7SR210 & 7SR220 Description of Operation
Unrestricted ©2018 Siemens Protection Devices Limited
Page 77 of 94
Section 5: Supervision Functions
5.1
Circuit Breaker Failure (50BF)
The circuit breaker fail function has two time delayed outputs that can be used for combinations of re-tripping or
back-tripping. CB Fail outputs are given after elapse of the
50BF-1 Delay
or
50BF-2 Delay
settings. The two
timers run concurrently.
The circuit breaker fail protection time delays are initiated either from: -
An output
Trip Contact
of the relay (MENU: OUTPUT CONFIG\BINARY OUTPUT CONFIG\Trip
Contacts), or
A binary or virtual input assigned to
50BF Ext Trig
(MENU: INPUT CONFIG\INPUT MATRIX\50BF Ext
Trig).
A binary or virtual input assigned to
50BF Mech Trip
(MENU: INPUT CONFIG\INPUT MATRIX\ 50BF
Mech Trip).
CB Fail outputs will be issued providing any of the 3 phase currents are above the
50BF Setting
or the current in
the fourth CT is above
50BF-I4
for longer than the
50BF-n Delay
setting, or for a mechanical protection trip the
circuit breaker is still closed when the
50BF-n Delay
setting has expired – indicating that the fault has not been
cleared.
Both
50BF-1
and
50BF-2
can be mapped to any output contact or LED.
If the
CB Faulty
input (MENU: INPUT CONFIG\INPUT MATRIX\50BF CB Faulty) is energised when a CB trip is
given the time delays
50BF-n Delay
will be by-passed and the output given immediately.
Operation of the CB Fail elements can be inhibited from: -
Inhibit 50BF
A binary input, virtual input or remote data Comms.
Figure 5.1-1 Logic Diagram: Circuit Breaker Fail Protection (50BF)
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...