7SR21 & 7SR22 Performance Specification
Unrestricted Page 34 of 68
© 2013 Siemens Protection Devices Limited
2.12 50N Instantaneous Derived Earth Fault
2.12.1 Reference
Parameter
Value
Is
Setting
0.05, 0.06… 25, 25.5… 50 x
In
t
d
Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.12.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 %
Is
,
±
5 % or
±
1%
In
Reset level
³
95 %
I
op
Repeatability
±
1 %
Transient overreach
(X/R
£
100)
£
-5 %
Variation
-10 °C to +55 °C
£
5 %
f
nom
- 3 Hz to
f
nom
+ 2 Hz
£
5 %
2.12.3 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
Switched from 0 to 2x
Is
: 40 ms,
±
10 ms
Switched from 0 to 5x
Is
: 30 ms,
±
10 ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10 ms
Repeatability
±
1 % or
±
10 ms
Overshoot time
< 40 ms
Disengaging time
< 50 ms
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...