7SR220 Technical Manual
Chapter 4 - Page 38 of 96
© 2017 Siemens Protection Devices Limited
Truncation
Calculations are performed as 32 bit. The 16 bit value is the lowest 16 bits of the 32 bit value. Therefore,
when values overflow the returned value is the lowest 16 bits of the calculated value. For Example, if the
value is 85400 = 14D98h, the value returned would be the lowest 16 bits = 4D98h which equals 19864.
4.2.5 EVENT
MODBUS does not define a method for extracting events; therefore a private method has been defined
based on that defined by IEC60870-5-103.
The EVENT register contains the earliest event record available. The event record is 8 registers (16
bytes) of information, whose format is described below. When this record has been read it will be
replaced by the next available record. Event records must be read completely; therefore the quantity
value must be set to 8 before reading. Failing to do this will result in an exception code 2. If no event
record is present the exception code 2 will be returned. The EVENT register should be polled regularly
by the master for events.
The
register can be checked periodically to determine how many events are stored.
The format of the event record is defined by the zero byte. It signifies the type of record which is used
to decode the event information. The zero byte can be one of the following.
Format
The format of the event record is defined by the zero byte. It signifies the type of record which is used
to decode the event information. The zero byte can be one of the following.
Type
Description
1 Event
2
4
Event with Relative Time
Measurand Event with Relative Time
The following table describes the fields in the event record.
Key
FUN
Description
Function Type, as defined for IEC870-5-103.
INF
DPI
Information Number, as defined for IEC870-5-103.
Measurand Event with Relative Time, values 1 = OFF, 2 = ON.
ms L
Time Stamp Milliseconds low byte.
ms H
Time Stamp Milliseconds high byte.
Mi
Ho
Time Stamp Minutes (MSB = invalid, time not set > 23 hours).
Time Stamp Hours (MSB = Summer time flag).
RT L
Relative Time low byte.
RT H
Relative Time high byte.
F# L
Fault Number low byte.
F# H
Meas
Fault Number high byte.
Measurand format R32.23, sent least significant byte first.
The following tables show the fields in the different event records as they are returned.
Byte
0
Content
1
14
15
Mi
Ho
Event Type 1 Format.
1
2
3
4
5
6
7
8
9
10
11
12
13
0
FUN INF DPI
0
0
0
0
0
0
0
ms L
ms
H
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...