Flash Detector Phase A operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 50AFD PhB Arc Flash Detector Phase B operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO...

Page 173: ... L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 AFD Zone 3 Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 AFD Zone 4 Flash Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V...

Page 174: ...ing correctly with the Protection CPU Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 En100 Error Raised when the En100 has detected an Error Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2...

Page 175: ...14 V15 V16 79 In Progress Indicates an auto reclose sequence is in progress Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 79 Block Extern Indicates that Extern for the current shot has been selected to be delayed This may be used to block external tripping elements in the same way as the internal protection elements ar...

Page 176: ...er has stored new information Note this is a pulsed output Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Out Of Service Mode Indicates the relay is in Out Of Service Mode Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Local Mode Indicates th...

Page 177: ...BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 E2 Quick Logic equation 2 operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 E3 Quick Logic equation 3 operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10...

Page 178: ...9 V10 V11 V12 V13 V14 V15 V16 E14 Quick Logic equation 14 operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 E15 Quick Logic equation 15 operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 L1 L2 L3 L4 L5 L6 L7 L8 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 E16 Quick Logic equation 16 operated Combina...

Page 179: ...nications link or by removing DC Supply By default relays are Self Resetting and will reset when the driving signal is removed Combination of 1 to 16 Min Operate Time 1 Minimum operate time of output relay if set to self reset if also set to be pulsed then this is the pulse width 0 0 01 59 60 0 1 s Min Operate Time 8 Minimum operate time of output relay 8 if set to self reset if also set to be pul...

Page 180: ...n of 1 to 32 Red LEDs Selects which LEDs will be red when driven Combination of 1 to 32 1 to 32 PU Green LEDs Selects which LEDs will be green when driven by a pickup Combination of 1 to 32 1 to 32 PU Red LEDs Selects which LEDs will be red when driven by a pickup Combination of 1 to 32 1 to 32 3 8 4 Pickup Config Description Range Default Gn P F Pickups When any of the selected pickups operate Ge...

Page 181: ...1 9999 10000 100 Gn CB E F Trip Count Target Selects the number of CB trips allowed before CB E F Trip Count counter output operates 0 1 9999 10000 100 Gn CB Delta Trip Count Selects whether the CB Delta Trip Count counter is enabled Disabled Enabled Disabled Gn CB Delta Trip Count Target Selects the number of CB trips allowed before CB Delta Trip Count counter output operates 0 1 9999 10000 100 G...

Page 182: ... 04 s Reset I 2t Count Reset the CB wear count 3 9 3 START COUNT Description Range Default Start Types s Selects which type of start up Power On Expected Unexpected All Start Count Target Selects number of times star up has occurred before output operatest 0 10000 100 3 10 Data Storage 3 10 1 Demand Data Log Description Range Default Data Log Period Selects period between stored samples 5 6 7 8 9 ...

Page 183: ...p 49 Alarm 37G 1 37G 2 Gn AFD Trig Storage As Above Combination of AFD 1 AFD 2 AFD 3 AFD 4 AFD 5 AFD 6 Pre trigger Storage Select Percentage of waveform record stored before the fault is triggered 10 20 30 40 50 60 70 80 90 20 Record Duration Select waveform record duration 10 Rec x 1 Sec 5 Rec x 2 Sec 2 Rec x 5 Sec 1 Rec x 10 Sec 10 Rec x 1 Sec Trigger Waveform Trigger waveform storage Clear Wave...

Page 184: ...is used NONE ODD EVEN EVEN COM3 Line Idle Selects the communications line idle sense LIGHT OFF LIGHT ON LIGHT OFF COM3 Data Echo Enables echoing of data from RX port to TX port when operating relays in a Fibre Optic ring configuration OFF ON OFF COM3 Mode Local Remote Local Or Remote Remote COM4 Protocol Selects protocol to use for COM4 OFF IEC60870 5 103 MODBUS RTU DNP3 OFF COM4 Baud Rate Sets th...

Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...

Page 186: ...out the permission of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of negligence ...

Page 187: ...phical revisions and added data Software Revision History 2011 05 2435H85009R7a 7a 7SR220 First Release 2013 01 2435H85009R7c 7b 7SR220 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line Check on non AR devices Added 74CCS Close Circuit Supervision 2014 06 2435H85009R7f 7d 7SR220 Added Fault Locator feature and Check Sync...

Page 188: ...age Meters 8 1 4 Frequency Meters 8 1 5 Power Meters 10 1 6 Energy Meters 12 1 7 WATTMETRIC Meters 12 1 8 Directional Meters 12 1 9 Thermal Meters 12 1 10 Auto Reclose Meters 14 1 11 Synchronising Meters 14 1 12 Maintenance Meters 14 1 13 General Alarm Meters 16 1 14 Demand Meters 16 1 15 Binary Input Meters 17 1 16 Binary Output Meters 17 1 17 Virtual Meters 19 1 18 Communication Meters 19 Miscel...

Page 189: ...7SR220 Instrumentation Guide Page 4 of 20 2017 Siemens Protection Devices Limited 1 Function Diagram ...

Page 190: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 5 of 20 2 Menu Structure ...

Page 191: ...ument Description CURRENT METERS to view This is the sub group that includes all the meters that are associated with Current TEST RESET allows access to this sub group Primary Current Ia 0 00A Ib 0 00A Ic 0 00A Displays the 3 phase currents Primary RMS values Secondary Current Ia 0 00A Ib 0 00A Ic 0 00A Displays the 3 phase currents Secondary RMS values Nom Current Ia 0 00xIn o Ib 0 00xIn o Ic 0 0...

Page 192: ...ent Description 5th Harmonic Current Ia 0 00xIn Ib 0 00xIn Ic 0 00xIn Displays the 3 phase currents 5 th Harmonic components Nominal RMS values Last Trip P F Ia 0 00A Ib 0 00A Ic 0 00A Displays the Last Trip Fault Current Last Trip E F In 0 00A Ig 0 00A Displays the Last Trip Fault Current ...

Page 193: ...MS values Angles with respect to PPS voltage Nom Ph N Voltage Va 0 00xVn o Vb 0 00xVn o Vc 0 00xVn o Displays the Phase to Neutral Voltage Nominal RMS values V Seq Components Izps 0 00V o Ipps 0 00V o Inps 0 00V o Displays the Voltage Sequence components Nominal RMS values phase angles with respect to PPS voltage Calc Earth Voltage Pri 0 00V Sec 0 00V o Displays the calculated Earth voltage both p...

Page 194: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 9 of 20 Frequency 0 000Hz ...

Page 195: ...0 0VAr Phase B 0 0VAr Phase C 0 0VAr Displays Primary Reactive Power Secondary Power Q Phase A 0 0VAr Phase B 0 0VAr Phase C 0 0VAr Displays Secondary Reactive Power Nominal Power Q Phase A 0 00xSn Phase B 0 00xSn Phase C 0 00xSn Displays Nominal Reactive Power Primary Power S Phase A 0 0VA Phase B 0 0VA Phase C 0 0VA Displays Primary Apparent Power Secondary Power S Phase A 0 0VAr Phase B 0 0VAr ...

Page 196: ...P 32S 0 0W Q 32S 0 0VAr S 32S 0 0VA Displays 3 Phase Primary Power 32S Secondary Power 32S P 32S 0 0W Q 32S 0 0VAr S 32S 0 0VA Displays 3 Phase Secondary Power 32S Nominal Power 32S P 32S 0 00xSn Q 32S 0 00xSn S 32S 0 00xSn Displays 3 Phase Nominal Power 32S Power Factor 32S PF 32S 0 00 Displays Power Factor 32S ...

Page 197: ...e Wattmetric component of residual current Wattmetric residual power Compensated residual phase angle Applied residual phase angle 1 8 Directional Meters Instrument Description DIRECTIONAL METERS to view This is the sub group that includes all the meters that are associated with Directional elements TEST RESET allows access to this sub group Only seen on models that have the 67 option P F Dir 67 N...

Page 198: ...2017 Siemens Protection Devices Limited Page 13 of 20 Instrument Description THERMAL METERS to view Thermal TEST RESET allows access to this sub group Thermal Status Phase A 0 0 Phase B 0 0 Phase C 0 0 Displays the thermal capacity ...

Page 199: ...ulated synchronising parameters in models that include this function 1 12 Maintenance Meters Instrument Description MAINTENANCE METERS to view This is the sub group that includes all the meters that are associated with Maintenance TEST RESET allows access to this sub group CB Total Trips Count 0 Target 100 Displays the number of CB trips experienced by the CB CB Phase A Trips Count 0 Target 100 Di...

Page 200: ... over the last rolling 1 hr period When the target is reached the relay will only do 1 Delayed Trip to Lockout CB Wear Phase A 0 00MA 2s Phase B 0 00MA 2s Phase C 0 00MA 2s Displays the current measure of circuit breaker wear CB Wear Remaining Phase A 100 Phase B 100 Phase C 100 Displays the current measure of circuit breaker wear remaining CB Trip Time 0 0ms Displays the trip time for the circuit...

Page 201: ... with the demand metering TEST RESET allows access to this sub group V Phase A Demand Max 0 00V Min 0 00V Mean 0 00V Shows the Max Min and Mean Voltage for Phase A V Phase B Demand Max 0 00V Min 0 00V Mean 0 00V Shows the Max Min and Mean Voltage for Phase AB V Phase C Demand Max 0 00V Min 0 00V Mean 0 00V Shows the Max Min and Mean Voltage for Phase AC V Phase AB Demand Max 0 00V Min 0 00V Mean 0...

Page 202: ...00VA Shows the Max Min and Mean for Power S 3P Demand Frequency Demand Max 0 000Hz Min 0 000Hz Mean 0 000Hz Shows the Max Min and Mean for System Frequency Demand Power Factor 3P Demand Max 0 00 Min 0 00 Mean 0 00 Shows the Max Min and Mean for System Power Factor 3P Demand 1 15 Binary Input Meters Instrument Description BINARY INPUT METERS to view This is the sub group that includes all the meter...

Page 203: ...Instrumentation Guide Page 18 of 20 2017 Siemens Protection Devices Limited Instrument Description BO 1 8 Displays the state of DC binary Outputs 1 to 8 The number of binary outputs may vary depending on model ...

Page 204: ... RESET allows access to this sub group COM1 COM2 COM3 COM4 Displays which com ports are currently active COM1 TRAFFIC Tx1 0 Rx1 0 Rx1 Errors 0 Displays traffic on Com1 COM2 TRAFFIC Tx2 0 Rx2 0 Rx2 Errors 0 Displays traffic on Com2 COM3 TRAFFIC Tx3 0 Rx3 0 Rx3 Errors 0 Displays traffic on Com3 COM4 TRAFFIC Tx4 0 Rx4 0 Rx4 Errors 0 Displays traffic on Com4 EN100 INFORMATION Version EN100 Version Inf...

Page 205: ...d in the relay 1 19 Quick Logic Meters Instrument Description QUICK LOGIC METERS to view This is the sub group that includes all the meters that are associated with QuickLogic TEST RESET allows access to this sub group E 1 8 E 9 16 Shows the state of all the equations E1 Equation EQN 0 TMR 0 0 0 CNT 0 1 0 Shows the state of an individual equation EQN shows the equation state TMR shows the timer pr...

Page 206: ...ystem without the permission of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of n...

Page 207: ...17 12 Typographical revisions and added data Software Revision History 2011 05 2435H85009R7a 7a 7SR220 First Release 2013 01 2435H85009R7c 7b 7SR220 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line Check on non AR devices Added 74CCS Close Circuit Supervision 2014 06 2435H85009R7f 7d 7SR220 Added Fault Locator feature a...

Page 208: ...4 1 3 51 3 14 3 4 1 4 51 4 15 3 4 1 5 50 1 15 3 4 1 6 50 2 16 3 4 1 7 50 3 16 3 4 1 8 50 4 17 3 4 2 Voltage Controlled O C 17 3 4 3 Cold Load 18 3 4 4 Derived E F 19 3 4 4 1 51N 1 19 3 4 4 2 51N 2 20 3 4 4 3 51N 3 20 3 4 4 4 51N 4 21 3 4 4 5 50N 1 22 3 4 4 6 50N 2 22 3 4 4 7 50N 3 22 3 4 4 8 50N 4 23 3 4 5 Measured E F 23 3 4 5 1 51G 1 23 3 4 5 2 51G 2 24 3 4 5 3 51G 3 25 3 4 5 4 51G 4 25 3 4 5 5 ...

Page 209: ...C Flash Detector 33 3 5 Voltage Protection 33 3 5 1 Phase U O Voltage 33 3 5 2 27 59 1 34 3 5 3 27 59 2 34 3 5 4 27 59 3 35 3 5 5 27 59 4 35 3 6 Vx U O Voltage 36 3 7 NPS Overvoltage 36 3 7 1 47 1 36 3 7 2 47 2 36 3 8 Neutral Overvoltage 37 3 8 1 59NIT 37 3 8 2 59NDT 37 3 9 U O Frequency 37 3 9 1 81 1 38 3 9 2 81 2 38 3 9 3 81 3 38 3 9 4 81 4 39 3 9 5 81 5 39 3 9 6 81 6 40 3 10 Supervision 40 3 10...

Page 210: ...QUICK LOGIC 49 3 12 Input Config 58 3 12 1 Input Matrix 58 3 12 2 Function Key Matrix 71 3 12 3 Binary Input Config 73 3 12 4 Function Key Config 74 3 12 5 General Alarms 75 3 13 Output Config 76 3 13 1 Output Matrix 76 3 13 2 Binary Output Config 99 3 13 3 LED Config 100 3 13 4 Pickup Config 101 3 14 Maintenance 101 3 14 1 CB Counters 102 3 14 2 I 2T CB Wear 102 3 14 3 START COUNT 103 3 15 Data S...

Page 211: ...7SR220 Settings Guide Unrestricted Page 6 of 107 2013 Siemens Protection Devices Limited 1 Function Diagram ...

Page 212: ...Y MATRIX BINARY INPUT CONFIG OUTPUT MATRIX BINARY OUTPUT CONFIG LED CONFIG PICKUP CONFIG CB COUNTERS I 2T CB WEAR NEUTRAL OVERVOLTAGE CONTROL MODE CB TRAVELLING CLOSE I OPEN AR OUT OF SERVICE AR TRIP RECLOSE AR TRIP LOCKOUT E F IN HOTLINE WORKING OUT INST PROT N IN IN I OUT CONFIRM ACTION CONFIRM ACTION IN I OUT IN I OUT IN I OUT FAVOURITE METERS CURRENT METERS VOLTAGE METERS FREQUENCY METERS POWE...

Page 213: ...wn in terms of x Nominal Primary or Secondary values on the Relay Fascia xNom Primary Secondary xNom E F Curr Set Display As Above xNom Primary Secondary xNom SEF REF Curr Set Display As Above xNom Primary Secondary xNom Export Power Lag VAr Selects the signs required for exporting power and lagging VArs ve ve ve ve ve ve ve ve ve ve Select Grp Mode Mode of operation of the group change from statu...

Page 214: ...o get back to Phase Nom Voltage 20 19 9 19 9 20 0 V Phase Voltage Trim Angle Allows trimming of voltage angle the setting value is added to the current voltage angle 45 44 9 44 9 45 0 deg Phase Voltage Config Required to allow for different types of physical VT connections Van Vbn Vcn Vab Vbc 3V0 Va Vb Vc Van Vbn Vcn Phase VT Ratio Prim 6 Character String 132000 V Phase VT Ratio Sec 40 40 5 159 5 ...

Page 215: ...elements will be functional and all associated settings will be hidden The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate Enabled Disabled Disabled Gn Derived E F When set to Disabled no Derived E F elements will be functional and all associated settings will be hidden The Setting Dependencies setting being set to Disabled will ...

Page 216: ...ll be hidden The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate Enabled Disabled Disabled Gn U O Frequency When set to Disabled no U O Frequency elements will be functional and all associated settings will be hidden The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to o...

Page 217: ...abled Gn I 2t CB Wear When set to Disabled no Gn I 2t CB Wear elements will be functional and all associated settings will be hidden The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate Enabled Disabled Disabled Gn Arc Flash Detector When set to Disabled no Arc Flash Detector elements will be functional and all associated settings...

Page 218: ... Inhibit Non Dir Off Gn 51 1 Inrush Action Selects if the 51 1 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off Gn 51 1 21LB 3P Action Selects if operation of the 51 1 element is blocked for defined load conditions Off Inhibit Inhibit Gn 51 1 21LB 1P Action Selects if operation of the 51 1 element is blocked for defined load conditions Off Inhibit Off 3 ...

Page 219: ...ing Pickup level 0 05 0 06 2 49 2 5 1 xIn Gn 51 3 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL DTL IEC NI IEC VI IEC EI IEC LTI ANSI MI ANSI VI ANSI EI IEC NI Gn 51 3 Time Mult IEC ANSI Time multiplier applicable to IEC and ANSI curves but not DTL selection 0 025 0 03 1 595 1 6 1 7 4 9 5 6 100 1 Gn 51 3 Delay DTL Delay applicable only when DTL is selected for characteristic 0 0...

Page 220: ... 0 01 19 99 20 0 s Gn 51 4 Reset Selects between an ANSI decaying reset characteristic or a definite time reset ANSI Decaying 0 59 60 0 s Gn 51 4 VTS Action Selects whether 51 4 element is blocked or made non directional when VTS operates Off Inhibit Non Dir Off Gn 51 4 Inrush Action Selects if the 51 4 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off Gn...

Page 221: ...r 50 2 element is blocked or made non directional when VTS operates Off Inhibit Non Dir Off Gn 50 2 Inrush Action Selects if the 50 2 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off Gn 50 2 21LB 3P Action Selects if operation of the 50 2 element is blocked for defined load conditions Off Inhibit Inhibit Gn 50 2 21LB 1P Action Selects if operation of the...

Page 222: ...f Inhibit Off Gn 50 4 21LB 3P Action Selects if operation of the 50 4 element is blocked for defined load conditions Off Inhibit Inhibit Gn 50 4 21LB 1P Action Selects if operation of the 50 4 element is blocked for defined load conditions Off Inhibit Off 3 4 2 Voltage Controlled O C Description Range Default Gn 51V Element Ph Ph Disabled Enabled Disabled Gn 51V Setting The voltage below which 51V...

Page 223: ...IEC LTI ANSI MI ANSI VI ANSI EI IEC NI Gn 51c 1 Time Mult IEC ANSI As Above 0 025 0 03 1 595 1 6 1 7 4 9 5 6 100 1 Gn 51c 1 Delay DTL As Above 0 0 01 19 99 20 5 s Gn 51c 1 Min Operate Time As Above 0 0 01 19 99 20 0 s Gn 51c 1 Follower DTL As Above 0 0 01 19 99 20 0 s Gn 51c 1 Reset As Above ANSI Decaying 0 59 60 0 s Gn 51c 2 Setting 51 2 element parameter used when Cold Load operates 0 05 0 06 2 ...

Page 224: ...4 Derived E F Description Range Default Gn 67N Polarizing Quantity Allows the directional element to select which quantities to use ZPS NPS ZPS Gn 67N Char Angle Maximum torque angle for derived earth fault elements 95 94 94 95 15 deg Gn 67N Minimum Voltage Selects the directional elements minimum voltage below which the element will be inhibited 0 33 0 5 1 1 5 2 2 5 3 0 33 V 3 4 4 1 51N 1 Descrip...

Page 225: ...al forward or reverse Non Dir Forward Reverse Non Dir Gn 51N 2 Setting Pickup level 0 05 0 06 2 49 2 5 0 5xIn Gn 51N 2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL DTL IEC NI IEC VI IEC EI IEC LTI ANSI MI ANSI VI ANSI EI IEC NI Gn 51N 2 Time Mult IEC ANSI Time multiplier applicable to IEC and ANSI curves but not DTL selection 0 025 0 03 1 595 1 6 1 7 4 9 5 6 100 1 Gn 51N 2 Dela...

Page 226: ...t Non Dir Off Gn 51N 3 Inrush Action Selects if the 51N 3 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 4 4 51N 4 Description Range Default Gn 51N 4 Element Selects whether the 51N 4 IDMTL derived Earth Fault element is enabled Disabled Enabled Disabled Gn 51N 4 Dir Control Selects whether 51N 4 element is non directional forward or reverse Non Di...

Page 227: ...rating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 4 6 50N 2 Description Range Default Gn 50N 2 Element Selects whether the DTL derived Earth fault element is enabled Disabled Enabled Disabled Gn 50N 2 Dir Control Selects whether 50N 2 element is non directional forward or reverse Non Dir Forward Reverse Non Dir Gn 50N 2 Setting Pickup level 0 05 0 06 49 5 50 0 5 xIn Gn 50N 2 De...

Page 228: ...rectional when VTS operates Off Inhibit Non Dir Off Gn 50N 4 Inrush Action Selects if the 50N 4 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 5 Measured E F Description Range Default Gn 67G Char Angle Maximum torque angle for measured earth fault elements 95 94 94 95 15 deg Gn 67G Minimum Voltage Selects the directional elements minimum voltage be...

Page 229: ...51G 2 Description Range Default Gn 51G 2 Element Selects whether the 51G 2 IDMTL measured Earth Fault element is enabled Disabled Enabled Disabled Gn 51G 2 Dir Control Selects whether 51G 2 element is non directional forward or reverse Non Dir Forward Reverse Non Dir Gn 51G 2 Setting Pickup level 0 005 0 006 0 995 1 0 5 xIn Gn 51G 2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL ...

Page 230: ...ecaying reset characteristic or DTL reset ANSI Decaying 0 59 60 0 s Gn 51G 3 VTS Action Selects whether 51G 3 element is blocked or made non directional when VTS operates Off Inhibit Non Dir Off Gn 51G 3 Inrush Action Selects if the 51G 3 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 5 4 51G 4 Description Range Default Gn 51G 4 Element Selects whe...

Page 231: ...400 0 s Gn 50G 1 VTS Action Selects whether 50G 1 element is blocked or made non directional when VTS operates Off Inhibit Non Dir Off Gn 50G 1 Inrush Action Selects if the 50G 1 element is blocked from operating when 2nd Harmonic Inrush Detector operates Off Inhibit Off 3 4 5 6 50G 2 Description Range Default Gn 50G 2 Element Selects whether the DTL measured Earth fault element is enabled Disable...

Page 232: ...erse Non Dir Forward Reverse Non Dir Gn 50G 4 Setting Pickup level 0 005 0 006 24 95 25 0 5 xIn Gn 50G 4 Delay Sets operate delay time 0 0 01 14300 14400 0 s Gn 50G 4 VTS Action Selects whether 50G 4 element is blocked or made non directional when VTS operates Off Inhibit Non Dir Off Gn 50G 4 Inrush Action Selects if the 50G 4 element is blocked from operating when 2nd Harmonic Inrush Detector ope...

Page 233: ...L derived Earth Fault element is enabled Disabled Enabled Disabled Gn 51SEF 2 Dir Control Selects whether 51SEF 2 element is non directional forward or reverse Non Dir Forward Reverse Non Dir Gn 51SEF 2 Setting Pickup level 0 005 0 006 0 995 1 0 2 xIn Gn 51SEF 2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL DTL IEC NI IEC VI IEC EI IEC LTI ANSI MI ANSI VI ANSI EI IEC NI Gn 51SEF...

Page 234: ...t is blocked or made non directional when VTS operates Off Inhibit Non Dir Off 3 4 6 4 51SEF 4 Description Range Default Gn 51SEF 4 Element Selects whether the 51SEF 4 IDMTL derived Earth Fault element is enabled Disabled Enabled Disabled Gn 51SEF 4 Dir Control Selects whether 51SEF 4 element is non directional forward or reverse Non Dir Forward Reverse Non Dir Gn 51SEF 4 Setting Pickup level 0 00...

Page 235: ... 2 element is non directional forward or reverse Non Dir Forward Reverse Non Dir Gn 50SEF 2 Setting Pickup level 0 005 0 006 4 995 5 0 2 xIn Gn 50SEF 2 Delay Sets operate delay time 0 0 01 14300 14400 0 s Gn 50SEF 2 VTS Action Selects whether 50SEF 2 element is blocked or made non directional when VTS operates Off Inhibit Non Dir Off 3 4 6 7 50SEF 3 Description Range Default Gn 50SEF 3 Element Sel...

Page 236: ...3 4 8 1 46IT Description Range Default Gn 46IT Element Selects whether the 46IT IDMTL DTL negative phase sequence current element is enabled Disabled Enabled Disabled Gn 46IT Setting Pickup level 0 05 0 06 2 49 2 5 0 25 xIn Gn 46IT Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL DTL IEC NI IEC VI IEC EI IEC LTI ANSI MI ANSI VI ANSI EI IEC NI Gn 46IT Time Mult IEC ANSI Time multipl...

Page 237: ...37 2 Element Phase under current element 37 2 Disabled Enabled Disabled Gn 37 2 Setting Pickup level 0 05 0 1 4 95 5 0 25 xIn Gn 37 2 Delay Sets operate delay time 0 0 01 14300 14400 0 s Gn 37 2 U I Guarded Selects whether to use the 37 2 guard element No Yes Yes Gn 37 2 Start Option Selects whether 31 2 element operates for any phase picked up or only when all phases are picked up All Any All 3 4...

Page 238: ...e Default Gn 49 Thermal Overload Selects whether the thermal overload protection element is enabled Disabled Enabled Disabled Gn 49 Overload Setting Pickup level 0 1 0 11 2 99 3 1 05 xIn Gn 49 Time Constant Minutes Thermal time constant 1 1 5 999 5 1000 10 minutes Gn 49 Capacity Alarm Selects whether thermal capacity alarm enabled Disabled 50 99 100 Disabled 49 Reset Therm State Control that allow...

Page 239: ...lement can block the operation of this element No Yes No Gn 27 59 1 VTS Inhibit Selects whether element is blocked or not when VTS operates No Yes No Gn 27 59 1 O P Phases Selects whether element operates for any phase picked up or only when all phases are picked up Any All Any 3 5 3 27 59 2 Description Range Default Gn 27 59 2 Element Selects whether the Under Over voltage element stage 2 is enab...

Page 240: ... Guard element can block the operation of this element No Yes Yes Gn 27 59 3 VTS Inhibit Selects whether element is blocked or not when VTS operates No Yes No Gn 27 59 3 O P Phases Selects whether element operates for any phase picked up or only when all phases are picked up Any All Any 3 5 5 27 59 4 Description Range Default Gn 27 59 4 Element Selects whether the Under Over voltage element stage ...

Page 241: ...esholds e g 3 on Overlevel picks up above pickup setting and drops off below 97 of setting 3 on Underlevel picks up below setting and drops off above 103 of setting 0 0 1 79 9 80 3 Gn Vx 27 59 Delay Sets operate delay time 0 0 01 14300 14400 0 1 s Gn Vx 27 59 U V Guarded No Yes No 3 7 NPS Overvoltage 3 7 1 47 1 Description Range Default Gn 47 1 Element Selects whether the definite time NPS overvol...

Page 242: ...p level 1 1 5 99 5 100 5 V Gn 59NIT Char Selects characteristic curve to be IDMTL or DTL DTL IDMTL IDMTL Gn 59NIT Time Mult IDMTL Time multiplier applicable to IDMTL curve but not DTL selection 0 1 0 2 139 5 140 1 Gn 59NIT Delay DTL Delay applicable only when DTL is selected for characteristic 0 0 01 19 99 20 5 s Gn 59NIT Reset Selects between an instantaneous reset characteristic or a definite ti...

Page 243: ...n Range Default Gn 81 2 Element Selects whether the Under Over frequency element stage 2 is enabled Disabled Enabled Disabled Gn 81 2 Operation Selects between Underfrequency and Overfrequency pickup for this element Under Over Under Gn 81 2 Setting Under or over frequency pickup level 40 40 01 69 98 69 99 49 Hz Gn 81 2 Hysteresis Sets the pickup to dropoff thresholds e g 3 on Overlevel picks up a...

Page 244: ...poff thresholds e g 3 on Overlevel picks up above pickup setting and drops off below 97 of setting 3 on Underlevel picks up below setting and drops off above 103 of setting 0 0 1 79 9 80 0 1 Gn 81 4 Delay Sets operate delay time 0 0 01 14300 14400 0 4 s Gn 81 4 U V Guarded Selects whether U V Guard element can block the operation of this element No Yes Yes 3 9 5 81 5 Description Range Default Gn 8...

Page 245: ...scription Range Default Gn 50BF Element Selects whether the Circuit Breaker Fail element is enabled Disabled Enabled Disabled Gn 50BF Setting Breaker Fail Current Pickup level If the current falls below this level then the CB is deemed to have opened and the element is reset 0 05 0 055 1 995 2 0 2 xIn Gn 50BF I4 Setting 0 005 0 01 1 995 2 0 05 xIn Gn 50BF 1 Delay Delay before Circuit Breaker Fail ...

Page 246: ... CT Supervision Description Range Default Gn 60CTS Element Selects whether the CT supervision element is enabled NPS current in the absence of NPS voltage Disabled Enabled Disabled Gn 60CTS Inps Arm if NPS Current Inps is above this level 0 05 0 1 0 15 0 2 0 25 0 3 0 35 0 4 0 45 0 5 0 55 0 6 0 65 0 7 0 75 0 8 0 85 0 9 0 95 1 0 1 xIn Gn 60CTS Vnps Inhibit if NPS Voltage Vnps is above this level 7 8...

Page 247: ...Gn 74CCS 1 Delay Time delay before trip circuit supervision operates 0 0 02 59 98 60 0 4 s Gn 74CCS 2 Selects whether the trip circuit supervision element 74CCS 2 is enabled Disabled Enabled Disabled Gn 74CCS 2 Delay Time delay before trip circuit supervision operates 0 0 02 59 98 60 0 4 s Gn 74CCS 3 Selects whether the trip circuit supervision element 74CCS 3 is enabled Disabled Enabled Disabled ...

Page 248: ... Prot n Description Range Default Gn 79 P F Inst Trips Selects which phase fault protection elements are classed as Instantaneous elements and start an autoreclose sequence These will be blocked from operating during Delayed autoreclose sequences See autoreclose section of manual for detail of what elements can cause only Delayed protection to be used Combination of 51 1 51 2 51 3 51 4 50 1 50 2 5...

Page 249: ...0 4 Gn 79 E F HS Trips Selects which earth fault elements are classed as High Set elements any selected elements operating will start an autoreclose sequence Combination of 50N 1 50N 2 50N 3 50N 4 50G 1 50G 2 50G 3 50G 4 3 11 2 Autoreclose Config Description Range Default Gn 79 Autoreclose If disabled then all attempts to control the AR IN OUT status will fail and the AR will be permanently Out Of...

Page 250: ... fault being cleared and the close pulse being issued 0 0 1 14300 14400 5 s Gn 79 P F Prot n Trip 4 Selects whether the fourth phase fault trip is Instantaneous Fast or Delayed When set to Delayed all P F Inst Trips will be Inhibited for this shot Inst Delayed Delayed Gn 79 P F Deadtime 4 Time period between the fault being cleared and the close pulse being issued 0 0 1 14300 14400 5 s Gn 79 P F P...

Page 251: ...ckout Selects how many Delayed trips are allowed before going to Lockout 1 2 3 4 5 5 3 11 2 3 SEF Shots Description Range Default Gn 79 SEF Prot n Trip 1 Selects whether the first sensitive earth fault trip is Instantaneous or Delayed When set to Delayed all SEF Inst Trips will be Inhibited for this shot Inst Delayed Inst Gn 79 SEF Deadtime 1 Time period between the fault being cleared and the clo...

Page 252: ...0 1 14300 14400 5 s Gn 79 Extern Prot n Trip 3 Selects whether the third external trip is Instantaneous or Delayed Not Blocked Blocked Not Blocked Gn 79 Extern Deadtime 3 Time period between the fault being cleared and the close pulse being issued 0 0 1 14300 14400 5 s Gn 79 Extern Prot n Trip 4 Selects whether the fourth external trip is Instantaneous or Delayed Not Blocked Blocked Not Blocked Gn...

Page 253: ...whether a phase fault line check trip is Instantaneous Fast or Delayed When set to Delayed all P F Inst Trips will be Inhibited for this shot Inst Delayed Inst Gn E F Line Check Trip Selects whether an earth fault line check trip is Instantaneous or Delayed When set to Delayed all E F Inst Trips will be Inhibited for this shot Inst Delayed Inst Gn SEF Line Check Trip Selects whether a sensitive ea...

Page 254: ...en this timer expires then an alarm will be raised to signify failure to close 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 1 s Gn CB DBI Delay Selects the Delay before relay goes to Lockout following a simultaneous Open and Close condition indication 0 0 01 1 1 1 11 2 0 s 3 11 6 QUICK LOGIC Description Range Default Quick Logic Enable or Disable all logic equations ...

Page 255: ...0 0 01 14300 14400 0 s E2 Counter Target Select number of times equation must be satisfied before equation output operates 1 2 998 999 1 E2 Counter Reset Mode Select type of counter reset mode Off Multi shot Single shot Off E2 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E3 Equation Enable or Disable logic equation E3 Disabled Enabled Disabled E3 Specify logic equations of t...

Page 256: ... counter reset mode Off Multi shot Single shot Off E4 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E5 Equation Enable or Disable logic equation E5 Disabled Enabled Disabled E5 Specify logic equations of the form En Operand Operator Operand using the following 0123456789 Digit Parenthesis NOT operation AND operation EXCLUSIVE OR operationE followed by a digit Equation numberF...

Page 257: ...ngle shot Off E6 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E7 Equation Enable or Disable logic equation E7 Disabled Enabled Disabled E7 Specify logic equations of the form En Operand Operator Operand using the following 0123456789 Digit Parenthesis NOT operation AND operation EXCLUSIVE OR operationE followed by a digit Equation numberF Followed by a digit Function Key num...

Page 258: ...gle shot Off E8 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E9 Equation Enable or Disable logic equation E9 Disabled Enabled Disabled E9 Specify logic equations of the form En Operand Operator Operand using the following 0123456789 Digit Parenthesis NOT operation AND operation EXCLUSIVE OR operationE followed by a digit Equation numberF Followed by a digit Function Key numb...

Page 259: ...e shot Off E10 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E11 Equation Enable or Disable logic equation E11 Disabled Enabled Disabled E11 Specify logic equations of the form En Operand Operator Operand using the following 0123456789 Digit Parenthesis NOT operation AND operation EXCLUSIVE OR operationE followed by a digit Equation numberF Followed by a digit Function Key nu...

Page 260: ...e shot Off E12 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E13 Equation Enable or Disable logic equation E13 Disabled Enabled Disabled E13 Specify logic equations of the form En Operand Operator Operand using the following 0123456789 Digit Parenthesis NOT operation AND operation EXCLUSIVE OR operationE followed by a digit Equation numberF Followed by a digit Function Key nu...

Page 261: ...e shot Off E14 Counter Reset Time Select counter reset time 0 0 01 14300 14400 0 s E15 Equation Enable or Disable logic equation E15 Disabled Enabled Disabled E15 Specify logic equations of the form En Operand Operator Operand using the following 0123456789 Digit Parenthesis NOT operation AND operation EXCLUSIVE OR operationE followed by a digit Equation numberF Followed by a digit Function Key nu...

Page 262: ...put number ExamplesMake a function key LED toggle when function key is pressed requires E1 to drive L11 in output matrix E1 F3 L11 20 Character String E16 Pick up Delay Time before equation output operates after equation satisfied 0 0 01 14300 14400 0 s E16 Drop off Delay Time before equation output resets after equation nolonger satisfied 0 0 01 14300 14400 0 s E16 Counter Target Select number of...

Page 263: ... BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 51 4 Selects which inputs inhibit the 51 4 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 50 1 Selects which inputs inhibit the 50 1 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI...

Page 264: ... BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 50N 4 Selects which inputs inhibit the 50N 4 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 51G 1 Selects which inputs inhibit the 51G 1 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 ...

Page 265: ...BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 50SEF 1 Selects which inputs inhibit the 50SEF 1 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 50SEF 2 Selects which inputs inhibit the 50SEF 2 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 ...

Page 266: ... V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 49 Selects which inputs inhibit the 49 thermal element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Reset 49 Selects which inputs resets the 49 thermal model element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 ...

Page 267: ...7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 81 3 Selects which inputs inhibit the 81 3 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 81 4 Selects which inputs inhibit the 81 4 element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 ...

Page 268: ... Trip contacts Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inhibit 50BF Selects which inputs inhibit the 50BF element Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 50BF CB Faulty Selects which input bypasses the 50BF timer due to a fault ...

Page 269: ...3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Reset CB E F Count Selects which inputs Reset the CB E F Count Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Reset CB Delta Trip Selects which inputs Reset the CB Delta Trip count Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 ...

Page 270: ...1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 General Alarm 7 Selects which inputs will activate the General Alarm 7 text Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 General Alarm 8 Selects which inputs will activate the General Alarm 8 text Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI...

Page 271: ...BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 General Alarm 20 Selects which inputs will activate the General Alarm 20 text Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 CB Open Selects which inputs are connected to the circuit breaker open contacts Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 ...

Page 272: ...2 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Reset AFDZone 3 Count Selects which inputs will reset ARC Flash Detector Count Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Reset AFDZone 4 Count Selects which inputs will reset ARC Flash Detector Count Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI1...

Page 273: ...V16 79 Ext Pickup Selects which input should be connected to the pickup of the external elements required to start an Auto reclose sequence Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 79 Block Reclose Selects which inputs will block the Auto recloser Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 B...

Page 274: ... V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Inst Prot n In Selects which inputs will switch in the instantaneous protection elements Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 E F Out Selects which inputs will switch out the E F protection elements Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI...

Page 275: ...V15 V16 Select Group 6 Switches active setting group to group 6 Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Select Group 7 Switches active setting group to group 7 Combination of BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Select Group 8 Switches acti...

Page 276: ...I11 BI12 BI13 3 12 2 Function Key Matrix Description Range Default Open CB Selects which function key will Open the circuit breaker Combination of 1 2 3 4 5 6 Close CB Selects which function key will Close the circuit breaker Combination of 1 2 3 4 5 6 79 In Out Selects which function key will toggle Autoreclose In Out Combination of 1 2 3 4 5 6 79 Trip Reclose Selects which function key will caus...

Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...

Page 278: ... Delay Delay on pickup of DC Binary Input 5 0 0 005 14300 14400 0 02 s BI 5 Drop off Delay Delay on dropoff of DC Binary Input 5 0 0 005 14300 14400 0 s BI 6 Pick up Delay Delay on pickup of DC Binary Input 6 0 0 005 14300 14400 0 02 s BI 6 Drop off Delay Delay on dropoff of DC Binary Input 6 0 0 005 14300 14400 0 s BI 7 Pick up Delay Delay on pickup of DC Binary Input 7 0 0 005 14300 14400 0 02 s...

Page 279: ...le text that will be used in the HMI function key confirmation screen when Function key 1 is pressed 20 Character String Function Key 1 Function Key 2 Text User definable text that will be used in the HMI function key confirmation screen when Function key 2 is pressed 20 Character String Function Key 2 Function Key 3 Text User definable text that will be used in the HMI function key confirmation s...

Page 280: ...isplayed for General Alarm 9 16 Character String ALARM 9 General Alarm 10 Defines the text to be displayed for General Alarm 10 16 Character String ALARM 10 General Alarm 11 Defines the text to be displayed for General Alarm 11 16 Character String ALARM 11 General Alarm 12 Defines the text to be displayed for General Alarm 12 16 Character String ALARM 12 General Alarm 13 Defines the text to be dis...

Page 281: ...5 V16 Active Setting Grp 3 Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Active Setting Grp 4 Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 ...

Page 282: ...MTL DTL Overcurrent operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 51 2 51 2 IDMTL DTL Overcurrent operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V1...

Page 283: ...V12 V13 V14 V15 V16 L4 51N 2 51N 2 IDMTL DTL derived Earth Fault operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 L4 51N 3 51N 3 IDMTL DTL derived Earth Fault operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 ...

Page 284: ...6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 L4 51G 3 51G 3 IDMTL DTL measured Earth Fault operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 L4 51G 4 51G 4 IDMTL DTL measured Earth Fault operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO...

Page 285: ...7 V8 V9 V10 V11 V12 V13 V14 V15 V16 L5 51SEF 4 51SEF 4 IDMTL DTL Sensitive Earth Fault operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 L5 50SEF 1 50SEF 1 INST DTL Sensitive Earth Fault operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 B...

Page 286: ...0 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 37 PhA PhA Under Current operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 37 PhB PhB Under Current operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2...

Page 287: ...V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 49 Trip Thermal capacity trip operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 49 Alarm Thermal capacity alarm operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9...

Page 288: ...V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 59NIT Neutral Overvoltage IDMTL DTL operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 59NDT Neutral Overvoltage INST DTL operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2...

Page 289: ...0 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 60CTS I Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 46BC 46 Broken Conductor element operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8...

Page 290: ...1 V12 V13 V14 V15 V16 General Pickup General Pickup operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 50BF 1 Circuit Breaker Fail stage 1 operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L...

Page 291: ...2 V13 V14 V15 V16 CB Total Trip Count Total CB trip count exceeded Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 CB Ph A Trip Count Total CB Ph A trip count exceeded Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9...

Page 292: ...ime Alarm Trip Time Alarm operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 CB Open Indicates that the circuit breaker is in the open position Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L...

Page 293: ...V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Derived E F Derive E F element operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Measured E F Measured E F element operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5...

Page 294: ... L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 AFD Zone 1 Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 AFD Zone 2 Flash Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 ...

Page 295: ...V16 AFD Zone 6 Flash Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 AFD Zone 6 Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 User Output ...

Page 296: ...ation of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Reverse P F The Phase fault is in the reverse direction Note this output is presented EVEN when relay elements are set to be non directional Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4...

Page 297: ...10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 79 Trip Lockout Indicates the Trip Lockout sequence being performed Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 79 Lockout Indicates the auto recloser is in the Lockout state Combination of BO...

Page 298: ...ere no auto reclose trip elements operated This is issued for 2 secs Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Successful Man Close Indicates that after a manual close and at the end of the Reclaim time the CB was closed and there were no auto reclose trip element...

Page 299: ... V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 25 In Sync Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 25 CS In Progress Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5...

Page 300: ...1 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 New Wave Stored The waveform recorder has stored new information Note this is a pulsed output Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 New Fault...

Page 301: ...V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 BI 1 Operated DC Binary Input 1 has operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 BI 2 Operated DC Binary Input 2 has operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L...

Page 302: ...V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 BI 10 Operated DC Binary Input 10 has operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 BI 11 Operated DC Binary Input 11 has operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 ...

Page 303: ...V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 E6 Quick Logic equation 6 operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 E7 Quick Logic equation 7 operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 ...

Page 304: ... BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 E16 Quick Logic equation 16 operated Combination of BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 Trip Contacts Assigns Output Contact as trip contact for ...

Page 305: ...inimum operate time of output relay 7 if set to self reset if also set to be pulsed then this is the pulse width 0 0 01 59 60 0 s Min Operate Time 8 Minimum operate time of output relay 8 if set to self reset if also set to be pulsed then this is the pulse width 0 0 01 59 60 0 s Min Operate Time 9 Minimum operate time of output relay 9 if set to self reset if also set to be pulsed then this is the...

Page 306: ... 10 11 12 13 14 PU Red LEDs Selects which LEDs will be red when driven by a pickup Combination of 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 3 13 4 Pickup Config Description Range Default Gn P F Pickups When any of the selected pickups operate General Pickup is driven Combination of 51 1 51 2 51 3 51 4 50 1 50 2 50 3 50 4 51 1 51 2 51 3 51 4 50 1 50 2 50 3 50 4 Gn E F Pickup...

Page 307: ... Count Target Selects the number of CB trips allowed before CB E F Trip Count counter output operates 0 1 9999 10000 100 Gn CB Delta Trip Count Selects whether the CB Delta Trip Count counter is enabled Disabled Enabled Disabled Gn CB Delta Trip Count Target Selects the number of CB trips allowed before CB Delta Trip Count counter output operates 0 1 9999 10000 100 Gn CB Delta Trip Count Reset Res...

Page 308: ...before output operatest 0 10000 100 3 15 Data Storage 3 15 1 Demand Data Log Description Range Default Data Log Period Selects period between stored samples 5 6 7 8 9 10 15 20 25 30 35 40 45 50 55 60 5 min Clear Data Log Clear the Data Log Gn Demand Window The time window over which the Min Max and Mean values are calculated 1 2 23 24 24 hrs Gn Demand Window Type Method used to calculate Demand va...

Page 309: ...age Select Percentage of waveform record stored before the fault is triggered 10 20 30 40 50 60 70 80 90 20 Record Duration Select waveform record duration 10 Rec x 1 Sec 5 Rec x 2 Sec 2 Rec x 5 Sec 1 Rec x 10 Sec 10 Rec x 1 Sec Trigger Waveform Trigger waveform storage Clear Waveforms Clear all stored waveform records 3 15 3 Fault Storage Description Range Default Gn Max Fault Rec Time Maximum ti...

Page 310: ...sabled Enabled Disabled Line Angle 0 Deg to 90 Deg 75 Deg EF Comp Z0 Z1 Ratio 0 to 10 2 5 EF Comp Z0 Angle 0 Deg to 359 Deg 75 Deg Z Impedance 0 1 Ohms to 250 Ohms 10 Ohms Sec y Z Per Unit Distance 0 005 Ohms to 5 Ohms 0 5 Ohm Display Units Percent kilometres miles Percent System Earthing Normal Compensated Normal Gn U0 U1 Ratio 0 to 1 0 1 Gn Freq FL Inhibits 6 Bit Binary 81 1 81 2 81 3 81 4 81 5 ...

Page 311: ... Selects the communications line idle sense LIGHT OFF LIGHT ON LIGHT OFF COM3 Data Echo Enables echoing of data from RX port to TX port when operating relays in a Fibre Optic ring configuration OFF ON OFF COM3 Mode Local Remote Local Or Remote Remote COM4 Protocol Selects protocol to use for COM4 OFF IEC60870 5 103 MODBUS RTU DNP3 OFF COM4 Baud Rate Sets the communications baud rate for COM4 75 11...

Page 312: ...ngs Guide Unrestricted 2018 Siemens Protection Devices Limited Page 107 of 107 Description Range Default DNP3 Application Timeout The address of the master to which unsolicited events will be sent 5 6 299 300 10 s ...

Page 313: ...rmission of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of negligence or any oth...

Page 314: ... revisions and added data Software Revision History 2011 05 2435H85008R7a 7a 7SR210 2435H85009R7a 7a 7SR220 First Release 2013 01 2435H85008R7c 7b 7SR210 2435H85009R7c 7b 7SR220 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line Check on non AR devices Added 74CCS Close Circuit Supervision 2014 06 2435H85008R7f 7d 7SR210 ...

Page 315: ...1 3 7 Fibre Optic Ethernet Data Communication Interface IEC 61850 Option 16 1 3 8 Electrical Ethernet Data Communication Interface IEC 61850 Option 16 1 3 9 Real Time Clock 16 1 4 Environmental Performance 17 1 4 1 General 17 1 4 2 Emissions 18 1 4 3 Immunity 18 1 4 4 Mechanical 20 Section 2 Protection Functions 21 2 1 27 59 Phase Under Over Voltage 21 2 1 2 Reference 21 2 1 3 Operate and Reset Le...

Page 316: ...Derived Earth Fault 34 2 12 1 Reference 34 2 12 2 Operate and Reset Level 34 2 12 3 Operate and Reset Time 34 2 1350SEF Instantaneous Sensitive Earth Fault 35 2 13 1 Reference 35 2 13 2 Operate and Reset Level 35 2 13 3 Operate and Reset Time 35 2 1451 Time Delayed Overcurrent 36 2 14 1 Reference 36 2 14 2 Operate and Reset Level 36 2 14 3 Operate and Reset Time 37 2 1551G Time Delayed Measured Ea...

Page 317: ...G31 Technical Manual for performance characteristics 55 2 25 1 Reference 55 2 25 2 Operate and Reset Level 55 2 25 3 Operate and Reset Time 55 Section 3 Supervision Functions 56 3 1 46BC 46BC U C Broken Conductor 56 3 1 1 Reference 56 3 1 2 Operate and Reset Level 56 3 1 3 Operate and Reset Time 56 3 2 50BF 50BF I4 Circuit Breaker Fail 57 3 2 1 Reference 57 3 2 2 Operate and Reset Level 57 3 2 3 O...

Page 318: ...unctions 66 4 1 Check Synchronising 66 4 1 1 Reference 66 4 1 2 Live Dead Line Bus Detector Elements 66 4 1 3 Line and Bus Undervoltage Elements 67 4 1 4 Voltage Difference 67 4 1 5 General Autoreclose Timers 67 4 1 6 CS SS COZ Line and Bus Phase Angle Difference 67 4 1 7 CS SS COZ Slip Frequency 67 4 1 8 CS SS Timer 67 4 1 9 Split Angle Detector 68 4 1 10 Split Slip Frequency Detector 68 4 2 Live...

Page 319: ...rotection Devices Limited Page 7 of 68 List of Figures Figure 2 1 Thermal Overload Protection Curves 31 Figure 2 2 IEC IDMTL Curves Time Multiplier 1 38 Figure 2 3 ANSI IDMTL Operate Curves Time Multiplier 1 39 Figure 2 4 ANSI IDMTL Reset Curves Time Multiplier 1 40 ...

Page 320: ...conditions unless specifically stated otherwise Parameter Value Auxiliary supply Nominal AC Current Nominal Frequency Nominal Ambient temperature 20 C 1 1 3 Dimensions Parameter Value Width E6 case 155 5 mm E8 case 207 5 mm E12 case 311 5 mm Height 177 mm Depth behind panel including clearance for Wiring Fibre Optic Ethernet enclosure Depth below Ethernet variant for cables 241 5 mm 286 5 mm 259 5...

Page 321: ...4 2 7SR2103 4 6 7SR2104 4 8 7SR2105 8 4 7SR2106 8 4 7SR2202 4 8 7SR2203 4 9 7SR2204 5 3 7SR2205 8 4 7SR2206 8 4 NB For relays supplied with additional optional communication interface devices please add an additional 0 165 kg to the figures in the above table For relays supplied with Ethernet interface optional please add 0 1 kg to the figures in the above table ...

Page 322: ...3 0 03 0 03 0 03 0 03 Per LED Yellow 0 08 0 06 0 06 0 06 0 06 0 06 0 06 Per Binary Output 0 35 0 3 0 3 0 3 0 3 0 28 0 28 Optional IEC61850 2 6 2 5 2 4 2 4 2 4 2 4 2 4 Attribute VA AC Voltage V 100 110 115 120 200 230 Quiescent Relay inc PROT HEALTHY LED 10 0 10 0 10 0 10 5 12 0 14 0 LCD backlight on 2 5 2 5 2 5 2 6 3 0 3 2 Per LED Red 0 06 0 06 0 06 0 06 0 06 0 07 Per LED Yellow 0 10 0 12 0 10 0 1...

Page 323: ...utdown occurs This condition is designed to protect the power supply from damage as well as prevent internal relay faults from developing into dangerous situations Once the relay has entered this safety mode it may be necessary to reduce the auxiliary input voltage to zero volts for up to 30 seconds before re application of the auxiliary supply will cause the relay to power up and operate normally...

Page 324: ...ntinuous 3 0 xIn 10 minutes 3 5 xIn 5 minutes 4 0 xIn 3 minutes 5 0 xIn 2 minutes 6 0 xIn 3 seconds 57 7 A 202 A 2 seconds 70 7 A 247 A 1 second 100 A 350 A 1 cycle 700 A 2500 A 1 2 3 AC Voltage Nominal Operating Range Vn 63 5 V 110 V 40 V rms to 160 V rms fn 50 Hz 60 Hz 47 Hz to 62 Hz 1 2 3 1 Burden Attribute Value AC Burden 0 1 VA at 110 V Attribute Value Phase and Earth 1 A 5 A AC Burden 0 1 VA...

Page 325: ...tinuously 5 A AC or DC Make and carry L R 40 ms and V 300 V for 0 5 s 20 A AC or DC for 0 2 s 30 A AC or DC Break 5 A and 300 V AC resistive 1250 VA AC inductive 250 VA at p f 0 4 DC resistive 75 W DC inductive 30 W at L R 40ms 50 W at L R 10 ms Contact Operate Release Time 7 ms 3 ms Minimum number of operations 1000 at maximum load Minimum recommended load 0 5 W at minimum of 10 mA or 5 V ...

Page 326: ... programmed to energise an output relay contact i e includes output relay operation 20 ms Sample Rate Every 5 ms The binary inputs are isolated from earth potential They have a low minimum operate current and may be set for high speed operation Where a binary input is both used to influence a control function e g provide a tripping function and it is considered to be susceptible to mal operation d...

Page 327: ...bre Optic Serial Data Communication Interface Optional Rear Mounted Port Attribute Value Physical layer Fibre optic Connectors STTM BFOC 2 5 Recommended fibre 62 5 125 mm glass fibre with ST connector Optical Wavelength 820 nm Launch power into recommended fibre 16 dBm Receiver sensitivity 24 dBm 1 3 4 RS485 Data Communication Interface Standard Rear Port Attribute Value Physical layer Electrical ...

Page 328: ...alue Physical layer Electrical Connectors RJ45 100BaseF in acc With IEEE802 3 Transmission Speed 100 MBits s Test Voltage with regard to socket 500 VAC 50 Hz Bridgeable distance 20 m 1 3 9 Real Time Clock 1 3 9 1 Internal Clock The specification below applies only while no external synchronisation signal e g IRIG B IEC 60870 5 103 is being received Attribute Value Accuracy 10 o C to 55 o C 100 ppm...

Page 329: ...h Operational test Outdoor 6 cycles at 24 h between 25 C 97 r h and 55 C 93 r h 1 4 1 3 Transient Overvoltage IEC 60255 5 Type Level Between all terminals and earth or between any two independent circuits 5 0 kV 1 2 50 ms 0 5j 1 4 1 4 Insulation IEC 60255 5 Type Level Between any terminal and earth 2 5 kV AC RMS for 1 min Between independent circuits Across normally open contacts 1 0 kV AC RMS for...

Page 330: ...o 30 MHz 73 dB mV 60 dB mV 1 4 3 Immunity 1 4 3 1 Auxiliary DC Supply Variation Quantity Value Allowable superimposed ac component 12 of DC voltage Allowable breaks dips in supply collapse to zero from nominal voltage 20 ms 1 4 3 2 High Frequency Disturbance IEC 60255 22 1 Class III Type Level Variation Common longitudinal mode 2 5 kV 5 Series transverse mode 1 0 kV 1 4 3 3 Electrostatic Discharge...

Page 331: ...rth 4 0 kV 10 or 1 mA Case Aux Power I O Line to Earth 2 0 kV 10 or 1 mA RS485 Comms Port Line to Earth 1 0 kV No Data Loss Analogue Inputs Line to Line 1 0 kV 10 or 1 mA Case Aux Power I O Line to Line 1 0 kV 10 or 1 mA Note 45 ms pick up delay for DTL applied to binary inputs 1 4 3 7 Conducted Radio Frequency Interference IEC 60255 22 6 Type Level Variation 0 15 MHz to 80 MHz 10 V 5 1 4 3 8 Magn...

Page 332: ...Type Level Variation Vibration response 0 5 gn 5 Vibration endurance 1 0 gn 1 4 4 2 Shock and Bump IEC 60255 21 2 Class I Type Level Variation Shock response 5 gn 11 ms 5 Shock withstand 15 gn 11 ms Bump test 10 gn 16 ms 1 4 4 3 Seismic IEC 60255 21 3 Class I Type Level Variation Seismic response 1 gn 5 1 4 4 4 Mechanical Classification Type Level Durability 106 operations ...

Page 333: ... 3 Operate and Reset Level Attribute Value Vop Operate level 100 Vs 1 or 0 25 V Reset level Overvoltage 100 hyst x Vop 1 or 0 25 V Undervoltage 100 hyst x Vop 1 or 0 25 V Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 1 4 Operate and Reset Time Attribute Value tbasicE Element basic operate time Overvoltage Switched from 0 to 1 1 x Vs 73 ms 10 ms Switched from 0 to 2 0 xVs 63 m...

Page 334: ... 2 2 2 Operate and Reset Level Attribute Value Vop Operate level 100 Vs 1 or 0 25 V Reset level Overvoltage 100 hyst x Vop 1 or 0 25 V Undervoltage 100 hyst x Vop 1 or 0 25 V Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 2 3 Operate and Reset Time Attribute Value tbasicE Element basic operate time Overvoltage Switched from 0 to 1 1 xVs 73 ms 10 ms Switched from 0 to 2 0 xVs 6...

Page 335: ...Sop Operate level 100 Ss 5 or 2 Sn Reset level Over power 95 Sop Under power 105 Sop Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 3 3 Operate and Reset Time Attribute Value tbasic Element basic operate time Over power 1 1 x Ss 60 ms 10 ms 2 0 x Ss 45 ms 10ms Under power 0 5 x Ss 30 ms 10ms top Operate time following delay tbasic td 1 or 10ms Disengaging time 40 ms 2 3 4 Operate Threshold At...

Page 336: ... Value Sop Operate level 100 Ss 5 or 2 Sn Reset level Over power 95 Sop Under power 105 Sop Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 4 3 Operate and Reset Time Attribute Value tbasicE Element basic operate time Over power 1 1 x Ss 60 ms 10 ms 2 0 x Ss 45 ms 10ms Under power 0 5 x Ss 30 ms 10ms top Operate time following delay tbasic td 1 or 10ms Disengaging time 40 ms 2 4 4 Operate Thre...

Page 337: ...10100 14400 s Is 37 n U I Guard Setting 0 05 0 10 5 0 xIn 2 5 2 Operate and Reset Level Attribute Value Iop Operate level 100 Is 5 or 1 In Reset level 105 Iop Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 5 3 Operate and Reset Time Attribute Value tbasic Element basic operate time 1 1 to 0 5 xIs 35 ms 10ms top Operate time following delay tbasic td 1 or 10ms Repeatability 1 o...

Page 338: ...1 1000 1010 10000 10100 14400 s 2 6 2 Operate and Reset Level Attribute Value Iop Operate level 100 Is 5 or 1 In Reset level 105 Iop or Iop 0 1 In Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 6 3 Operate and Reset Time Attribute Value tbasic Element basic operate time 1 1 to 0 5 xIs 35 ms 10 ms top Operate time following delay tbasic td 1 or 10 ms Repeatability 1 or 10 ms Ov...

Page 339: ...X R 100 5 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 7 3 Operate and Reset Time 46DT Attribute Value tbasic Element basic operate time Switched from 0 to 2 xIs 40 ms 10 ms Switched from 0 to 5 xIs 30 ms 10 ms top Operate time following delay tbasic td 1 or 10 ms Repeatability 1 or 10 ms Overshoot time 40 ms Disengaging time 60 ms 2 7 4 Reference 46IT Parameter Value char Characteristic se...

Page 340: ...rate time char IEC NI IEC VI IEC EI IEC LTI Tm K t Is I op 1 a 5 or 50 ms for char IEC NI K 0 14 a 0 02 IEC VI K 13 5 a 1 0 IEC EI K 80 0 a 2 0 IEC LTI K 120 0 a 1 0 char ANSI MI ANSI VI ANSI EI Tm B A t P Is I op ú ú û ù ê ê ë é 1 5 or 50 ms for char ANSI MI A 0 0515 B 0 114 P 0 02 ANSI VI A 19 61 B 0 491 P 2 0 ANSI EI A 28 2 B 0 1217 P 2 0 char DTL td 1 or 20 ms Reset time ANSI DECAYING Tm R t I...

Page 341: ...1 1000 1010 10000 10100 14400 s 2 8 2 Operate and Reset Level 47 Attribute Value Vop Operate level 100 Vs 2 or 0 5 V Reset level 100 Hyst x Vop 1 or 0 25 V Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 8 3 Operate and Reset Time 47 Attribute Value tbasic Element basic operate time 0 to 2 xVs 80 ms 20 ms 0 to 10 xVs 55 ms 20 ms top Operate time following delay tbasic td 2 or 2...

Page 342: ...constant setting 1 1 5 1000 min 2 9 2 Operate and Reset Level Attribute Value Iol Overload level 100 Is 5 or 1 In Reset level 95 Iol Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 9 3 Operate and Reset Time Attribute Value top Overload trip operate time þ ý ü î í ì t 2 2 2 P 2 I I I ln B I k t where IP prior current 5 o r 1 0 0 m s For Is range 0 3 xIn to 3 xIn Repeatability 1...

Page 343: ...restricted 2013 Siemens Protection Devices Limited Page 31 of 68 0 1 1 10 100 1000 10000 100000 0 1 2 3 4 5 6 7 8 9 10 Current multiple of setting Time sec t 1000 mins t 100 mins t 10 mins t 1 min Figure 2 1 Thermal Overload Protection Curves ...

Page 344: ...ing 0 00 0 01 20 00 20 50 100 101 1000 1010 10000 10100 14400 s 2 10 2 Operate and Reset Level Attribute Value Iop Operate level 100 Is 5 or 1 In Reset level 95 Iop Repeatability 1 Transient overreach X R 100 5 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 10 3 Operate and Reset Time Attribute Value tbasic Element basic operate time Switched from 0 to 2x Is 40 ms 10 ms Switched from 0 to 5x ...

Page 345: ...0 00 20 50 100 101 1000 1010 10000 10100 14400 s 2 11 2 Operate and Reset Level Attribute Value Iop Operate level 100 Is 5 or 1 In Reset level 95 Iop Repeatability 1 Transient overreach X R 100 5 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 11 3 Operate and Reset Time Attribute Value tbasic Element basic operate time Switched from 0 to 2x Is 35 ms 10 ms Switched from 0 to 5x Is 25 ms 10 ms ...

Page 346: ...00 14400 s 2 12 2 Operate and Reset Level Attribute Value Iop Operate level 100 Is 5 or 1 In Reset level 95 Iop Repeatability 1 Transient overreach X R 100 5 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 12 3 Operate and Reset Time Attribute Value tbasic Element basic operate time Switched from 0 to 2x Is 40 ms 10 ms Switched from 0 to 5x Is 30 ms 10 ms top Operate time following delay tbasi...

Page 347: ...erate and Reset Level Attribute Value Iop Operate level 100 Is 5 or 1 In Reset level 95 Iop 5 or 0 1 In Repeatability 1 Transient overreach X R 100 5 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz harmonics to fcutoff 5 2 13 3 Operate and Reset Time Attribute Value tbasic Element basic operate time Switched from 0 to 0 to 2x Is 35 ms 10 ms Switched from 0 to 0 to 5x Is 25 ms 10 ms top Operate tim...

Page 348: ...r Characteristic setting IEC NI VI EI LTI ANSI MI VI EI DTL Tm Time Multiplier setting 0 025 0 05 1 6 td Delay setting 0 0 01 20 s tres Reset setting ANSI DECAYING 0 1 60 s I Applied Current for operate time IDMTL 2 to 20 x ls DTL 5 x Is 2 14 2 Operate and Reset Level Attribute Value Iop Operate level 105 Is 4 or 1 In Reset level 95 Iop Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 ...

Page 349: ... A 0 0515 B 0 114 P 0 02 ANSI VI A 19 61 B 0 491 P 2 0 ANSI EI A 28 2 B 0 1217 P 2 0 char DTL td 1 or 20ms Reset time ANSI DECAYING Tm R t Is I res 1 2 5 or 30 ms for char ANSI MI R 4 85 ANSI VI R 21 6 ANSI EI R 29 1 tres tres 1 or 20 ms Repeatability 1 or 20 ms Overshoot time 40 ms Disengaging time 50 ms Figure 2 2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1 ...

Page 350: ...e 38 of 68 2013 Siemens Protection Devices Limited 0 1 1 10 100 1000 1 10 100 Current multiples of setting Time sec 2 3 4 5 6 8 20 30 40 50 60 80 Long Time Inverse Normal Inverse Very Inverse Extremely Inverse Figure 2 2 IEC IDMTL Curves Time Multiplier 1 ...

Page 351: ...2013 Siemens Protection Devices Limited Page 39 of 68 0 1 1 10 100 1000 1 10 100 Current multiples of setting Time sec 2 3 4 5 6 8 20 30 40 50 60 80 Moderately Inverse Extremely Inverse Very Inverse Figure 2 3 ANSI IDMTL Operate Curves Time Multiplier 1 ...

Page 352: ...age 40 of 68 2013 Siemens Protection Devices Limited 1 10 100 1000 0 1 1 Current multiples of setting Time sec Moderately Inverse Extremely Inverse Very Inverse 0 2 0 3 0 4 0 5 0 6 0 8 0 9 0 7 5 50 500 Figure 2 4 ANSI IDMTL Reset Curves Time Multiplier 1 ...

Page 353: ...n Char Characteristic setting IEC NI VI EI LTI ANSI MI VI EI DTL Tm Time Multiplier setting 0 025 0 05 1 6 td Delay setting DTL 0 0 01 20 s tres Reset setting ANSI DECAYING 0 1 60 s I Applied current for operate time IDMTL 2 to 20 xIs DTL 5 xIs 2 15 2 Operate and Reset Level Attribute Value Iop Operate level 105 Is 4 or 1 In Reset level 95 Iop Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to ...

Page 354: ...15 B 0 114 P 0 02 ANSI VI A 19 61 B 0 491 P 2 0 ANSI EI A 28 2 B 0 1217 P 2 0 char DTL td 1 or 20 ms Reset time ANSI DECAYING Tm R t Is I res 1 2 5 or 30 ms for char ANSI MI R 4 85 ANSI VI R 21 6 ANSI EI R 29 1 tres tres 1 or 20 ms Repeatability 1 or 20 ms Overshoot time 40 ms Disengaging time 50 ms Figure 2 2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1 Figure...

Page 355: ...alue Is Setting 0 05 0 06 2 5 xIn char Characteristic setting IEC NI VI EI LTI ANSI MI VI EI DTL Tm Time Multiplier setting 0 025 0 05 1 6 td Delay setting 0 0 01 20 s tres Reset setting ANSI DECAYING 0 1 60 s 2 16 2 Operate and Reset Level Attribute Value Iop Operate level 105 Is 4 or 1 In Reset level 95 Iop Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 ...

Page 356: ...15 B 0 114 P 0 02 ANSI VI A 19 61 B 0 491 P 2 0 ANSI EI A 28 2 B 0 1217 P 2 0 char DTL td 1 or 20 ms Reset time ANSI DECAYING Tm R t Is I res 1 2 5 or 30 ms for char ANSI MI R 4 85 ANSI VI R 21 6 ANSI EI R 29 1 tres tres 1 or 20 ms Repeatability 1 or 20 ms Overshoot time 40 ms Disengaging time 50 ms Figure 2 2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1 Figure...

Page 357: ... char Characteristic setting IEC NI VI EI LTI ANSI MI VI EI DTL Tm Time multiplier 1 0 td Delay setting 0 00 20 00 s tres Reset setting DECAYING 0 1 60 s I Applied current for operate time IDMTL 2 to 20xIs DTL 5 xIs 2 17 2 Operate and Reset Level Attribute Value Iop Operate level 105 Is 4 or 1 In Reset level 95 Iop 4 or 1 In Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz harmonics...

Page 358: ...0 491 P 2 0 ANSI EI A 28 2 B 0 1217 P 2 0 char DTL td 1 or tcycle Reset time char ANSI and tres DECAYING Tm R t Is I res 1 2 5 or 30 ms for char ANSI MI R 4 85 ANSI VI R 21 6 ANSI EI R 29 1 tres DECAYING tres 1 or 20 ms Repeatability 1 or 20 ms Overshoot time 40 ms Disengaging time 50 ms Variation fnom 3 Hz to fnom 2 Hz harmonics to fcutoff 5 Figure 2 2 shows the operate times for the four IEC IDM...

Page 359: ... 199 5 200 V m Multiplier 0 25 0 3 0 95 1 Is Setting 1 xIn 2 18 2 Operate and Reset Level Attribute Value Vop Operate level 100 Vs 1 or 0 25 V Reset level 105 Vop Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz harmonics to fcutoff 5 Operate and Reset Time As per Phase Fault Shaped Characteristic Element ANSI 51 Where Pickup Level Is for Voltage Vs Pickup Level Is x m for Voltage V...

Page 360: ...e and Reset Level Attribute Value PFop Operate Level PFs 0 05 Reset Level Under PF PFop 0 02 Over PF PFop 0 02 Repeatability 0 05 Variation 10 C to 55 C 0 05 fnom 3 Hz to fnom 2 Hz 0 05 2 19 3 Operate and Reset Time Attribute Value tbasic Element basic operate time 70 ms top Operate time following delay tbasic td 1 or 10ms Disengaging time 80 ms 2 19 4 Operate Threshold Attribute Value Minimum lev...

Page 361: ...0 Vs 2 or 0 5 V Reset level 95 Vop or 0 25 V Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 20 3 Operate and Reset Time 59NDT Attribute Value tbasic Element basic operate time Switched from 0 to 1 5 xVs 76 ms 20 ms Switched from 0 to 10 xVs 63 ms 20 ms top Operate time following delay tbasic td 1 or 20 ms Repeatability 1 or 20 ms Overshoot time 40 ms Disengaging time 50 ms 2 2...

Page 362: ...t level 95 Vop or 0 25 V Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 20 6 Operate and Reset Time 59NIT Attribute Value tbasic Starter operate time 2xVs 65 ms 20 ms top Operate time char IDMTL 1 M t Vs 0 V 3 op 5 or 65 ms char DTL td 1 or 40 ms Reset Time char IDMTL tres 5 or 65 ms char DTL tres 1 or 40 ms Repeatability 1 or 20 ms Overshoot time 40 ms Disengaging time 50 ms ...

Page 363: ...00 0 101 1000 1010 10000 10100 14400 s 2 21 2 Operate and Reset Level Attribute Value Iop Operate level 100 Is 5 or 1 xIn Reset level 95 Iop 5 or 0 1 xIn Repeatability 1 Transient overreach X R 100 5 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 21 3 Operate and Reset Time Attribute Value tbasic Element basic operate time top Operate time following delay tbasic td 1 or 10 ms Repeatability 1 ...

Page 364: ...perate Angle Attribute Value CA Characteristic angle I with respect to V us 5 Operating angle forward CA 85 5 to CA 85 5 reverse CA 180 85 5 to CA 180 85 5 Variation in characteristic angle 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 2 22 3 Operate Threshold Attribute Value Minimum levels for operation I p f 5 In I e f 10 In V p f 1 V V e f 1 V 2 22 4 Operate and Reset Time Attribute Value Operate tim...

Page 365: ...0 10 20 0 xInxW Where In 1A or 5A I Applied current In 1A 10mA 5A V Applied voltage 10V 200V q Angle 87 5deg CA 67SEF Char Angle qc 0 f Nominal 50 60Hz 2 23 2 Operate and Reset Level Attribute Value Pop Operate level 100 Po 25 or 25mW Reset level 95 Pop Variation 10 C to 55 C 5 2 23 3 Operate and Reset Time Attribute Value tbasic Element basic operate time 50ms Repeatability 1 or 10ms ...

Page 366: ... 2 Operate and Reset Level Attribute Value Fop Operate level 100 Fs 10 mHz Reset level overfrequency 100 hyst xFop 10 mHz underfrequency 100 hyst xFop 10 mHz Repeatability 1 Variation 10 C to 55 C 5 2 24 3 Operate and Reset Time Attribute Value tbasic Element basic operate time for ROCOF between 0 1 and 5 0 Hz sec overfrequency Typically 110 ms Maximum 150 ms underfrequency Typically 110 ms Maximu...

Page 367: ...istics 2 25 1 Reference Parameter Value 50 AFD Setting 1 2 10 xIn 2 25 2 Operate and Reset Level Attribute Value Iop Operate level 100 Is 10 Transient overreach X R 100 30 Reset level 95 Iop Repeatability 5 2 25 3 Operate and Reset Time Attribute Value tbasic 50AFD Overcurrent operate time 10 ms 16 ms top AFD Zone operate time Flash 50AFD 15 ms 25 ms Repeatability 10 ms Disengaging time 50 ms ...

Page 368: ...d setting 0 05 0 1 4 95 5 tf Delay setting 0 02 1000 s 3 1 2 Operate and Reset Level Attribute Value Icurr Operate level 100 Iset 5 Reset level 90 Icurr 5 Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz harmonics to fcutoff 5 3 1 3 Operate and Reset Time Attribute Value tbasic Basic operate time 1x In to 0 A 40 ms Operate time tf tbasic 1 or 20 ms Repeatability 1 or 20 ms Variation...

Page 369: ...1 Delay setting 20 25 60000ms tCBF2 Stage 2 Delay setting 20 25 60000ms 3 2 2 Operate and Reset Level Attribute Value Iop Operate level 100 Is 5 or 1 In Ireset Reset level 100 Iop 5 or 1 In Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 3 2 3 Operate and Reset Time Attribute Value tbasic Element basic operate time 20 ms top Stage 1 tCBF1 1 or 20 ms Stage 2 tCBF2 1 or 20 ms Repea...

Page 370: ... 1000 1010 10000 10100 14400 s CTS I Ithresh Current Threshold 0 05 0 1 2 xIn 3 3 2 Current Voltage Threshold Attribute Value Iop CT failed current level 100 Ithresh 5 or 1 In Reset level 90 Iop 5 or 1 In Vop CT failed voltage level 100 Vthresh 2 or 0 5 V Reset level 110 Vop 2 or 0 5 V Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz harmonics to fcutoff 5 3 3 3 Operate and Reset Ti...

Page 371: ...1000 1010 10000 10100 14400 s 3 4 2 Operate and Reset Level Attribute Value VNPSop Voltage NPS operate level 100 Vnps 5 Vn Voltage NPS reset level 90 VNPSop 5 Vn VPPSop Voltage PPS operate level 100 Vpps 5 Vn Voltage PPS reset level 110 VPPSop 5 Vn INPSblk Current NPS operate level 100 Inps 5 xIn Current NPS reset level 90 INPSblk 5 xIn IPPSblk Current PPS operate level 100 IFpps 5 xIn Current PPS...

Page 372: ...cification Unrestricted Page 60 of 68 2013 Siemens Protection Devices Limited 3 4 3 Operate and Reset Time Attribute Value tbasic Basic operate time 0V to 2 x Vs 32 ms 10 ms Operate time tbasic 1 or 10 ms Repeatability 1 or 10 ms ...

Page 373: ...74TCS Trip Circuit Supervision 3 5 1 Reference Parameter Value td Delay setting 0 0 02 60 s 3 5 2 Operate and Reset Time Attribute Value tbasic Element basic operate time 25 ms 20 ms top Operate time following delay tbasic td 1 or 10 ms Repeatability 1 or 10 ms Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 ...

Page 374: ... 0 10 0 11 0 5 3 6 2 Operate and Reset Level Attribute Value Iop Operate level 100 I 4 or 1 In Reset level 100 Iop 4 or 1 In Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 3 6 3 Operate and Reset Time Attribute Value tbasic Element basic operate time Will pick up before operation of any protection element due to magnetic inrush Reset Time Will operation until drop off of any pro...

Page 375: ...current 0 10 0 11 0 5 3 7 2 Operate and Reset Level Attribute Value Iop Operate level 100 I 4 or 1 In Reset level 100 Iop 4 or 1 In Repeatability 1 Variation 10 C to 55 C 5 fnom 3 Hz to fnom 2 Hz 5 3 7 3 Operate and Reset Time Attribute Value tbasic Element basic operate time Will pick up before operation of any protection element due to overfluxing Reset Time Will operation until drop off of any ...

Page 376: ...eg Z Impedance 1 Ohm to 100 Ohms Vpps Vpps Level 1 V to 110 V Inps Inps Level 0 05 xIn to 5 xIn 3 8 2 Operate Level Attribute Value VPPS Voltage PPS operate level 100 Vs 2 or 0 5 V INPS Current NPS operate level 100 Is 5 or 1 In Impedance 100 Zs 5 or 0 1 Ω Repeatability 1 3 8 3 Operate Angle Attribute Value Operating angle forward 21LB 3P Angle ve 5 to 21LB 3P Angle ve 5 reverse 180 21LB 3P Angle ...

Page 377: ... to 100 Ohms Vpps Vpps Level 1 V to 110 V Izps Izps Level 0 05 xIn to 5 xIn 3 9 2 Operate Level Attribute Value VPPS Voltage PPS operate level 100 Vs 2 or 0 5 V Voltage PPS reset level 110 VPPSop 5 Vn IZPS Current ZPS operate level 100 Is 5 or 1 In Impedance 100 Zs 5 or 0 1 Ω Repeatability 1 3 9 3 Operate Angle Attribute Value Operating angle forward 21LB 1P Angle ve 5 to 21LB 1P Angle ve 5 revers...

Page 378: ...iff Voltage Differential Setting 5 95 Θcs CS Angle 1 90 º Θss SS Angle 1 90 º fcoz COZ Slip 30 mHz 250 mHz fcs CS Slip Freq 20 mHz 250 mHz fss SS Slip Freq 10 mHz 250 mHz tcs CS Timer 0 100 s tss SS Timer 0 1 s fsps Split Slip 20 mHz 250 mHz tdlc tdbc DLC DBC Delays 0 60 s tcw Sync Close Window 1 s 1200 s 4 1 2 Live Dead Line Bus Detector Elements Attribute Value Vlive act Live operate level 100 V...

Page 379: ... level Vop 4 Repeatability 2 4 1 5 General Autoreclose Timers Attribute Value tbasic Element basic operate time 20 ms 20 ms top tdlc tdbc tcw top tbasic 1 Repeatability 20 ms 4 1 6 CS SS COZ Line and Bus Phase Angle Difference Attribute Value qop Operate angle qdiff 1 º Reset angle qop 1 º Repeatability 1 º 4 1 7 CS SS COZ Slip Frequency Attribute Value fop Operate frequency fslip 10 mHz Reset fre...

Page 380: ...rate frequency fslip 10 mHz Reset frequency fop 10 mHz Repeatability 10 mHz 4 2 Live Dead 4 2 1 Reference Parameter Value Vs Setting ABC side 5 5 5 200 V Vs Setting XYZ side 5 5 5 120 V 4 2 2 Live Dead Detector Elements Attribute Value Vlive act Live operate level 100 Vlive 1 Vn Live reset level Vdead act 1 Vn Vdead act Dead operate level 100 Vdead 1 Vn Dead reset level Vlive act 1 Vn Repeatabilit...

Page 381: ...roduced or modified or stored in another form in any data retrieval system without the permission of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by an...

Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...

Page 383: ...4 3 Disturbance Recorder Actual Channel ACC Numbers 33 4 MODBUS Definitions 35 4 1 Introduction 35 4 2 MODBUS Register Data Types 36 4 2 1 FLOAT_IEEE_754 36 4 2 2 FP_32BITS_3DP 37 4 2 3 UINT32 37 4 2 4 UINT16 37 4 2 5 EVENT 38 4 2 6 EVENTCOUNT 39 4 2 7 TIME_METER 39 4 2 8 STR32 STR64 39 4 2 9 BITSTRING 39 4 3 Point List 41 4 3 1 Coils Read Write Binary values 41 4 3 2 Inputs Read Only Binary value...

Page 384: ...Figures Fig 2 1 Communication to Front USB Port 8 Fig 2 2 Communication to Multiple Devices using RS485 Standard Port 10 Fig 2 3 Communication to Multiple Devices using Fibre optic Ring Network 13 Fig 2 4 Communication to Multiple Devices from Control System and Laptop using Fibre optic Star Network 13 Fig 2 5 Additional Optional Rear RS485 IRIG B Connection to a PC 14 Fig 2 6 Additional Optional ...

Page 385: ...ns protocols DNP3 IEC 60870 5 103 IEC 61850 and MODBUS RTU Note not all protocols are available on all devices Reydisp Evolution or Reydisp Manager Software is available for computers running Microsoft Windows to connect to devices to provide operational information post fault analysis setting interrogation and editing facilities etc Configuration software can be downloaded from our website http w...

Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...

Page 387: ...g communication with the Reydisp software An ASCII protocol is also available through this port the main use of this protocol is to allow the Relay firmware to be updated via the front connection MODBUS RTU or the optional DNP3 protocols are also available COM3 Where fitted an additional rear serial fibre optic RS232 or RS485 port This port can be used for IEC60870 5 103 MODBUS RTU or DNP3 communi...

Page 388: ...out the need to first change any settings Access to the communication settings for the USB port is only available from the relay front fascia via the key pad setting menu COMMUNICATIONS MENU Setting Name Range Options Default Setting Notes COM2 USB Protocol OFF IEC60870 5 103 MODBUS RTU ASCII DNP3 IEC60870 5 103 Reydisp software requires IEC60870 5 103 COM2 USB Station Address 0 254 for IEC60870 5...

Page 389: ...cted in reverse communication to all devices will be disturbed but no damage will occur If problems are experienced during commissioning the connections should be tried in reverse The maximum number of relays that can be connected to the bus is 64 The RS485 data comms link will be broken for that particular relay element if it is withdrawn from the case but the chain of communication to the other ...

Page 390: ...llations The following table gives the launch power and receiver sensitivity of each of the fibre optic communication ports on the Relay when used with specific fibre optic types Fibre Type 62 5 125µm Tx Launch Power dB RX Receive Sensitivity dB Min 11 7 Max 15 7 Min 24 Max 9 2 1mm Polymer 6 4 10 4 24 9 2 200µm PCS 2 8 6 8 24 9 2 Factors to be considered when calculating fibre optic transmission d...

Page 391: ... at connectors IxJ dB L Total losses E H K dB M N Receive power budget A L Safety Margin dB dB O Device Receive Sensitivity dB The following settings on the COMMUNICATIONS MENU must be configured when using the fibre Optic Com3 interface Setting Name Range Options Default Setting Notes COM3 Protocol OFF IEC60870 5 103 MODBUS RTU DNP3 IEC60870 5 103 The protocol used to communicate on the standard ...

Page 392: ...Default Setting Notes COM4 Protocol OFF IEC60870 5 103 MODBUS RTU DNP3 IEC60870 5 103 The protocol used to communicate on the standard RS485 connection COM4 0 254 for IEC60870 5 103 0 An address within the range of the relevant protocol must be Station 1 247 for Modbus RTU given to identify the Address 0 65534 for DNP3 0 relay Each relay in a network must have a unique address The baud rate set on...

Page 393: ...ultiple Devices using Fibre optic Ring Network To Control System 7SG24 Sigma 1 Tx Master Rx Rx Rx Tx Tx Tx Rx Tx Rx Tx Rx RS232 straight through cable Tx Rx Computer or Control System Rx Tx 62 5 125µm fibre optic with ST connectors USB or 9 pin male D connector 25 pin male D connector Fig 2 4 Communication to Multiple Devices from Control System and Laptop using Fibre optic Star Network 2 5 Option...

Page 394: ... as the 57600 115200 one set on the master device The parity set on all of the relays COM3 NONE ODD EVEN connected to the control system must Parity EVEN be the same and in accordance with the master device COM3 Line Idle LIGHT ON LIGHT OFF LIGHT OFF LIGHT OFF Not applicable for RS 485 or RS 232 option set to OFF COM3 Data Echo 1 ON OFF OFF OFF Not applicable for RS 485 or RS 232 option set to OFF...

Page 395: ...l system must Baud Rate 9600 19200 38400 be the same as the 57600 115200 one set on the master device The parity set on all of the relays COM3 Parity NONE ODD EVEN EVEN connected to the control system must be the same and in accordance with the master device COM3 Line Idle LIGHT ON LIGHT OFF LIGHT OFF LIGHT OFF Not applicable for RS 485 or RS 232 option set to OFF COM3 Data Echo 1 ON OFF OFF OFF N...

Page 396: ...is setting is set to off access to relay data using Reydisp Evolution and Reydisp Manager Software via the Ethernet interface is not available Connections to the optional EN100 Ethernet module are made on the rear underside of the relay Connections are made to either RJ45 sockets electrical or Duplex LC fibre optic connectors Fibre cables should be 62 5 125µm or 50 125µm multimode with LC connecto...

Page 397: ... of 96 L LED green LED green EN100 Module RJ45 Interface EN100 Module Duplex LC Interface Green LED Physical Link Off No link On Link present Yellow LED Activity Off No traffic On flashing Traffic Fig 2 8 EN100 Ethernet Module Ethernet EN100 O Ch 1 Ch 2 Ethernet EN100 E Ch 1 Ch 2 ED yellow LED yellow ...

Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...

Page 399: ...ng as a slave responding to the master s commands The implementation provides event information time synchronising commands and measurands and also supports the transfer of disturbance records This protocol can be set to use any or all of the relays hardware interfaces USB Fibre Optic RS232 RS485 and Ethernet where fitted and is the standard protocol used by the USB port The relay can communicate ...

Page 400: ...ction table lists possible causes of transmission for these frames The following abbreviations are used Abbreviation Description SE spontaneous event T test mode GI general interrogation Loc local operation Rem remote operation Ack command acknowledge Nak Negative command acknowledge Note Events listing a GI cause of transmission can be raised and cleared other events are raised only ...

Page 401: ...column of the Information Number and Function table lists the possible ASDUs returned for a point ASDU Description 1 Time tagged message monitor direction 2 3 1 Time tagged message relative time monitor direction Measurands I 4 Time tagged measurands with relative time 5 Identification message 6 Time synchronisation 7 9 General Interrogation Initialization Measurands II 20 General command ...

Page 402: ...trol Received 1 SE 60 13 Command Received 1 SE 60 128 Cold Start 1 SE 60 129 Warm Start 1 SE 60 130 Re Start 1 SE 60 131 Expected Restart 1 SE GI 60 132 Unexpected Restart 1 SE GI 60 133 Reset Start Count 1 20 SE Ack Nak 60 135 Trigger Storage 1 SE 60 136 Clear Waveform Records 1 SE 60 137 Clear Fault Records 1 SE 60 138 Clear Event Records 1 SE 60 140 Demand metering reset 1 SE 20 Ack Nak 1 SE GI...

Page 403: ...1 5 General Alarm 17 1 SE GI 61 6 General Alarm 18 1 SE GI 61 7 General Alarm 19 1 SE GI 61 8 General Alarm 20 1 SE GI 70 5 Binary Input 5 1 SE GI 70 6 Binary Input 6 1 SE GI 70 7 Binary Input 7 1 SE GI 70 8 Binary Input 8 1 SE GI 70 9 Binary Input 9 1 SE GI 70 10 Binary Input 10 1 SE GI 70 11 Binary Input 11 1 SE GI 70 12 Binary Input 12 1 SE GI 70 13 Binary Input 13 1 SE GI 75 1 Virtual Input 1 ...

Page 404: ... 80 11 80 12 Binary Output 10 Binary Output 11 Binary Output 12 1 SE GI 20 Ack Nak 1 SE GI 20 Ack Nak 1 SE GI 20 Ack Nak 80 13 Binary Output 13 1 SE GI 20 Ack Nak 80 14 Binary Output 14 1 SE GI 20 Ack Nak 90 1 LED 1 1 SE GI 90 2 90 3 LED 2 LED 3 1 SE GI 1 SE GI 90 4 90 5 LED 4 LED 5 1 SE GI 1 SE GI 90 6 LED 6 1 SE GI 90 7 90 8 LED 7 LED 8 1 SE GI 1 SE GI 90 9 90 10 LED 9 LED 10 1 SE GI 1 SE GI 90 ...

Page 405: ... SE GI 20 Ack Nak 160 24 Setting G2 selected 1 SE GI 20 Ack Nak 160 25 Setting G3 selected 1 20 SE GI Ack Nak 160 26 Setting G4 selected 1 20 SE GI Ack Nak 160 27 Binary Input 1 1 SE GI 160 28 Binary Input 2 1 SE GI 160 29 Binary Input 3 1 SE GI 160 30 Binary Input 4 1 SE GI 160 36 Trip Circuit Fail 1 SE GI 160 38 VT Fuse Failure 1 SE GI 160 51 Earth Fault Forward Line 2 SE GI 160 52 Earth Fault R...

Page 406: ...3 22 51 3 2 SE GI 183 23 50 3 2 SE GI 183 24 51N 3 2 SE GI 183 25 50N 3 2 SE GI 183 26 51G 3 2 SE GI 183 27 50G 3 2 SE GI 183 28 51 4 2 SE GI 183 29 50 4 2 SE GI 183 30 51N 4 2 SE GI 183 31 50N 4 2 SE GI 183 32 51G 4 2 SE GI 183 33 50G 4 2 SE GI 183 34 50BF Stage 2 2 SE GI 183 35 49 Alarm 2 SE GI 183 36 49 Trip 2 SE GI 183 40 60 CTS 2 SE GI 183 41 51SEF 1 2 SE GI 183 42 50SEF 1 2 SE GI 183 43 51SE...

Page 407: ... 183 94 81 5 2 SE GI 183 95 81 6 2 SE GI 183 96 81HBL2 1 SE GI 183 100 CB Alarm 1 SE GI 183 101 Trip Circuit Fail 1 2 SE GI 183 102 Trip Circuit Fail 2 2 SE GI 183 103 Trip Circuit Fail 3 2 SE GI 183 110 Setting G5 selected 1 SE GI 20 Ack Nak 183 111 Setting G6 selected 1 SE GI 20 Ack Nak 183 112 Setting G7 selected 1 SE GI 20 Ack Nak 183 113 Setting G8 selected 1 20 SE GI Ack Nak 183 114 Close CB...

Page 408: ...d 1 SE GI 1 SE GI 183 163 183 164 Trip Time Alarm Close Circuit Fail 1 1 SE 2 SE GI 183 165 Close Circuit Fail 2 2 SE GI 183 166 183 167 Close Circuit Fail 3 Close Circuit Fail 2 SE GI 2 SE GI 183 168 183 169 Distance To Fault Distance To Fault Percent 1 SE 1 SE 183 170 Fault Reactance 1 SE 183 171 183 172 60 CTS I Act Energy Exp 2 SE GI 4 SE 183 173 183 174 Act Energy Imp React Energy Exp 4 SE 4 ...

Page 409: ...E GI 183 221 Wattmetric Po 1 SE GI 183 222 37 PhA 2 SE GI 183 223 37 PhB 2 SE GI 183 224 37 PhC 2 SE GI 183 231 50BF PhA 2 SE GI 183 232 50BF PhB 2 SE GI 183 233 50BF PhC 2 SE GI 183 234 50BF EF 2 SE GI 183 235 79 Last Trip Lockout 2 SE GI 183 237 CB DBI 1 SE GI 183 238 CB Travelling 1 SE GI 183 239 In Fault Current 4 SE 183 240 Ia Fault Current 4 SE 183 241 Ib Fault Current 4 SE 183 242 Ic Fault ...

Page 410: ...GI 185 181 User Output 11 1 SE GI 185 182 User Output 12 1 SE GI 185 183 User Output 13 1 SE GI 185 184 User Output 14 1 SE GI 185 185 User Output 15 1 SE GI 185 186 User Output 16 1 SE GI 185 187 User Output 17 1 SE GI 185 188 User Output 18 1 SE GI 185 189 User Output 19 1 SE GI 185 190 User Output 20 1 SE GI 185 191 User Output 21 1 SE GI 185 192 User Output 22 1 SE GI 185 193 User Output 23 1 ...

Page 411: ...ash 1 SE GI 186 14 AFD Zone 5 1 SE GI 186 15 AFD Zone 6 Flash 1 SE GI 186 16 AFD Zone 6 1 SE GI 186 17 AFD Zone1 Count 4 SE 186 18 AFD Zone2 Count 4 SE 186 19 AFD Zone3 Count 4 SE 186 20 AFD Zone4 Count 4 SE 186 21 AFD Zone5 Count 4 SE 186 22 AFD Zone6 Count 4 SE 200 1 CB 1 1 20 SE Ack Nak 200 6 CB 1 Opened 1 SE GI 20 Ack Nak 200 7 CB 1 Closed 1 SE GI 20 Ack Nak 200 150 User SP Command 1 1 SE GI 2...

Page 412: ...5 0 General Interrogation GI Initiation General Interrogation GI End 7 Init GI 8 End of GI 255 0 Time Synchronisation 6 Time Synch 3 4 2 Measurands The following Measurand EVT and INF numbers apply to this device FUN INF Description ASDU COT 183 148 Measurand IL1 2 3 VL1 2 3 P Q F VL1 2 L2 3 L3 1 IL1 2 4x Window 1 IL2 2 4x Window 1 IL3 2 4x Window 1 VL1 1 2x Window 1 VL2 1 2x Window 1 VL3 1 2x Win...

Page 413: ...g nominal 9 Cyclic Refresh rate 5 seconds or value change greater than Window x 183 236 Measurand Max Ia b c Van bn cn P Q Vab bc ca Ia Max 2 4x Window 1 Ib Max 2 4x Window 1 Ic Max 2 4x Window 1 Van Max1 1 2x Window 1 Vbn Max2 1 2x Window 1 Vcn Max3 1 2x Window 1 P Max 2 4x Window 1 Q Max 2 4x Window 1 Vab Max 1 2x Window 1 Vbc Max 1 2x Window 1 Vca Max 1 2x Window 1 Voltages only supported on 7S...

Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...

Page 415: ...ibre Optic RS232 and RS485 where fitted The relay can communicate simultaneously on all ports regardless of protocol used The Station Address of the port being used must be set to a suitable address within the range 1 247 to enable communication This can be set by the Communications Menu COM n xxxxx Station Address setting Communication via MODBUS over Ethernet requires external devices Please ref...

Page 416: ... instance xyz The mantissa represents the binary fraction of a number therefore the MSB represents 2 1 or 1 2 1 and its LSB 2 23 or 1 2 23 The following table shows a detailed layout of the mantissa 1 21 1 22 1 23 1 24 1 221 1 222 1 223 0 5 0 25 0 125 0 0625 4 768e 7 2 384e 7 1 192e 7 As an example 1 000 000 would be represented as follows hex 49742400 4 9 7 4 2 4 0 0 0 1 0 0 1 0 0 1 0 1 1 1 0 1 0...

Page 417: ...tion these two registers should be interpreted in the correct order as a 32 bit integer 4 2 3 UINT32 The UINT32 is a signed 32 bit integer As it is an integer negative numbers are sent as 2 s complement UINT32 MODBUS In this MODBUS implementation the 32 bit value is stored in 2 16 bit registers in Big Endian format As an example if we take the hex representation of 123456 in 2 s complement we have...

Page 418: ...an be checked periodically to determine how many events are stored The format of the event record is defined by the zero byte It signifies the type of record which is used to decode the event information The zero byte can be one of the following Format The format of the event record is defined by the zero byte It signifies the type of record which is used to decode the event information The zero b...

Page 419: ...s follows The following table describes the fields in the time Key Description ms L Time Stamp Milliseconds low byte ms H Time Stamp Milliseconds high byte Mi Time Stamp Minutes MSB invalid time not set 23 hours Ho Time Stamp Hours MSB Summer time flag Da Time Stamp Days Mo Time Stamp Months Ye L Time Stamp Years low byte Ye H Time Stamp Years high byte Not Used The following table shows the field...

Page 420: ...n a 16 bit register in Big Endian format As an example assume bits 1 3 9 and 12 are set The binary representation of this would be 00001001000001012 giving a hex representation of 0905h Assume this is stored in the register 30001 it would look as follows On reception this register should be interpreted as a 16 bit integer Address 30001 Value 0905 ...

Page 421: ... 11 00012 Binary Output 12 00013 Binary Output 13 00014 Binary Output 14 00101 Setting G1 selected 00102 Setting G2 selected 00103 Setting G3 selected 00104 Setting G4 selected 00105 Setting G5 selected 00106 Setting G6 selected 00107 Setting G7 selected 00108 Setting G8 selected 00109 CB 1 00112 Auto reclose active 00113 HotLine Working 00114 E F Out 00115 SEF Out 00116 Inst Protection Out 00155 ...

Page 422: ... 1 10002 Binary Input 2 10003 Binary Input 3 10004 Binary Input 4 10005 Binary Input 5 10006 Binary Input 6 10007 Binary Input 7 10008 Binary Input 8 10009 Binary Input 9 10010 Binary Input 10 10011 Binary Input 11 10012 Binary Input 12 10013 Binary Input 13 10102 Remote Mode 10103 Out Of Service Mode 10104 Local Mode 10105 Local Remote 10110 General Trip 10111 Trip Circuit Fail 10112 Start Pick u...

Page 423: ...10137 50N 3 10138 51G 3 10139 50G 3 10140 51 4 10141 50 4 10142 51N 4 10143 50N 4 10144 51G 4 10145 50G 4 10146 50BF Stage 2 10147 49 Alarm 10148 49 Trip 10149 60 CTS 10150 46IT 10151 46DT 10152 47 1 10153 47 2 10154 46BC 10155 27 59 1 10156 27 59 2 10157 27 59 3 10158 27 59 4 10159 59NIT 10160 59NDT 10161 81 1 10162 81 2 10163 81 3 10164 81 4 10165 81 5 10166 81 6 10167 64H 10168 37 1 10169 37 2 ...

Page 424: ... 10203 50SEF 1 10204 51SEF 2 10205 50SEF 2 10206 51SEF 3 10207 50SEF 3 10208 51SEF 4 10209 50SEF 4 10210 SEF Out 10211 Trip Circuit Fail 1 10212 Trip Circuit Fail 2 10213 Trip Circuit Fail 3 10214 CB Total Trip Count 10215 CB Delta Trip Count 10216 CB Count To AR Block 10217 CB Frequent Ops Count 10218 I 2t CB Wear 10219 CB 1 Opened 10220 CB 1 Closed 10283 Close Circuit Fail 1 10284 Close Circuit ...

Page 425: ...ic E13 10315 Quick Logic E14 10316 Quick Logic E15 10317 Quick Logic E16 10334 60 CTS I 10335 81HBL2 10336 37G 1 10337 37G 2 10338 37SEF 1 10339 37SEF 2 10352 25 System Split 10353 25 Live Line 10354 25 Live Bus 10355 25 Line U V 10356 25 Bus U V 10357 25 Voltage Dif 10358 25 CS Slip Freq 10359 25 SS Slip Freq 10360 25 COZ Slip Freq 10361 25 In Sync 10362 25 CS In Progress 10363 25 SS In Progress ...

Page 426: ... General Alarm 19 10418 General Alarm 20 10501 Virtual Input 1 10502 Virtual Input 2 10503 Virtual Input 3 10504 Virtual Input 4 10505 Virtual Input 5 10506 Virtual Input 6 10507 Virtual Input 7 10508 Virtual Input 8 10509 Virtual Input 9 10510 Virtual Input 10 10511 Virtual Input 11 10512 Virtual Input 12 10513 Virtual Input 13 10514 Virtual Input 14 10515 Virtual Input 15 10516 Virtual Input 16 ...

Page 427: ...802 Re Start 10803 Power On 10804 Expected Restart 10805 Unexpected Restart 10806 Reset Start Count 10900 User SP Command 1 10901 User SP Command 2 10902 User SP Command 3 10903 User SP Command 4 10904 User SP Command 5 10905 User SP Command 6 10906 User SP Command 7 10907 User SP Command 8 10908 User DP Command 1 10909 User DP Command 2 10910 User DP Command 3 10911 User DP Command 4 10912 User D...

Page 428: ...1039 User Output 20 11040 User Output 21 11041 User Output 22 11042 User Output 23 11043 User Output 24 11044 User Output 25 11045 User Output 26 11046 User Output 27 11047 User Output 28 11048 User Output 29 11049 User Output 30 11050 User Output 31 11051 User Output 32 11071 E F In 11072 SEF In 11073 CB DBI 11074 CB Travelling 11075 Close CB Failed 11076 Open CB Failed 11077 Start Count Alarm 11...

Page 429: ...Vab Degrees 30036 Vbc Nominal FP_32BITS_3DP 1 000000 Vbc Degrees 30038 Vca Nominal FP_32BITS_3DP 1 000000 Vca Degrees 30040 Va Nominal FP_32BITS_3DP 1 000000 Va Degrees 30042 Vb Nominal FP_32BITS_3DP 1 000000 Vb Degrees 30044 Vc Nominal FP_32BITS_3DP 1 000000 Vc Degrees 30048 Vzps FP_32BITS_3DP 1 000000 Vzps V 30050 Vpps FP_32BITS_3DP 1 000000 Vpps V 30052 Vnps FP_32BITS_3DP 1 000000 Vnps V 30054 ...

Page 430: ...3DP 0 000001 Phase A VA 30130 Apparent Power B FP_32BITS_3DP 0 000001 Phase B VA 30132 Apparent Power C FP_32BITS_3DP 0 000001 Phase C VA 30134 S 3P FP_32BITS_3DP 0 000001 3 Phase VA 30136 Power Factor A FP_32BITS_3DP 1 000000 Phase A 30138 Power Factor B FP_32BITS_3DP 1 000000 Phase B 30140 Power Factor C FP_32BITS_3DP 1 000000 Phase C 30142 Power Factor 3P FP_32BITS_3DP 1 000000 3 Phase 30144 Ac...

Page 431: ...3DP 1 000000 Ic Fault 30307 Va Last Trip FP_32BITS_3DP 1 000000 Va Fault 30309 Vb Last Trip FP_32BITS_3DP 1 000000 Vb Fault 30311 Vc Last Trip FP_32BITS_3DP 1 000000 Vc Fault 30313 In Last Trip FP_32BITS_3DP 1 000000 In Fault 30315 Ig Last Trip FP_32BITS_3DP 1 000000 Ig Fault 30317 Isef Last Trip FP_32BITS_3DP 1 000000 Isef Fault 30319 V Phase A Max FP_32BITS_3DP 1 000000 Va Max Demand 30321 V Pha...

Page 432: ...3P Max 30444 Sec Active Power A FP_32BITS_3DP 1 000000 Secondary A Phase W 30446 Sec Active Power B FP_32BITS_3DP 1 000000 Secondary B Phase W 30448 Sec Active Power C FP_32BITS_3DP 1 000000 Secondary C Phase W 30450 Sec P 3P FP_32BITS_3DP 1 000000 Secondary 3 Phase W 30452 Sec Reactive Power A FP_32BITS_3DP 1 000000 Secondary Phase A VAr 30454 Sec Reactive Power B FP_32BITS_3DP 1 000000 Secondary...

Page 433: ...upported the complete list is described in the attached table For static non change event object requests request qualifier codes 07 and 08 limited quantity and 17 and 28 index are supported Static object requests sent with qualifiers 07 or 08 will be responded with qualifiers 00 or 01 Output Event Object 11 is supported Maximum Data Link Frame Size octets Transmitted 256 Received 256 Maximum Appl...

Page 434: ...e Pulse On Never Always Sometimes Configurable Pulse Off Never Always Sometimes Configurable Latch On Never Always Sometimes Configurable Latch Off Never Always Sometimes Configurable Queue Never Always Sometimes Configurable Clear Queue Never Always Sometimes Configurable Attach explanation if Sometimes or Configurable was checked for any operation Reports Binary Input Change Events when no speci...

Page 435: ...CUMENT Also see the DNP 3 0 Implementation Table in Section 5 2 beginning on page 56 File Transfer Support Append File Mode Yes Yes No No Custom Status Code Strings Yes No Permissions Field Yes No File Events Assigned to Class Yes No File Events Send Immediately Yes No Multiple Blocks in a Fragment Max Number of Files Open 0 Yes No ...

Page 436: ...9 response 00 01 start stop 17 28 index see note 2 2 0 Binary Input Change Any Variation 1 read 06 no range or all 07 08 limited qty 2 1 Binary Input Change without Time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 2 2 default see note 1 Binary Input Change with Time 1 read 06 no range or all 07 08 limited qty 129 17 28 index response 130 unsol resp 129 2 3 B...

Page 437: ... 12 2 3 3 select Pattern Control Block 3 select Pattern Mask 7 limited quantity 00 01 start stop 129 echo of request response 129 echo of request response 13 0 Binary Output Command Event 1 read Any Variation 06 no range or all 07 08 limited qty 13 1 default see note 1 Binary Output Command Event 1 read without Time 06 no range or all 07 08 limited qty 129 response 17 28 index 130 unsol resp 13 2 ...

Page 438: ... 6 16 Bit Frozen Counter without Time Of Freeze 1 read 00 01 start stop 06 no range or all 07 08 limited qty 17 27 28 index 129 response 00 01 start stop 17 28 index see note 2 21 7 32 Bit Frozen Delta Counter with Time Of Freeze 21 8 16 Bit Frozen Delta Counter with Time Of Freeze 21 9 default see note 1 32 Bit Frozen Counter without Flag 1 read 00 01 start stop 06 no range or all 07 08 limited q...

Page 439: ...og Input Any Variation 1 read 22 assign class 00 01 start stop 06 no range or all 07 08 limited qty 17 27 28 index 30 1 32 Bit Analog Input 1 read 00 01 start stop 06 no range or all 07 08 limited qty 17 27 28 index 129 response 00 01 start stop 17 28 index see note 2 30 2 default see note 1 16 Bit Analog Input 1 read 00 01 start stop 06 no range or all 07 08 limited qty 17 27 28 index 129 respons...

Page 440: ...point Analog Change Event with Time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 32 8 long floating point Analog Change Event with Time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 33 0 Frozen Analog Event Any Variation 33 1 32 Bit Frozen Analog Event without Time 33 2 16 Bit Frozen Analog Event without Time 33 3 32 Bit ...

Page 441: ...unsol 22 assign class 1 read 06 no range or all 06 no range or all 07 08 limited qty 20 enbl unsol 21 dab unsol 22 assign class 1 read 06 no range or all 06 no range or all 07 08 limited qty 20 enbl unsol 21 dab unsol 22 assign class 06 no range or all 80 1 Internal Indications 1 read 00 01 start stop 129 00 01 start stop response 2 write see note 3 00 start stop index 7 No Object 13 cold restart ...

Page 442: ...y inputs are by default returned in a class zero interrogation Note not all points listed here apply to all builds of devices Binary Input Points Static Steady State Object Number 1 Packed Format Change Event Object Number 1 w o Time Static Variation reported when variation 0 requested 1 Binary Input w o status or 2 Binary Input with status Change Event Variation reported when variation 0 requeste...

Page 443: ...2 44 Start Pick up L3 0 2 2 2 45 General Start Pick up 0 2 2 2 46 VT Fuse Failure 0 2 2 2 47 Earth Fault Forward Line 0 2 2 2 48 Earth Fault Reverse Busbar 0 2 2 2 49 Start Pick up N 0 2 2 2 50 Fault Forward Line 0 2 2 2 51 Fault Reverse Busbar 0 2 2 2 52 51 1 0 2 2 2 53 50 1 0 2 2 2 54 51N 1 0 2 2 2 55 50N 1 0 2 2 2 56 51G 1 0 2 2 2 57 50G 1 0 2 2 2 58 51 2 0 2 2 2 59 50 2 0 2 2 2 60 51N 2 0 2 2 ...

Page 444: ...0 2 2 2 92 51 4 0 2 2 2 93 50 4 0 2 2 2 94 51N 4 0 2 2 2 95 50N 4 0 2 2 2 96 51G 4 0 2 2 2 97 50G 4 0 2 2 2 98 Cold Load Active 0 2 2 2 99 E F Out 0 2 2 2 100 P F Inst Protection Inhibited 0 2 2 2 101 E F Inst Protection Inhibited 0 2 2 2 102 SEF Inst Protection Inhibited 0 2 2 2 103 Ext Inst Protection Inhibited 0 2 2 2 117 51SEF 1 0 2 2 2 118 50SEF 1 0 2 2 2 119 51SEF 2 0 2 2 2 120 50SEF 2 0 2 2...

Page 445: ... 218 37 2 0 2 2 2 219 CB Alarm 0 2 2 2 225 General Alarm 1 0 2 2 2 226 General Alarm 2 0 2 2 2 227 General Alarm 3 0 2 2 2 228 General Alarm 4 0 2 2 2 229 General Alarm 5 0 2 2 2 230 General Alarm 6 0 2 2 2 231 General Alarm 7 0 2 2 2 232 General Alarm 8 0 2 2 2 233 General Alarm 9 0 2 2 2 234 General Alarm 10 0 2 2 2 235 General Alarm 11 0 2 2 2 236 General Alarm 12 0 2 2 2 237 Quick Logic E1 0 2...

Page 446: ... 50BF PhC 0 2 2 2 286 50BF EF 0 2 2 2 287 79 Last Trip Lockout 0 2 2 2 288 60 CTS I PhA 0 2 2 2 289 60 CTS I PhB 0 2 2 2 290 60 CTS I PhC 0 2 2 2 291 Trip PhA 0 2 2 2 292 Trip PhB 0 2 2 2 293 Trip PhC 0 2 2 2 302 27 59 PhA 0 2 2 2 303 27 59 PhB 0 2 2 2 304 27 59 PhC 0 2 2 2 310 General Alarm 13 0 2 2 2 311 General Alarm 14 0 2 2 2 312 General Alarm 15 0 2 2 2 313 General Alarm 16 0 2 2 2 314 Gener...

Page 447: ...2 411 Setting G1 selected 0 2 2 2 412 Setting G2 selected 0 2 2 2 413 Setting G3 selected 0 2 2 2 414 Setting G4 selected 0 2 2 2 415 Setting G5 selected 0 2 2 2 416 Setting G6 selected 0 2 2 2 417 Setting G7 selected 0 2 2 2 418 Setting G8 selected 0 2 2 2 420 79 AR In progress 0 2 2 2 422 HotLine Working 0 2 2 2 425 Inst Protection Out 0 2 2 2 427 CB 1 0 2 2 2 434 Man Override Sync 0 2 2 2 435 7...

Page 448: ...611 LED 11 0 2 2 2 612 LED 12 0 2 2 2 613 LED 13 0 2 2 2 614 LED 14 0 2 2 2 615 LED 15 0 2 2 2 616 LED 16 0 2 2 2 701 LED PU 1 0 2 2 2 702 LED PU 2 0 2 2 2 703 LED PU 3 0 2 2 2 704 LED PU 4 0 2 2 2 705 LED PU 5 0 2 2 2 706 LED PU 6 0 2 2 2 707 LED PU 7 0 2 2 2 708 LED PU 8 0 2 2 2 709 LED PU 9 0 2 2 2 710 LED PU 10 0 2 2 2 711 LED PU 11 0 2 2 2 712 LED PU 12 0 2 2 2 713 LED PU 13 0 2 2 2 714 LED P...

Page 449: ... 0 2 2 2 891 CB 1 Closed 0 2 2 2 900 User SP Command 1 0 2 2 2 901 User SP Command 2 0 2 2 2 902 User SP Command 3 0 2 2 2 903 User SP Command 4 0 2 2 2 904 User SP Command 5 0 2 2 2 905 User SP Command 6 0 2 2 2 906 User SP Command 7 0 2 2 2 907 User SP Command 8 0 2 2 2 1010 User Output 1 0 2 2 2 1011 User Output 2 0 2 2 2 1012 User Output 3 0 2 2 2 1013 User Output 4 0 2 2 2 1014 User Output 5 ...

Page 450: ... User Output 32 0 2 2 2 1061 E F In 0 2 2 2 1062 SEF In 0 2 2 2 1063 CB DBI 0 2 2 2 1064 CB Travelling 0 2 2 2 1065 Close CB Failed 0 2 2 2 1066 Open CB Failed 0 2 2 2 1067 Start Count Alarm 0 2 2 2 1068 50AFD PhA 0 2 2 2 1069 50AFD PhB 0 2 2 2 1070 50AFD PhC 0 2 2 2 1071 50AFD 0 2 2 2 1072 AFD Zone 1 Flash 0 2 2 2 1073 AFD Zone 1 0 2 2 2 1074 AFD Zone 2 Flash 0 2 2 2 1075 AFD Zone 2 0 2 2 2 1076 ...

Page 451: ... Points are included here for completeness they are not often polled by DNP 3 0 Masters Binary Output Status points are not recommended to be included in class 0 polls As an alternative it is recommended that actual status values of Control Relay Output Block points be looped around and mapped as Binary Inputs The actual status value as opposed to the commanded status value is the value of the act...

Page 452: ...n Event Object 11 Default Command Event Object 13 Assigned Class 1 2 3 or none Default Variation Command Event Object 13 CROB Supported Operations Default CROB Operations 1 RL 1 0 2 2 0 1 Pulse On Pulse On Latch On Close Pulse On 2 RL 2 0 2 2 0 1 Latch On Pulse On Close 3 RL 3 0 2 2 0 1 Pulse On Latch On Close Pulse On 4 RL 4 0 2 2 0 1 Pulse On Latch On Close Pulse On 5 RL 5 0 2 2 0 1 Pulse On Pul...

Page 453: ...fault Variation Command Event Object 13 CROB Supported Operations Default CROB Operations 34 Settings Group 1 0 2 2 0 1 Pulse On Latch On Close Latch On 35 Settings Group 2 0 2 2 0 1 Pulse On Latch On Latch On Close Pulse On 36 Settings Group 3 0 2 2 0 1 Latch On Latch On Close 37 Settings Group 4 0 2 2 0 1 Pulse On Latch On Latch On Close Pulse On 38 Settings Group 5 0 2 2 0 1 Latch On Latch On C...

Page 454: ...ations Close Trip 46 Inst Protection off on 0 2 2 0 1 Pulse On Pulse Off Latch On Latch Off Close Trip Pulse On Pulse Off Latch On Latch Off 48 Reset CB Total Trip Count write only location 0 2 2 0 1 Pulse On Latch On Close Pulse On 49 Reset CB Delta Trip Count write only location 0 2 2 0 1 Pulse On Latch On Close Pulse On 50 Reset CB Count To AR Block write only location 0 2 2 0 1 Pulse On Latch ...

Page 455: ...3 or none Default Variation Command Event Object 13 CROB Supported Operations Default CROB Operations 90 Local mode 0 2 2 0 1 Pulse On Latch On Close Pulse On 91 Local Remote 0 2 2 0 1 Pulse On Latch On Pulse On Close Pulse On Pulse Off Pulse On 92 Man Override Sync on off 0 2 2 0 1 Latch On Latch Off Pulse Off Latch On Close Latch Off Trip 93 79 Override Sync on off 0 2 2 0 1 Pulse On Pulse Off L...

Page 456: ...nt Object 13 Assigned Class 1 2 3 or none Default Variation Command Event Object 13 CROB Supported Operations Default CROB Operations 103 User SP Command 5 0 2 2 0 1 Pulse On Latch On Close Pulse On 104 User SP Command 6 0 2 2 0 1 Pulse On Pulse On Latch On Close Pulse On 105 User SP Command 7 0 2 2 0 1 Latch On Pulse On Close 106 User SP Command 8 0 2 2 0 1 Pulse On Pulse On Latch On Close Pulse ...

Page 457: ... Object Number 13 Static Variation reported when variation 0 requested 1 Binary Output w o status or 2 Binary Output with status Change Event Variation reported when variation 0 requested 1 Binary Output Event w o Time or 2 Binary Output Event with Time Command Event Variation reported when variation 0 requested 1 Command Status w o Time or 2 Command Status with Time Point Description Index Defaul...

Page 458: ...ozen Counter w o Flag or 10 16 Bit Frozen Counter w o Flag Change Event Variation reported when variation 0 requested 1 32 Bit Frozen Counter Event with Flag or 2 16 Bit Frozen Counter Event with Flag or 5 32 Bit Frozen Counter Event with Flag and Time or 6 16 Bit Frozen Counter Event with Flag and Time Counter Frozen Counter Point Index Description Default Change Event Assigned Class 1 2 3 or non...

Page 459: ...ss 1 2 3 or none Counter Frozen Counter Default Variation Static Object 20 Default Variation Event Object 22 Is Resettable IsFreezable Default Change Event Assigned Class 1 2 3 or none Default Variation Static Object 21 Default Variation Event Object 23 25 E5 Counter 0 3 5 1 1 0 2 9 1 26 E6 Counter 0 3 5 1 1 0 2 9 1 27 E7 Counter 0 3 5 1 1 0 2 9 1 28 E8 Counter 0 3 5 1 1 0 2 9 1 29 E9 Counter 0 3 ...

Page 460: ...ct 32 Default Multiplier Default Deadband 0 Frequency 0 3 2 4 100 000 1 000 1 Vab Primary 0 3 2 4 0 010 100 000 2 Vbc Primary 0 3 2 4 0 010 100 000 3 Vca Primary 0 3 2 4 0 010 100 000 4 Va Primary 0 3 2 4 0 010 100 000 5 Vb Primary 0 3 2 4 0 010 100 000 6 Vc Primary 0 3 2 4 0 010 100 000 7 Va Secondary 0 3 2 4 10 000 1 000 8 Vb Secondary 0 3 2 4 10 000 1 000 9 Vc Secondary 0 3 2 4 10 000 1 000 21 ...

Page 461: ... 1000000 000 60 P 3P 0 3 2 4 0 000 1000000 000 61 Reactive Power A 0 3 2 4 0 000 1000000 000 62 Reactive Power B 0 3 2 4 0 000 1000000 000 63 Reactive Power C 0 3 2 4 0 000 1000000 000 64 Q 3P 0 3 2 4 0 000 1000000 000 65 Apparent Power A 0 3 2 4 0 000 1000000 000 66 Apparent Power B 0 3 2 4 0 000 1000000 000 67 Apparent Power C 0 3 2 4 0 000 1000000 000 68 S 3P 0 3 2 4 0 000 1000000 000 71 Power ...

Page 462: ... 000 100 000 115 Isef Primary 0 3 2 4 1 000 10 000 116 Isef Secondary 0 3 2 4 1000 000 0 050 117 Isef Nominal 0 3 2 4 1000 000 0 050 118 Fault Distance Percent 0 3 2 4 100 000 Disabled 119 Fault Reactance 0 3 2 4 1000 000 Disabled 135 CB Total Trip Count 0 3 1 3 1 000 1 000 136 CB Delta Trip Count 0 3 1 3 1 000 1 000 137 CB Count To AR Block 0 3 1 3 1 000 1 000 138 CB Frequent Ops Count 0 3 1 3 1 ...

Page 463: ...00 Default Deadband 1000000 000 186 CB Wear C 0 3 1 3 0 000 1000000 000 187 CB Wear A Remaining 0 3 1 3 1 000 1 000 188 CB Wear B Remaining 0 3 1 3 1 000 1 000 189 CB Wear C Remaining 0 3 1 3 1 000 1 000 190 CB Wear Minimum 0 3 1 3 1 000 1 000 191 Fault Distance Perunit 0 3 5 7 0 001 1 000 196 Frequency Max 0 3 2 4 100 000 1 000 197 S 3P Max 0 3 2 4 0 000 1000000 000 318 Sec Active Power A 0 3 2 4...

Page 464: ...Limited Setting Name Range Options Default Setting Notes Destination Address 0 65534 0 As Required Setting is only visible when DNP3 Unsolicited Events set to Enabled DNP3 Application Timeout 5 6 299 300 10s As Required Setting is only visible when any port Protocol is set to DNP3 ...

Page 465: ...Chapter 4 Data Communications Definitions 2017 Siemens Protection Devices Limited Chapter 4 Page 85 of 96 6 Not Applicable This section intentionally left blank ...

Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...

Page 467: ...C61850 Protocol Support 7 1 Introduction The relay can optionally be provided with IEC61850 comms For further details refer to the following publications Model Implementation Conformance Statement MICS Protocol Implementation Conformance Statement PICS Protocol Implementation Extra Information for Testing PIXIT ...

Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...

Page 469: ...nfigured as auto answer This will allow it to initiate communications with the relays Next the user should set the data configuration at the local port i e baud rate and parity so that communication will be at the same rate and format as that set on the relay and the error correction is disabled Auto answer usually requires two parameters to be set The auto answer setting should be switched on and...

Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...

Page 471: ...Chapter 4 Data Communications Definitions 2017 Siemens Protection Devices Limited Chapter 4 Page 91 of 96 9 Not Applicable This section intentionally left blank ...

Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...

Page 473: ...s simultaneously Half Duplex Asynchronous Communications Communications in two directions but only one at a time Hayes AT Modem command set developed by Hayes Microcomputer products Inc LAN Local Area Network A computer network covering a small geographic area LC Fibre optic connector type designed by Lucent Technologies Inc Line Idle Determines when the device is not communicating if the idle sta...

Page 474: ...ices Limited Start Bit Bit logical 0 sent to signify the start of a byte during data transmission Stop Bit Bit logical 1 sent to signify the end USB Universal Serial Bus standard for the transfer of data WAN Wide Area Network A computer network covering a large geographic area ...

Page 475: ...Service Control Com1 when Com1 Mode Local when Com1 Mode Remote Com2 USB when Com2 Mode Local when Com2 Mode Remote Com3 when Com3 Mode Local Com4 when Com4 Mode Local when Com3 Mode Remote when Com4 Mode Remote Fascia Control Mode Function Key n Binary Input n when BI n Mode Local when F Key n Mode Remote when BI n Mode Remote Binary Outputs Reporting Spontaneous IEC DNP3 General Interrogation IE...

Page 476: ...s Limited Siemens Protection Devices Ltd SPDL P O Box 8 Hebburn Tyne and Wear NE31 1TZ United Kingdom For enquiries please contact our Customer Support Centre Tel 49 180 524 8437 24hrs Fax 49 180 524 2471 E Mail support ic siemens com www siemens com reyrolle Template Revision 17 ...

Page 477: ...e permission of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of negligence or any...

Page 478: ...dition of Disposal information 2018 10 Addition of check sync diagram Software Revision History 2011 05 2435H85008R7a 7a 7SR210 2435H85009R7a 7a 7SR220 First Release 2013 01 2435H85008R7c 7b 7SR210 2435H85009R7c 7b 7SR220 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line Check on non AR devices Added 74CCS Close Circuit ...

Page 479: ...Section 5 Connection Wiring Diagrams 19 5 1 Wiring Diagram 7SR21 OC EF Relay 19 5 2 Wiring Diagram 7SR22 Directional OC EF Relay 20 Section 6 Data Comms Connections 21 6 1 Standard RS485 Connections 21 6 2 IRIG B Connections 21 6 3 Additional Optional Fibre Optic Connections 22 6 4 Additional Optional RS485 Connections 23 6 5 Additional Optional RS232 Connections 23 6 6 Additional Optional Etherne...

Page 480: ...2 E12 Standard Additional Comms IRIG B RS485 See Note 2 16 Figure 4 3 3 E12 Standard Additional Comms IRIG B RS232 See Note 2 17 Figure 4 3 4 E12 Standard Additional Comms RS485 Ethernet x2 See Note 2 17 Figure 4 3 5 Standard Comms Additional Ethernet Ports RJ45 shown Duplex LC Fibre Optic similar 18 Figure 5 1 1 Connection Diagram for 7SR21 Relay 19 Figure 5 2 1 Connection Diagram for 7SR22 Relay...

Page 481: ... for any subsequent repairs 1 2 Recommended Mounting Position The relay uses a liquid crystal display LCD which is used in the programming and for operation The LCD has a vertical viewing angle of 30 and is back lit However the best viewing position is at eye level and this is particularly important given its control features The relay should be mounted on the circuit breaker or protection panel t...

Page 482: ...s not provide a threat to health or the environment All laws and regulations specific to the country of disposal should be adhered to 2 5 1 Environmental Protection Hints Disposal of Old Equipment and Batteries Applicable only for European Union and Countries with a Recycling System The disposal of our products and possible recycling of their components after decommissioning has to be carried out ...

Page 483: ...ing the format or delete functions only changes the file management information and does not completely delete the data from your mobile storage device When disposing of or transferring a mobile storage device Siemens strongly recommends physically destroying it or completely deleting data from the mobile storage device by using a commercially available computer data erasing software REACH RoHS De...

Page 484: ...PANELS HOLES TO BE M4 CLEARANCE TYPICALLY 4 5 DIAMETER AND RELAYS MOUNTED USING M4 MACHINE SCREWS NUTS AND LOCKWASHERS SUPPLIED IN PANEL FIXING KIT 2 ACCESS CLEARANCE REQUIRED FOR OPTIONAL ETHERNET COMMS MODULE RETAINING SCREW Case Earth connection TOP VIEW Optional ethernet comms module FRONT See note 2 PANEL CUT OUT 168 130 150 159 10 Diameter 3 6 4 holes see note FRONT VIEW 155 5 177 SIDE VIEW ...

Page 485: ...mm FOR ETHERNET COMMS MODULE 70mm FOR F O COMMS CABLE 75 mm MIN CLEARANCE FOR ETHERNET COMMS WIRING NOTE THE 3 6 HOLES ARE FOR M4 THREAD FORMING TRILOBULAR SCREWS THESE ARE SUPPLIED AS STANDARD AND ARE SUITABLE FOR USE IN FERROUS ALUMINIUM PANELS 1 6mm THICK AND ABOVE FOR OTHER PANELS HOLES TO BE M4 CLEARANCE TYPICALLY 4 5 DIAMETER AND RELAYS MOUNTED USING M4 MACHINE SCREWS NUTS AND LOCKWASHERS SU...

Page 486: ...ical Net Weight kg 7SR2102 4 2 7SR2103 4 6 7SR2104 4 8 7SR2105 8 4 7SR2106 8 4 7SR2202 4 8 7SR2203 4 9 7SR2204 5 3 7SR2205 8 4 7SR2206 8 4 NB For relays supplied with additional optional communication interface devices please add an additional 0 165 kg to the figures in the above table For relays supplied with Ethernet EN100 interface optional please add 0 1 kg to the figures in the above table ...

Page 487: ...4 off M4x10 mm Screws 4 off M4 Nuts 4 off M4 Lock Washers Typical rear terminal block fixing kit 1 kit per terminal block fitted to relay consists of 28 x M4 8 mm Screws 28 x M4 Lock Washers 3 2 3 Fibre Optic Connectors The relay has Fibre Optic STTM BFOC 2 5 bayonet connectors fitted when specified 3 2 4 Connectors Ethernet Option The relay has RJ45 connectors for electrical Ethernet and Duplex L...

Page 488: ...Figure 4 1 2 E6 Standard Additional Comms IRIG B 2 x F O ST Connectors See Note 2 Notes 1 Recommended terminations are pre insulated must be crimped using approved tooling 2 RS485 block B terms 14 16 18 20 connections to this communication facility is by screened twisted pair cable On site when wiring other facilities ensure that these terminals are not obscured by other wiring runs Cable should b...

Page 489: ...nstallation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 13 of 36 Figure 4 1 3 E6 Standard Additional Comms IRIG B RS485 See Note 2 Figure 4 1 4 E6 Standard Additional Comms IRIG B RS232 See Note 2 ...

Page 490: ...nrestricted Page 14 of 36 2018 Siemens Protection Devices Limited B C A 4 2 E8 Case Figure 4 2 1 E8 Standard Comms USB Front Port Rear RS485 See Note 2 Figure 4 2 2 E8 Standard Additional Comms IRIG B 2 x F O ST Connectors See Note 2 ...

Page 491: ...nstallation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 15 of 36 Figure 4 2 3 E8 Standard Additional Comms IRIG B RS485 See Note 2 Figure 4 2 4 E8 Standard Additional Comms IRIG B RS232 See Note 2 ...

Page 492: ...e Unrestricted Page 16 of 36 2018 Siemens Protection Devices Limited 4 3 E12 Case Figure 4 3 1 E12 Standard Additional Comms IRIG B 2 x F O ST Connectors See Note 2 Figure 4 3 2 E12 Standard Additional Comms IRIG B RS485 See Note 2 ...

Page 493: ...allation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 17 of 36 Figure 4 3 3 E12 Standard Additional Comms IRIG B RS232 See Note 2 Figure 4 3 4 E12 Standard Additional Comms RS485 Ethernet x2 See Note 2 ...

Page 494: ... Ports RJ45 shown Duplex LC Fibre Optic similar Notes 1 Recommended terminations are pre insulated must be crimped using approved tooling 2 RS485 block B terminals 14 16 18 20 and optional COMMS MODULE connections are by screened twisted pair cable Ensure that these terminals are not obscured by other wiring runs Cable should be RS485 compliant ...

Page 495: ...220 Installation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 19 of 36 Section 5 Connection Wiring Diagrams 5 1 Wiring Diagram 7SR21 OC EF Relay Figure 5 1 1 Connection Diagram for 7SR21 Relay ...

Page 496: ...7SR21 7SR22 Installation Guide Unrestricted Page 20 of 36 2018 Siemens Protection Devices Limited 5 2 Wiring Diagram 7SR22 Directional OC EF Relay RS485 Figure 5 2 1 Connection Diagram for 7SR22 Relay ...

Page 497: ...g the connection A terminating resistor is fitted in each relay when required this is connected in circuit using an external wire loop between terminals 18 and 20 of the power supply module Up to 64 relays can be connected to the RS485 bus The RS485 data communications link with a particular relay will be broken if the relay element is withdrawn from the case all other relays will still communicat...

Page 498: ...the fibre used typically 50 mm is acceptable Computer or Control System 7SG24 Tx Rx Tx Rx 62 5 125 µm fibre optic with ST connectors Tx Rx Tx Rx Tx Rx Tx Rx Tx Rx Tx Rx Master To Control System USB or 9 pin male D connector RS232 straight Through cable 25 pin male D connector Figure 6 3 1 Data Comms to Multiple Devices Using 7SG24 and F O Star Network Figure 6 3 2 Data Comms to Multiple Devices Us...

Page 499: ...are fitted with an internal terminating resistor which can be connected between the A and B by fitting an external wire loop between terminals 18 and 20 on the power supply module Figure 6 4 1 RS485 Data Comms Connections Between Relays 6 5 Additional Optional RS232 Connections The additional optional RS232 9 pin plug DTE communication port is located at the rear of the relay and can be connected ...

Page 500: ...With IEEE802 3 Fibre Optic or RJ45 100BaseF in acc With IEEE802 3 electrical connectors When installing fibre ensure that the fibres bend radii comply with the recommended minimum for the fibre used typically 50 mm is acceptable 62 5 125 mm glass fibre with Duplex LC connector recommended for all distances Figure 6 6 1 Ethernet connection for IEC 61850 star connection Figure 6 6 2 Ethernet connect...

Page 501: ...he EN100 module All current 7SR21 22 IEC61850 variants are delivered with the EN100 Plus module and firmware 4 24 or later The EN100 module firmware can be updated by connecting to the relay via the rear Ethernet port For more information on connecting to the relay via the Ethernet port please see the Reydisp Manager User guide Depending on the EN100 module type and Firmware version the following ...

Page 502: ...eydisp Manager user guide Network rings with up to 30 devices is possible Figure 6 7 1 1 RSTP Ethernet Network Ring Configuration 6 7 2 PRP Parallel Redundancy Protocol The HSR redundancy protocol according to the IEC 62439 3 standard is based on double transmission of message frames over ring topology networks in both directions In the case of an error the message frame will be transmitted withou...

Page 503: ...7SR210 7SR220 Installation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 27 of 36 Figure 6 7 2 1 PRP Ethernet Network Configuration ...

Page 504: ...s based on double transmission of message frames over ring topology networks in both directions In the case of an error the message frame will be transmitted without any delay No reconfiguration time is necessary for the network HSR needs to be enabled on the device within Reydisp Manager See Reydisp Manager user guide Network rings with up to 50 devices is possible Figure 6 7 3 1 HSR Ethernet Net...

Page 505: ...A 1A 5A 1A 5A 15 16 11 12 1A 5A 3 4 7 8 B C S1 S2 P2 L1 L2 L3 S1 S2 P1 V4 VX VL3 VC VL2 VB VL1 VA NOTES 1 CT circuits are shown connected to 1 A tap use alternative tap for 5 A rated CTs 2 CT and Earth connections are typical only 3 Application shows use of I5 as an REF input with external stabilising and voltage limiting resistor 4 Phase Voltage Config VanVbnVcn P2 P1 S1 S2 S1 S2 IL2 IB IL3 IC I4...

Page 506: ...stallation Guide Unrestricted Page 30 of 36 2018 Siemens Protection Devices Limited 7 2 Typical Connection 7SR22 Directional OC EF and NVD Figure 7 2 1 7SR22 Applied to Transformer Incomer Including HV NVD Protection ...

Page 507: ...o 1 A tap use alternative tap for 5 A rated CTs 2 CT and Earth connections are typical only 3 Application shows use of V4 as an NVD input 4 Star Connected VT Phase Voltage Config Van Vbn Vcn IL1 IA 1 2 5 6 9 10 13 14 A 17 18 19 20 21 22 23 24 25 26 27 28 1A 5A 1A 5A 1A 5A 1A 5A 15 16 11 12 1A 5A 3 4 7 8 B C V4 VX VL3 VC VL2 VB VL1 VA IL2 IB IL3 IC I4 IG I5 ISEF Figure 7 3 1 7SR22 Applied to Feeder...

Page 508: ... P1 P2 IL1 IA 1 2 5 6 9 10 13 14 A 17 18 19 20 21 22 23 24 25 26 27 28 1A 5A 1A 5A 1A 5A 1A 5A 15 16 11 12 1A 5A 3 4 7 8 B C V4 VX VL3 VC VL2 VB VL1 VA IL2 IB IL3 IC I4 IG I5 ISEF NOTES 1 CT circuits are shown connected to 1 A tap use alternative tap for 5 A rated CTs 2 CT and Earth connections are typical only 3 Voltage Config Vab Vbc 3V0 Figure 7 4 1 7SR22 Applied to Feeder ...

Page 509: ...26 27 28 1A 5A 1A 5A 1A 5A 1A 5A 15 16 11 12 1A 5A 3 4 7 8 B C V4 VX VL3 VC VL2 VB VL1 VA IL2 IB IL3 IC I4 IG I5 ISEF NOTES 1 CT circuits are shown connected to 1 A tap use alternative tap for 5 A rated CTs 2 CT and Earth connections are typical only 3 Vee Connected VT Phase Voltage Config Va Vb Vc 4 DEF elements must be NPS polarised Vo polarising not applicable Figure 7 5 1 7SR22 Applied to Feed...

Page 510: ...A 5A 1A 5A 1A 5A 15 16 11 12 1A 5A 3 4 7 8 B C V4 VX VL3 VC VL2 VB VL1 VA IL2 IB IL3 IC I4 IG I5 ISEF NOTES 1 CT circuits are shown connected to 1 A tap use alternative tap for 5 A rated CTs 2 CT and Earth connections are typical only 3 Vee Connected VT Phase Voltage Config Va Vb Vc 4 DEF elements must be NPS polarised Vo polarising not applicable 5 V4 used for NVD input Capacitor Cones Adaptor Un...

Page 511: ...Transformer Configurations for Check Synchronisation Relay Voltage Configuration Description Connection Vbn line Vbn bus 25 Check Sync A21 A22 A27 A28 A B C N n a b c A B C N n a b c V Line V Bus Vab line Vab bus 25 Check Sync A21 A22 A27 A28 A B C N n a b c A B C N n a b c V Line V Bus Figure 7 7 1 7SR22 Applied to Check Synchronisation ...

Page 512: ...y Voltage Configuration Setting Description Connection Van Vbn Vcn 67 67N 67G 47 27 59 81 Phase Neutral Phase Phase Calculated NPS ZPS Va Vb Vc 67 67N NPS polarising 47 27 59 81 Phase Phase Calculated NPS Vab Vbc 3V0 67 67N 67G 47 59N 27 59 81 Phase Neutral Calculated Phase Phase Phase Vca Calculated NPS ZPS Figure 7 8 1 7SR22 VT Connections ...

Page 513: ... of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of negligence or any other cause...

Page 514: ...05 2435H85008R7a 7a 7SR210 2435H85009R7a 7a 7SR220 First Release 2013 01 2435H85008R7c 7b 7SR210 2435H85009R7c 7b 7SR220 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line Check on non AR devices Added 74CCS Close Circuit Supervision 2014 06 2435H85008R7f 7d 7SR210 2435H85009R7f 7d 7SR220 Added Fault Locator feature and C...

Page 515: ...rent 67 50 67 51 17 2 2 1 Definite Time Overcurrent 50 18 2 2 2 Inverse Time Overcurrent 51 18 2 3 Voltage Controlled Overcurrent 51V 20 2 4 Cold Load 51c 22 2 4 1 Inverse Time Overcurrent 51C 23 2 1 Arc Flash Detection 50AFD 25 2 2 Directional Earth Fault Polarity Check 67N 26 2 3 Derived Earth Fault 67 50N 67 51N 27 2 3 1 Directional Polarity 28 2 3 2 Definite Time Overcurrent 50N 28 2 3 3 Inver...

Page 516: ...ower 32S 61 2 13Power Factor 55 63 Section 3 Supervision Functions 65 3 1 CB Fail 50BF 65 3 2 Voltage Transformer Supervision 60VTS 67 3 2 1 1 or 2 Phase VT fail 68 3 2 2 3 Phase VT fail 68 3 3 Current Transformer Supervision 60CTS 69 3 3 1 Element Blocking 70 3 4 Broken Conductor 46BC 71 3 4 1 Element Blocking 72 3 5 Load Blinder 21 73 3 5 1 Determining Load Blinder Regions 21LB 75 3 5 2 Determin...

Page 517: ...h Fault 39 Figure 2 10 1 Negative Phase Sequence Overcurrent 41 Figure 2 11 1 Undercurrent 44 Figure 2 12 1 Thermal Overload 46 Figure 2 13 1 Phase Under Over Voltage 48 Figure 2 13 2 Vx Under Over Voltage 51 Figure 2 13 3 NPS Overvoltage 53 Figure 2 13 4 Neutral Overvoltage 55 Figure 2 13 5 Under Over Frequency 57 Figure 2 11 1 Power 59 Figure 2 12 1 Sensitive Power 61 Figure 2 13 1 Power Factor ...

Page 518: ...rement of a current transformer C T secondary current is involved the failure or blowing of an instrument fuse or the operation of an instrument cut out could cause the secondary winding of the C T to become an open circuit Open circuit secondary windings on energised current transformers are a hazard that can produce high voltages dangerous to personnel and damaging to equipment test procedures m...

Page 519: ... from Reydisp as follows From the File menu select Save As change the file type to Export Default Actual Setting RTF and input a suitable filename When testing is completed the event and waveform records should be cleared and the settings file checked to ensure that the required in service settings are being applied 1 2 4 Precautions Before electrical testing commences the equipment should be isol...

Page 520: ...ay screen If the View Group is not shown at the top of the display this indicates that the setting is common to all groups CT VT ratio I O mapping and other settings which are directly related to hardware are common to all groups If the relay is allowed to trip during testing then the instruments display will be interrupted and replaced by the Trip Alert screen which displays fault data informatio...

Page 521: ...e to apply test connections between the current transformer and the power transformer windings Primary injection is needed however to verify the polarity of the CTs In these circumstances primary current must be injected through the associated power transformer winding It may be necessary to short circuit another winding in order to allow current to flow During these primary injection tests the in...

Page 522: ...nnection and measurement accuracy by single phase secondary injection at nominal levels Ensure that the correct instrument displays the applied signal within limits of the Performance Specification Applied Current Applied Voltage IA IB IC IG ISEF VA VAB VB VBC VC VCB VX Secondary Primary Apply 3P balanced Current and Voltage at nominal levels and ensure that the measured Zero Phase Sequence and Ne...

Page 523: ... of the scheme logic or individually To check a binary pick up time delay temporarily map the binary to an output relay that has a normally open contact This can be achieved in the Output Matrix sub menu by utilising the BI n Operated settings Use an external timer to measure the interval between binary energisation and closure of the output contacts Similarly to measure the drop off delay map to ...

Page 524: ...et trip relays Close each output relay in turn from the Reydisp Evolution PC programme Relay Control Close output relay This function will energise the output for its minimum operate time This time is specified in the Output Config Binary Output Config menu for each output relay and may be too short to measure with a continuity tester An alternative method of energising an output permanently so th...

Page 525: ...ay Case Shorting Contacts CT inputs and terminals B25 B26 Relay Withdrawn Alarm are fitted with case mounted shorting contacts which provide a closed contact when the relay is withdrawn from the case The operation of these contacts should be checked CT Shorting contacts checked Relay Withdrawn Alarm Checked ...

Page 526: ...indicates functions where function conflicts may occur during testing consideration should be given to disabling functions to avoid interference Any LED can be assigned to be a General Pickup LED in the Output Matrix menu and can be used to assess operation of functions during testing if other functions are disabled or if the setting allocating General Pickup is temporarily modified Voltage inputs...

Page 527: ... equivalent Measured and Calculated Earth Fault direction meters can be used as an aid to commissioning testing 1 Check the direction of each pole in turn by connecting to the appropriate terminals The table below shows the polarising quantity for each pole Connections for Directional Polarity Overcurrent pole Polarising voltage Phase A VBC Phase B VCA Phase C VAB 2 Inject single phase rated curre...

Page 528: ...gure 2 1 1 Directional Phase Fault Boundary System Angles 4 With the instrument reading Fwd or Rev reduce the voltage until the element resets Record the minimum phase phase operate voltage Minimum Voltage Setting Measured 2 1 1 2 out of 3 logic Ensure that at least 1 Phase Overcurrent element is set to Directional Apply balanced nominal voltage Apply current at a level above on phase A only at th...

Page 529: ...1 Phase Overcurrent Voltage Inputs VL1 VA VL2 VB VL3 VC for directional elements Current Inputs IL1 IA IL2 IB IL3 IC Disable 51V 51c 46 49 50BF 79 Map Pickup LED 51 n 50 n Self Reset Other protection functions may overlap with these functions during testing it may be useful to disable some functions to avoid ambiguity It should be particularly noted that if the function is enabled the 51C Cold Loa...

Page 530: ...ut in the Pickup Config sub menu in the Output Config menu as this will allow the Pick up led to operate for the function Gradually increase current until Pickup LED operates Apply 2x setting current and record operating time Apply 5x setting current and record operating time Compare to calculated values for operating times Gradually reduce current until the element drops off and record the level ...

Page 531: ...rom operated condition to fully reset are as follows for zero applied current and Time multiplier TM 1 0 The reset curve characteristic type and TM is defined by the operating characteristic Curve Fully operated to reset with Zero current applied TM 1 secs ANSI MI 4 85 ANSI VI 21 6 ANSI EI 29 1 Apply current in the following sequence a 2x setting for a time to ensure element operation b Zero curre...

Page 532: ...set Shaped Phase Overcurrent elements 51 n should be tested for pick up and timing before this function is tested The General Pickup LED can be used to assess operation of this function if other functions are disabled or if the setting allocating General Pickup is temporarily modified Apply nominal 3 phase balanced voltage Apply 3 phase balanced current at a level below the normal 51 n setting but...

Page 533: ... case the phase angle of the current must be set with respect to the voltage to produce operation of the elements Voltage Setting V p p Measured V p p I Setting Multiplier Calculated PU Measured Tolerance 51 1 Pickup 51 2 Pickup 51 3 Pickup 51 4 Pickup 1 1 1 1 Element Blocking The Voltage Controlled Overcurrent function can be set to Inhibit for VT Supervision operation This functionality should b...

Page 534: ... 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 2 4 1 Cold Load Voltage Inputs VL1 VA VL2 VB VL3 VC for directional elements Current Inputs IL1 IA IL2 IB IL3 IC Disable 51V 46 49 50BF 79 Map Pickup LED 51 n Self Reset The CB must be open for more than the Cold Load Pick up Time to allow testing of this function It may be convenient to reduce this setting to suit the test procedure If the CB i...

Page 535: ...e Cold Load Active is raised Apply current above the Reduced Current Level if this functionality is Enabled before applying CB Closed Measure the time for Cold Load Active to reset 2 4 1 Inverse Time Overcurrent 51C It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the Pickup Config sub menu in the Output Config menu as this will allow the ...

Page 536: ...SI reset times from operated condition to fully reset are as follows for zero applied current and TM 1 0 The reset curve characteristic type and TM is defined by the operating characteristic Curve Fully operated to reset with Zero current applied TM 1 secs ANSI MI 4 85 ANSI VI 21 6 ANSI EI 29 1 Apply current in the following sequence a 2x setting for a time to ensure element operation b Zero curre...

Page 537: ...t The overcurrent level can be tested without an arc flash by separately energising or inverting the arc detector binary input continuously for the duration of the test for the zone being tested If the current setting is low gradually increase current until element operates If the current level required is greater than the thermal limit of the relay apply 0 9x setting check for no operation apply ...

Page 538: ... and simulate the fault The fault current on the faulted phase only should be set at the MTA with respect to the phase neutral voltage on the faulted phase e g for a relay setting of 15º set the phase current to lag the ph n voltage by 15º Alternatively a single phase voltage source can be used in the above test The polarity of this voltage applied to the faulted phase neutral alone must be revers...

Page 539: ...50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 2 3 1 Derived Earth Fault Voltage Inputs VL1 VA VL2 VB VL3 VC Current Inputs IL1 IA IL2 IB IL3 IC Disable 37 46 49 60CTS 50BF 60CTS 46BC 79 Map Pickup LED 51N n 50N n Self Reset Other protection functions may overlap with these functions during testing it may be useful to disable some functions to avoid ambiguity Derived EF Measured EF Sens...

Page 540: ...Operate Time 2 x Is NOTES E If VTS action is set to BLOCK this option should be tested Apply balanced voltage and current Reduce a phase voltage to cause a VTS condition Increase 3P current and check that the element does not operate If VTS action is set to Non Directional this option should be tested Apply balanced voltage and current Reduce a phase voltage to cause a VTS condition Increase a pha...

Page 541: ...67 3 33 IEC LTI 120 00 30 00 ANSI MI 3 80 1 69 ANSI VI 7 03 1 31 ANSI EI 9 52 1 30 Note that the operate time may be subject to the Minimum op time setting for the element and or may have a Follower DTL applied 1 1 1 1 Element Blocking The Derived Earth Fault elements can be blocked by Binary Input Inhibit VT Supervision and Inrush Detector operation The Characteristic can be made non directional ...

Page 542: ...secs ANSI MI 4 85 ANSI VI 21 6 ANSI EI 29 1 Apply current in the following sequence a 2x setting for a time to ensure element operation b Zero current for the reset time above xTM c 2x setting for a time to ensure element operation Check that the second operation c is similar to the first a and in line with the expected operate time for the element at this current level Repeat the test with the re...

Page 543: ...60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 2 4 1 Measured Earth Fault Voltage Inputs VL1 VA VL2 VB VL3 VC for directional elements Current Inputs I4 IG Disable 50BF 79 Map Pickup LED 51G n 50G n Self Reset Other protection functions may overlap with these functions during testing it may be useful to disable some functions to avoid ambiguity Derived EF Measured E...

Page 544: ...can be set to directional If VTS action is set to BLOCK this option should be tested Apply balanced voltage and current Reduce a phase voltage to cause a VTS condition Increase a phase current and check that the element does not operate If VTS action is set to Non Directional this option should be tested Apply balanced voltage and current Reduce a phase voltage to cause a VTS condition Increase a ...

Page 545: ...sted Apply balanced voltage and current Reduce a phase voltage to cause a VTS condition Increase a phase current and check that the element does not operate If VTS action is set to Non Directional this option should be tested Apply balanced voltage and current Reduce a phase voltage to cause a VTS condition Increase a phase current and check that the element operates at its normal setting Reverse ...

Page 546: ...secs ANSI MI 4 85 ANSI VI 21 6 ANSI EI 29 1 Apply current in the following sequence a 2x setting for a time to ensure element operation b Zero current for the reset time above xTM c 2x setting for a time to ensure element operation Check that the second operation c is similar to the first a and in line with the expected operate time for the element at this current level Repeat the test with the re...

Page 547: ...S I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 2 5 1 Sensitive Earth Fault Voltage Inputs VL1 VA VL2 VB VL3 VC for directional elements Current Inputs I5 ISEF Disable 64H 50BF 79 Map Pickup LED 51SEF n 50SEF n Self Reset Other protection functions may overlap with these functions during testing it may be useful to disable some functions to avoid ambiguity Derived EF Meas...

Page 548: ...on is set to BLOCK this option should be tested Apply balanced voltage and current Reduce a phase voltage to cause a VTS condition Increase a phase current and check that the element does not operate If VTS action is set to Non Directional this option should be tested Apply balanced voltage and current Reduce a phase voltage to cause a VTS condition Increase a phase current and check that the elem...

Page 549: ...oltage to cause a VTS condition Increase a phase current and check that the element does not operate If VTS action is set to Non Directional this option should be tested Apply balanced voltage and current Reduce a phase voltage to cause a VTS condition Increase a phase current and check that the element operates at its normal setting Reverse the voltage phase direction whilst checking that the ele...

Page 550: ...ecs ANSI MI 4 85 ANSI VI 21 6 ANSI EI 29 1 Apply current in the following sequence a 2x setting for a time to ensure element operation b Zero current for the reset time above xTM c 2x setting for a time to ensure element operation Check that the second operation c is similar to the first a and in line with the expected operate time for the element at this current level Repeat the test with the res...

Page 551: ... 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 2 6 1 Restricted Earth Fault Voltage Inputs n a Current Inputs I5 IREF Disable 51SEF 50SEF 79 Map Pickup LED 64H Self Reset The setting resistance should be measured and the value compared to that specified in the settings data Both values should be recorded Settings Data Resistor Value Measured The high value of setting resistance R will ...

Page 552: ... Precautions should be taken to ensure that no personnel are at risk of contact with any of the energised secondary wiring during the test Settings Data Voltage Setting Measured To complete testing of the REF requires primary injection through the phase and residual REF CT in series to simulate an out of zone fault and ensure stability of the relay The test can then be repeated with the REF CT sec...

Page 553: ...60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 2 7 1Negative Phase Sequence Overcurrent Voltage Inputs n a Current Inputs IL1 IA IL2 IB IL3 IC Disable 51 51V 51c 37 49 50BF 60CTS 46BC Map Pickup LED 46IT 46DT Self Reset Where two NPS elements are being used with different settings it is convenient to test the elements with the highest settings first The ele...

Page 554: ...temporarily drive the relevant Pickup output in the Pickup Config sub menu in the Output Config menu as this will allow the Pick up led to operate for the function Gradually increase current until Pickup LED operates Apply 2x setting current and record operating time Apply 5x setting current and record operating time Compare to calculated values for operating times P U D O TIMING TESTS Ph Dir Char...

Page 555: ...sure element operation b Zero current for the reset time above xTM c 2x setting for a time to ensure element operation Check that the second operation c is similar to the first a and in line with the expected operate time for the element at this current level Repeat the test with the reset time b reduced to 50 of the previous value Ensure that the second operate time c is 50 of the first a operate...

Page 556: ...AFD 50 AFD 51c 51c 51c Figure 2 8 1Undercurrent Voltage Inputs n a Current Inputs IL1 IA IL2 IB IL3 IC Disable 51N 51G 46 60CTS 46BC Map Pickup LED 37 n Self Reset If two Undercurrent 37 elements are used with different settings it is convenient to test the element with the lowest setting first The higher setting element can then be tested without interference from the other element Apply 3P balan...

Page 557: ...s DTL sec P U Current Amps Tolerance Operate Time 0 5 x Is Tolerance IL1 IA IL2 IB IL3 IC 1 1 1 1 Element Blocking The Undercurrent elements can be blocked by Binary Input Inhibit This functionality should be checked Element BI Inhibits 37 1 37 2 Check correct indication trip output alarm contacts waveform record ...

Page 558: ... 60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 2 9 1Thermal Overload Voltage Inputs n a Current Inputs IL1 IA IL2 IB IL3 IC Disable 51 50 37 50BF Map Pickup LED 49Alarm The current can be applied from a 3P balanced supply or phase by phase from a 1P supply Alternatively the 3 phase current inputs can be connected in series and injected simultaneously from ...

Page 559: ...ermal State then apply 2x the Overload Setting current Calculated Operate Time s Measured Operate Time s If the Thermal Overload Capacity Alarm is used this can be tested by monitoring the Thermal Capacity in the instruments menu If the Thermal time constant is longer than a few minutes this can be assessed during the timing test above If the Time Constant is less than a few minutes a lower multip...

Page 560: ...F 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 2 10 1 Phase Under Over Voltage Voltage Inputs VL1 VA VL2 VB VL3 VC Current Inputs n a apply zero current to stabilize other functions Disable 47 59N 60VTS Map Pickup LED 27 59 n Self Reset Where more than one Undervoltage 27 elements are being used with different settings it is convenient to test the elements with the lowest settings first The elements...

Page 561: ...tested without disabling the higher settings If the O P Phases is set to All the voltage on all phases must be increased simultaneously Otherwise the 3 phases should be tested individually If the DTL setting is short starting from nominal voltage slowly increase the applied 3P or VL1 test voltage until the Pickup LED temporarily mapped is lit The LED should light at setting Volts 5 Decrease the in...

Page 562: ...st during testing 27UVG operation will reset the General Pickup if no other element is operated This LED should not be set as Hand Reset in the Output matrix Starting from nominal voltage apply a step decrease to the applied voltage to a level below the 27 Undervoltage setting but above the 27UVG setting such that an Undervoltage element operation occurs Slowly reduce the applied voltage until the...

Page 563: ...Vx Under Over Voltage Voltage Inputs V4 VX Current Inputs n a apply zero current to stabilize other functions Disable Map Pickup LED Vx 27 59 Self Reset If DTL setting is small gradually increase single phase voltage applied to Vx input until element operates if the element is Overvoltage Alternatively if the element is Undervoltage increase single phase voltage applied to Vx input until element o...

Page 564: ... D O calculated P U Volts D O Volts Op Time 2x Vs OV 0 5x Vs UV Tolerence V4 Vx 1 1 1 1 Element Blocking The Vx Under Over Voltage elements can be blocked by Binary Input Inhibit and VT Supervision This functionality should be checked Element BI Inhibits VT Supervision 27 59x Check correct indication trip output alarm contacts waveform record ...

Page 565: ...c 51c Figure 2 10 3 NPS Overvoltage Voltage Inputs VL1 VA VL2 VB VL3 VC Current Inputs n a apply zero current to stabilize other functions Disable 27 59 59N 60VTS Map Pickup LED 47 n Self Reset Where two NPS elements are being used with different settings it is convenient to test the elements with the highest settings first The elements with lower settings can then be tested without disabling the ...

Page 566: ...ting Volts U O DTL sec Hyst D O calculated P U Volts D O Volts Op Time 2x Vs Tolerence NPS 1 1 1 1 Element Blocking The NPS Overvoltage element can be blocked by Binary Input Inhibit This functionality should be checked Element BI Inhibits 47 1 47 2 Check correct indication trip output alarm contacts waveform record ...

Page 567: ... x2 37S x2 51c 60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 2 10 4 Neutral Overvoltage Voltage Inputs VL1 VA VL2 VB VL3 VC Current Inputs n a apply zero current to stabilize other functions Disable 27 59 47 60VTS Map Pickup LED 59N n Self Reset The voltage source for the Neutral Overvoltage 59N function can be set as either Vn calculated from the applied ...

Page 568: ...e voltage until Pickup LED operates Apply 2x setting voltage and record operating time Apply a higher multiple of setting voltage and record operating time Compare to calculated values for operating times from ú û ù ê ë é 1 1 sec Vs Vn op M onds t Where M Time multiplier and Vn Vs multiple of setting P U D O TIMING TESTS Ph Vs V TM Operate Voltage Operate Time P U Volts D O Volts Tol 2 x Vs sec x ...

Page 569: ...r functions Disable Map Pickup LED 81 n Self Reset This function can be tested by application of 1P or 3P voltage For Over frequency the elements with the highest setting should be tested first and for Under frequency the elements with the lowest settings should be tested first The elements with other settings can then be tested without need to disable the elements already tested Note that the rel...

Page 570: ...or Under frequency and record operating time Starting with the element in the operated condition gradually increase or decrease the applied voltage until the element resets Measure the reset voltage level to check the 81 Hysteresis setting F Hertz U O DTL sec Hyst D O calc P U Freq Hertz D O Freq Hertz Operate Time 0 5Hz UV Guard NOTES If the element is set as 81 nU V Guarded this setting can be t...

Page 571: ...by application 3P current and voltage For Over power the elements with the highest setting should be tested first and for Under power the elements with the lowest settings should be tested first The elements with other settings can then be tested without need to disable the elements already tested From the nominal power setting Sn gradually increase decrease applied voltage or current until 32 n o...

Page 572: ...below the 32 n U C Guard Setting at a power in the operate range Increase the current until the relay operates UCG UCG Setting xIn Power element Used for test Blocked Current D O Unblocked Current P U NOTES U O Power 1 1 1 1 Element Blocking The U O Power elements can be blocked by Binary Input Inhibit This functionality should be checked Element BI Inhibits 32 1 32 2 Check correct indication trip...

Page 573: ... tested by application 1P current and 3P voltage For Over power the elements with the highest setting should be tested first and for Under power the elements with the lowest settings should be tested first The elements with other settings can then be tested without need to disable the elements already tested From the nominal power setting Sn gradually increase decrease applied voltage or current u...

Page 574: ...vel below the 32S n U C Guard Setting at a power in the operate range Increase the current until the relay operates UCG UCG Setting xIn Power element Used for test Blocked Current D O Unblocked Current P U NOTES U O Power 1 1 1 1 Element Blocking The U O Power elements can be blocked by Binary Input Inhibit This functionality should be checked Element BI Inhibits 32S 1 32S 2 Check correct indicati...

Page 575: ...27 59 27 59 x4 27 59 x4 27 59 x4 47 x2 81 x6 79 Optional 59N x2 81 HBL 2 5N 37G x2 37S x2 51c 60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c 32S x2 32 x2 55 21 LB 21 LB 21 LB 51V 21FL 60 VTS 51V 51V Figure 2 13 1 Power Factor Voltage Inputs VL1 VA VL2 VB VL3 VC Current Inputs IL1 IA IL2 IB IL3 IC Disable 49 Map Pickup LED 55 n Self Reset Apply balanced 3 phase rat...

Page 576: ... operate range Increase the current until the relay operates UCG UCG Setting xIn Power element Used for test Blocked Current D O Unblocked Current P U NOTES Power Factor 1 1 1 1 Element Blocking The Power Factor elements can be blocked by Binary Input Inhibit This functionality should be checked Element BI Inhibits 55 1 55 2 Check correct indication trip output alarm contacts waveform record When ...

Page 577: ...67 51 x4 67 51 x4 67 51N x4 67 50G x4 67 51G x4 67 50S x4 67 51S x4 64 H 27 59 27 59 x4 27 59 x4 27 59 x4 47 x2 81 x6 79 Optional 59N x2 81 HBL 2N 60 VTS 51V 51V 51V 37G x2 37S x2 51c 60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 3 1 1 CB Fail Voltage Inputs n a Current Inputs IL1 IA IL2 IB IL3 IC Disable Map Pickup LED 50BF n Self Reset The circuit breake...

Page 578: ...F 2 Delay Repeat the sequence with current at 90 of the 50BF Setting current level after the element trip and check for no CB Fail operation 50BF Setting xIn Test Current 50BF 1 Delay 50BF 2 Delay 110 90 No Operation No Operation 50BF CB Faulty Operation No Delay Operation No Delay 50BF I4 Setting xIn Test Current 50BF 1 Delay 50BF 2 Delay 110 90 No Operation No Operation 50BF CB Faulty Operation ...

Page 579: ...use of some functions are mutually exclusive 67 50 x4 67 51 x4 67 50N x4 67 50 x4 67 50 x4 67 51 x4 67 51 x4 67 51N x4 67 50G x4 67 51G x4 67 50S x4 67 51S x4 64 H 27 59 27 59 x4 27 59 x4 27 59 x4 47 x2 81 x6 79 Optional 59N x2 81 HBL 2N 60 VTS 51V 51V 51V 37G x2 37S x2 51c 60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 3 2 1 Voltage Transformer Supervision...

Page 580: ...setting Return the voltage to nominal and ensure that VTS resets Reduce the 3P balanced current to a level below the 60VTS Ipps Load setting Reduce the 3P balanced voltage to a level below the operate level above Gradually increase the 3P balanced current until the VTS operates Check that the thermal rating of the relay current inputs is not exceeded during the following test Increase the 3P balan...

Page 581: ... 51V 37G x2 37S x2 51c 60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 21 FL 21 FL 21 FL 51c 51c 51c Figure 3 3 1 Current Transformer Supervision Voltage Inputs VL1 VA VL2 VB VL3 VC for directional elements Current Inputs IL1 IA IL2 IB IL3 IC Disable 51N 46IT 46DT 46BC Map Pickup LED 60CTS Self Reset The presence of NPS current without NPS voltage is used to indicate a current transformer failure ...

Page 582: ...70 of 82 2013 Siemens Protection Devices Limited Setting Measured 60CTS Delay 60CTS Inps 60CTS Vnps 3 3 1 ELEMENT BLOCKING The CT Supervision function can be blocked by Binary Input Inhibit This functionality should be checked Element BI Inhibits 60CTS ...

Page 583: ...IB IL3 IC Disable 51N 46IT 46DT Map Pickup LED 46BC Self Reset Broken Conductor uses the ratio of NPS current to PPS current to detect an open circuit conductor These quantities can be produced directly from many advanced test sets but with limited equipment the following approach can be applied Apply 3P balanced current with normal phase rotation direction This current will consist of PPS alone n...

Page 584: ...P unbalance current of 3P current 20 75 25 100 30 129 35 161 40 200 46BC Setting 3P balanced current A 1P unbalance current A Measured Unbalance current Apply 1 A 1P unbalance current without 3P balanced current Measure 46BC operating time 46BC Delay setting Measured 3 4 1 ELEMENT BLOCKING The Broken Conductor element can be blocked by Binary Input Inhibit This functionality should be checked Elem...

Page 585: ... 5 1 Load Blinder 21 Voltage Inputs VL1 VA VL2 VB VL3 VC Current Inputs IL1 IA IL2 IB IL3 IC Disable 51 n 51V 51c 46 49 50BF 79 Map Pickup LED 21LB 3P 21LB 1P Self Reset Load Blinders are designed to block Overcurrent elements from tripping in heavy load conditions User settings 21LB 3P Angle and 21LB 3P Impedance allow user to define the Blinder region depending on the networks or specifically a ...

Page 586: ...generators feed in PPS current into the system In case of high load in system due to distributed generation hence resulting in change of Zpps Zpps is calculated from Vpps and Ipps The magnitude and angle of Zpps is compared with 21LB 3P Impedance and 21LB 3P Angle to determine if the impedance is in operate or block and or FWD or REV zone R X Phase Fault Block Zone Load Impedance b a Nominal Imped...

Page 587: ...nto the Load Blinder region 7 Rotating the angle in an anti clockwise direction will see the LEDs extinguish this indicates the drop off point of the Load Blinder region Record the angle as Point1 in the table of values 8 Rotating the angle from this point in a clockwise direction will see the LEDs illuminate which indicates the pick up point of the Load Blinder region Record the angle as Point 2 ...

Page 588: ...se on the Omicron 4 Apply Omicron current and voltage to the relay 5 Using the PC mouse click the appropriate arrow to adjust current level 6 View the LEDs for indication of Load Blinder operation as the current increases out of the Load Blinder region This is the DO point 5 7 View the LEDs for indication of Load Blinder operation as the current decreases into the Load Blinder region This is the P...

Page 589: ...x4 67 50N x4 67 50 x4 67 50 x4 67 51 x4 67 51 x4 67 51N x4 67 50G x4 67 51G x4 67 50S x4 67 51S x4 64 H 27 59 27 59 x4 27 59 x4 27 59 x4 47 x2 81 x6 79 Optional 59N x2 81 HBL 2N 60 VTS 51V 51V 51V 37G x2 37S x2 51c 60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 3 6 1 Trip Circuit Supervision Voltage Inputs n a Current Inputs n a Disable Map Pickup LED 74TCS...

Page 590: ...e 67 50 x4 67 51 x4 67 50N x4 67 50 x4 67 50 x4 67 51 x4 67 51 x4 67 51N x4 67 50G x4 67 51G x4 67 50S x4 67 51S x4 64 H 27 59 27 59 x4 27 59 x4 27 59 x4 47 x2 81 x6 79 Optional 59N x2 81 HBL 2N 60 VTS 51V 51V 51V 37G x2 37S x2 51c 60 CTS I 60 CTS I 60 CTS I 37 50 BF 37 50 BF 25 50 AFD 50 AFD 50 AFD 51c 51c 51c Figure 3 7 1 Magnetising Inrush Detector Voltage Inputs n a Current Inputs IL1 IA IL2 I...

Page 591: ...able Map Pickup LED Logical operation of the harmonic blocking can be tested by injection of 5 th harmonic current at 250Hz for 50Hz relay to cause operation of the blocking signals Note that injection of any level of 5th harmonic alone on a current input will cause the block to be raised since the harmonic content on this input is 100 i e greater than setting Fundamental frequency current can be ...

Page 592: ...vide a realistic simulation of the actual system conditions The Instruments Menu contains Autoreclose Meters for the Autoreclose State and the Shot No which are useful during sequence testing The time stamped Events listing can be downloaded from the relay to a pc to allow diagnosis of the sequence including measurements of sequence Dead Times and other timing without the use of external measuring...

Page 593: ...of each element 5 2 Maintenance Relay failure will be indicated by the Protection Healthy LED being off or flashing A message may also be displayed on the LCD In the event of failure Siemens Protection Devices Ltd or one of its agents should be contacted see defect report sheet in section 5 3 The relay should be returned as a complete unit No attempt should be made to disassemble the unit to isola...

Page 594: ...eration default instruments are enabled Remove all instruments from the default list and only add those that are required Cannot communicate with the relay Check that all of the communications settings match those used by Reydisp Evolution Check that the Tx and Rx fibre optic cables are connected correctly Tx Rx and Rx Tx Check that all cables modems and fibre optic cables work correctly Ensure th...

Page 595: ...ssion of Siemens Protection Devices Limited nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of negligence or any other ...

Page 596: ...Software Revision History 2011 05 2435H85008R7a 7a 7SR210 2435H85009R7a 7a 7SR220 First Release 2013 01 2435H85008R7c 7b 7SR210 2435H85009R7c 7b 7SR220 Introduced journaling file system Added 61850 logical nodes for CB Counters metering 50BF 46BC 81HBL2 and line check Added Line Check on non AR devices Added 74CCS Close Circuit Supervision 2014 06 2435H85008R7f 7d 7SR210 2435H85009R7f 7d 7SR220 Ad...

Page 597: ...dercurrent 37 25 2 12Thermal Overload 49 25 2 13Under Over Voltage Protection 27 59 26 2 14Neutral Overvoltage 59N 27 2 14 1 Application with Capacitor Cone Units 28 2 14 2 Derived NVD Voltage 28 2 15Negative Phase Sequence Overvoltage 47 28 2 16Under Over Frequency 81 29 2 17Power Protection 30 2 17 1 Power 32 30 Section 3 CT Requirements 31 3 1 CT Requirements for Overcurrent and Earth Fault Pro...

Page 598: ...9 Figure 2 7 3 Application of Directional Overcurrent Protection 20 Figure 2 7 4 Feeder Fault on Interconnected Network 21 Figure 2 8 1 Earth Fault Angles 22 Figure 2 9 1 Balanced and Restricted Earth fault protection of Transformers 23 Figure 2 9 2 Composite Overcurrent and Restricted Earth fault Protection 24 Figure 2 12 1 Thermal Overload Heating and Cooling Characteristic 25 Figure 2 14 1 NVD ...

Page 599: ...itchable earthing connections Loss of Grid connection see below Figure 1 1 1 Example Use of Alternative Settings Groups RADIAL SUBSTATION Start generators Select alternate settings group Local Generation Industrial system draws power from grid system during normal operation Relays normally use settings group 1 On loss of mains Local generation switched in Non essential loads tripped Relays on esse...

Page 600: ...the Relay Alarm and Tripping Inputs A common use of binary inputs is to provide indication of alarm or fault conditions e g transformer Buchholz Gas or Buchholz Surge conditions The Binary Inputs are mapped to LED s waveform storage trigger and binary outputs Note that transformer outputs which require high speed tripping such as a Buchholz Surge should be wired to a binary input to provide LED in...

Page 601: ... with the relay The binary inputs will be less likely to mal operate if they 1 Have both the positive and negative switched double pole switched 2 Do not have extensive external wiring associated with them e g if the wiring is confined to the relay room Where a binary input is both used to influence a control function e g provide a tripping function and it is considered to be susceptible to mal op...

Page 602: ...7 5 V Operative IOP 50 mA 1K2 330 BI DTL 10 ms 10 µF 60 V Capacitance discharge BI DTL 10 ms 10 µF 150 V Capacitance discharge BI 19 V BI 19 V BI 19 V BI 19 V BI 19 V Resistor power ratings 30 V DC Nominal 3 W 48 V DC Nominal 3 W 110 V DC Nominal 10 W ESI 1 110 V DC Nominal 20 W ESI 2 Resistors must be wired with crimped connections as they may run hot 110 V DC Nominal 87 5 V to 137 5 V Operative ...

Page 603: ...should be utilised 1 4 LEDs Output function LEDs are mapped to output functions by means of settings These could be used to display such digital signals as trips a general pick up plant control signals etc User Defined Function Key LEDs are used to indicate the status of Function Key operation These do not relate directly to the operation of the Function Key but rather to its consequences If a Fun...

Page 604: ...ign the required LED as a particular colour either red or green type the LED number in the appropriate row To assign the required LED as a yellow colour type the LED number in both red and green rows NB If a LED number is not assigned that particular LED will not illuminate Figure 1 4 2 LED configuration via the Settings OUTPUT CONFIG LED CONFIG menu ...

Page 605: ... are defined as Inverse because their tripping times are inversely proportional to the Fault Current being measured This makes them particularly suitable to grading studies where it is important that only the Relay s closest to the fault operate Discrimination can be achieved with minimised operating times To optimise the grading capability of the relay additional time multiplier Follower DTL Fig ...

Page 606: ...are important where the fault path to earth is a high resistance one such as in highly arid areas or where the system uses high values of earthing resistor reactance and the fault current detected in the phase conductors will be limited 2 1 1 Selection of Overcurrent Characteristics Each pole has two independent over current characteristics Where required the two curves can be used To produce a co...

Page 607: ... time after which the insulation fails again The same phenomenon has occurred in compound filled joint boxes or on clashing overhead line conductors The repeating process of the fault can cause electromechanical disc relays to ratchet up and eventually trip the faulty circuit if the reset time of the relay is longer than the time between successive faults To mimic an electromechanical relay the re...

Page 608: ...R will have a declared minimum sustained fault current and this must be above the protection over current settings Close in short circuit faults may also cause the AVR to reach its safety limits for supplying maximum excitation boost in the order of several seconds and this will result in AVR internal protection devices such as diode fuses to start operating The generator excitation will then coll...

Page 609: ...ne circuit breaker alone should be tripped for arc faults in the cable termination and CT compartment The whole busbar must be cleared for arc faults which cannot be identified as being on the line side of the circuit breaker Overcurrent supervision can only be applied if the arrangement ensures that current will be measured for all arc faults In Figure Zone 2 can only be supervised by current if ...

Page 610: ...es A combination of instantaneous and DTL elements can be used in blocked overcurrent protection schemes These protection schemes are applied to protect substation busbars or interconnectors etc Blocked overcurrent protection provides improved fault clearance times when compared against normally graded overcurrent relays The blocked overcurrent scheme of busbar protection shown in Figure 2 4 2 ill...

Page 611: ...circuit faults However to include for both equipment tolerances and a safety margin a minimum time delay of 100 ms is recommended This type of scheme is very cost effective and provides a compromise between back up overcurrent busbar protection and dedicated schemes of busbar protection Instantaneous elements are also commonly applied to autoreclose schemes to grade with downstream circuit reclose...

Page 612: ...EF relays may be graded with each other Where very sensitive current settings are required then it is preferable to use a core balance CT rather than wire into the residual connection of the line CTs The turns ratio of a core balance CT can be much smaller than that of phase conductors as they are not related to the rated current of the protected circuit Since only one core is used the CT magnetis...

Page 613: ...Shift Current leading Voltage between reference and operate quantities which must be allowed for in the Characteristic Angle setting This is the expected fault angle sometimes termed the Maximum Torque Angle MTA as an analogy to older Electro mechanical type relays Example Expected fault angle is 30º Current lagging Voltage so set Directional Angle to 90 30 60 A fault is determined to be in the se...

Page 614: ...and G have directional overcurrent relays fitted since fault current can flow in both directions at these points The forward direction is defined as being away from the busbar and against the direction of normal load current flow These forward looking IDMTL elements can have sensitive settings applied i e low current and time multiplier settings Note that 7SR22 relays may be programmed with forwar...

Page 615: ...D By using different settings for forward and reverse directions closed ring circuits can be set to grade correctly whether fault current flows in a clockwise or counter clockwise direction i e it may be practical to use only one relay to provide dual directional protection 2 Out of 3 Logic Sensitive settings can be used with directional overcurrent relays since they are directionalised in a way w...

Page 616: ...t The required setting is entered directly as dictated by the system impedances Example Expected fault angle is 45 i e residual current lagging residual voltage therefore 67G Char Angle 45 However directional earth elements can be selectable to use either ZPS or NPS Polarising This is to allow for the situation where ZPS voltage is not available perhaps because a 3 limb VT is being used Care must ...

Page 617: ...f the presence of the transformer Figure 2 9 1 Balanced and Restricted Earth fault protection of Transformers The calculation of the value of the Stability Resistor is based on the worst case where one CT fully saturates and the other balancing CT does not saturate at all A separate Siemens Protection Devices Limited Publication is available covering the calculation procedure for REF protection To...

Page 618: ...ctively earthed system can result in a zero sequence current of up 3 times phase charging current flowing through the relay location The step change from balanced 3 phase charging currents to this level of zero sequence current includes transients It is recommended to allow for a transient factor of 2 to 3 when determining the limit of charging current Based on the above considerations the minimum...

Page 619: ... are used to indicate that current has ceased to flow or that a low load situation exists For this reason simple Definite Time Lag DTL elements may be used For example once it has been determined that fault current has been broken the CB is open and no current flows an auto isolation sequence may safely be initiated 2 12 Thermal Overload 49 The element uses measured 3 phase current to estimate the...

Page 620: ...connection of motors To confirm presence loss of supply the voltage elements should be set to values safely above below that where a normal system voltage excursion can be expected The switchgear plant design should be considered The Dead level may be very near to the live level or may be significantly below it The variable hysteresis setting allows the relay to be used with all types of switchgea...

Page 621: ...ide via an unearthed transformer winding Insufficient earth current would be present to cause a trip but residual voltage would increase significantly reaching up to 3 times the normal phase earth voltage level If Neutral Overvoltage protection is used it must be suitably time graded with other protections in order to prevent unwanted tripping for external system earth faults Figure 2 14 1 NVD App...

Page 622: ...tection detects phase unbalances and is widely used in protecting rotating plant such as motors and generators However such protection is almost universally based on detecting NPS Current rather than Voltage This is because the NPS impedance of motors etc is much less than the Positive Phase Sequence PPS impedance and therefore the ratio of NPS to PPS Current is much higher than the equivalent rat...

Page 623: ...in stages until the frequency stabilises and returns to an acceptable level The relay has six under over frequency elements An example scheme may have the first load shedding stage set just below the nominal frequency e g between 49 0 Hz and 49 5 Hz A time delay element would be associated with this to allow for transient dips in frequency and to provide a time for the system regulating equipment ...

Page 624: ...ted power cannot be reached during starting for example where the motor is started with no connected load it may be necessary to inhibit this function for a set time This feature requires a 52a circuit breaker auxiliary contact mapped to an opto input to get the information CB Closed CB Open Directional power measurement may operate on occurrence of a system power supply fail or system fault Power...

Page 625: ...eeded magnitude accuracy is not important Often however there is also the need to consider instantaneous HighSet overcurrent protection as part of the same protection system and the settings would normally be of the order of 10x the CT rating or higher Where higher settings are to be used then the overcurrent factor must be raised accordingly e g to P20 3 1 2 Earth Fault Protection CTs Considerati...

Page 626: ...nough to allow for protection operation for the same fault but not so long that two separate faults could occur in the same Autoreclose ARC sequence and cause unnecessary lockouts Since large fault currents could potentially damage the system during a prolonged ARC sequence there are also settings to identify which protection elements are High sets and these can cause an early termination of the s...

Page 627: ...lt is cleared by the correct CB 4 1 1 Auto Reclose Example 1 Requirement Settings shall provide four phase fault recloses two instantaneous and two delayed and only two recloses for faults detected by the SEF protection Proposed settings include CONTROL LOGIC AUTORECLOSE PROT N 79 P F Inst Trips 50 1 79 P F Delayed Trips 51 1 79 SEF Delayed Trips 51SEF 1 CONTROL LOGIC AUTORECLOSE CONFIG 79 Num Sho...

Page 628: ...TROL LOGIC AUTORECLOSE CONFIG P F SHOTS 79 P F Prot n Trip 1 Inst 79 P F Prot n Trip 2 Inst 79 P F Prot n Trip 3 Delayed 79 P F Prot n Trip 4 Delayed The above settings are suitable at values of fault current above I2 however were a fault to occur with a current value between I1 and I2 this would be detected by the 51 1 element only As Prot n Trip 1 Inst then the relay would trip and reclose where...

Page 629: ...s opened e g Binary Input 1 and that no current flows in the circuit e g 37 1 Virtual 1 Incomer 1 Relay is Configured CB1 Open auxiliary switch wired to B I 1 Trip output to CB1 B O 2 OUTPUT CONFIG OUTPUT MATRIX 37 1 V1 OUTPUT CONFIG OUTPUT MATRIX E1 BO3 CONTROL LOGIC QUICK LOGIC E1 O2 I1 V1 The output from Incomer 1 BO3 relay is input to the relay on CB 3 Binary Input 1 A panel switch may be used...

Page 630: ...ent CB s On other systems however this output will be used to re trip the local CB to minimise potential disruption to the system if possible via a secondary trip coil and wiring The second CB Failure stage will then be used to back trip the adjacent CB s If the CB is faulty and unable to open a faulty contact can be wired to the CB faulty input of the relay and if a trip occurs while this input i...

Page 631: ...nce for each stage of the circuit breaker fail function is as below CB Backtrip Sucessful 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 System Fault ms from fault occuring Relay Operation and CBF Timer Started Main Trip Relay Operation Failure of CB to trip Reset of CBF elements does not occur Backtrip Operation Backtrip Trip Relay CB Operate Time Stage 1 CBF Timer Backtrip 120ms...

Page 632: ...ifferentiate between the two conditions the element uses NPS voltage to restrain the CTS algorithm as show in the accompanying table NPS Current NPS Voltage Decision Setting Setting System Fault Setting Setting CT Failure Table 5 2 Determination of CT Failure 1 or 2 Phases Following a CT Failure there should be little or no NPS voltage Perhaps 0 1 x Vn as a maximum Operation is subject to a time d...

Page 633: ... quantities to meet some older specifications There are possible problems with using NPS quantities due to load imbalances These would also generate significant levels of NPS current and so possibly cause a VT failure to be missed This problem can be overcome by careful selection of settings however setting the NPS current threshold above the level expected for imbalance conditions If a failure oc...

Page 634: ...G INPUT MATRIX menu To avoid giving spurious alarm messages while the circuit breaker is operating the input is given a 0 4 s Drop off Delay in the INPUT CONFIG BINARY INPUT CONFIG menu To provide an alarm output a normally open binary output is mapped to 74TCS n 5 4 1 Trip Circuit Supervision Connections The following circuits are derived from UK ENA S15 standard schemes H5 H6 and H7 For complian...

Page 635: ...f trip coil with the circuit breaker Open or Closed It does not provide pre closing supervision of the connections and links between the tripping contacts and the circuit breaker and may not therefore be suitable for some circuits which include an isolating link Scheme 3 Comprehensive Figure 5 4 3 Trip Circuit Supervision Scheme 3 H7 Scheme 3 provides full Trip supervision with the circuit breaker...

Page 636: ...dual phase Provides good compromise between Inrush stability and fast fault detection Table 5 5 Magnetic Inrush Bias 5 6 Broken Conductor Load Imbalance 46BC This feature is used to detect an open circuit condition when a conductor breaks or a mal operation occurs in phase segregated switchgear There will be little or no fault current and so overcurrent elements will not detect the condition Howev...

Page 637: ...e the relay setting and can cause tripping of overcurrent elements One typical example is on paralleled incoming transformer circuits forward directional overcurrent elements are parametised such that they detect faults on the transformer LV connections for currents flowing in the direction contrary to the normal load flow These forward elements have a relatively low current setting typically 45 o...

Page 638: ...figuration specifically the line loading and fault levels The measured impedance a Is used to confirm the forward or reverse flow of current i e load blinder operated b Is used to confirm that current flow is outside the defined limits of load flow i e load blinder not operated The transition between operated and non operated is subject to a 5 degree hysteresis adjustment R X Phase Fault Block Zon...

Page 639: ...able system power flow conditions i e an overcurrent blocking signal can only be issued when a Positive Sequence Voltage Vpps is not significantly reduced i e is above the 21LB 3P VPPS Setting AND b Negative Sequence Current Inps is lower than 21LB 3P INPS Setting AND c The impedance measured in all phases is within the operate zone Zpps is calculated from Vpps and Ipps The calculated Zpps is used...

Page 640: ...ad blinder takes into consideration the following effects of a high unbalanced load non fault condition The blinder is operated when a Positive Sequence Voltage Vpps is not significantly changed A high 21LB 1P VPPS setting will allow inhibiting Load Blinders in case of larger voltage drops representing fault situation AND b Zero Sequence Current Izps is lower than 21LB 1P IZPS Setting AND c The im...

Page 641: ...current relay so that tripping does not occur for load current levels with a P F 0 94 to Unity R X Phase Fault Block Zone Load Impedance b a Nominal Impedance Z 1p u VL 3 x I c R X Vpps value Point 1 Point 2 Point 3 Point 4 0 360 Trip Level I Vs Z Operate Zone a 21LB 3P Impedance setting b 21LB 3P Angle ve setting c 21LB 3P Angle ve setting Point 6 Point 5 Fwd Block Zone Load Impedance b a c Point...

Page 642: ... S P 21LB 3P Angle setting b and c A setting of 20 degrees will allow blocking of the overcurrent element for system load power factors between 0 94 and Unity 21LB 3P VPPS setting The Blinder is only operational during normal load levels of reverse load flow Where reverse current flow is caused by a system fault the positive sequence voltage will reduce significantly To facilitate Load Blinder ope...

Page 643: ...Unrestricted ...

Page 644: ...1 1TZ UnitedKingdom Phone 44 0 191 401 7901 Fax 44 0 191 401 5575 E mail marketing spdl gb siemens com For enquires please contact our Customer Support Center Phone 49 180 524 8437 24hrs Fax 49 180 524 2471 E mail support energy siemens com EMEA T10050 00 76GB October 2018 www siemens com energy ...

Reviews: