background image

Chapter 3 – Point Database 

27 

Siemens Industry, Inc. 

BACnet ATEC Owner's Manaul 

125-5050, Rev. AA 

 

4/20/2010 

Descriptor 

Address

1

 

Application 

Description 

travel (for use as an auxiliary slave point). This value is 

calculated based on motor run time. See MTR2 TIMING. 

VLV POS 

{53} 

2565  

The current position of the valve in percent of full travel for 

applications using a water valve. This value is calculated 

based on motor run time. 

VLV1 POS 

{53} 

2563 

The current position of valve 1 in percent of full travel for 

applications using a water valve. This value is calculated 

based on motor run time. 

MTR2 TIMING 

55 

All 

except

  

2562, 2564, 2566  

The time required for the Motor 2 actuator to travel from full 

closed to the full open position. 

DMPR ROT ANG 

56 

All 

except

 

2597

 

The number of degrees the damper is free to travel. 

DPR1 ROT ANG 

56 

2597

 

The number of degrees that damper 1 is free to travel. 

DPR2 ROT ANG 

57 

2597 

 

The number of degrees that damper 2, the hot duct damper, is 

free to travel. 

MTR SETUP 

58 

All 

The configuration setup code for Motors 1 and 2. This enables 

the motors individually and sets each motor to be either direct 

or reverse acting.  
Note: When a motor is enabled, its associated DOs are 

enabled. 

DO DIR.REV 

59

 

All 

The configuration setup code for DOs. Allows the DOs to be 

direct or reverse acting (enabled equals energized or disabled 

equals de-energized). 

EHEAT FLOW 

60 

2562 

The flow required before the electric heat will be enabled. 

COOL TEMP 

61 

2561 

The discharge air temperature where the controller will switch 

from heating to cooling mode. Used only in applications with 

SUPPLY TEMP. 

HEAT TEMP 

62 

2561 

The discharge air temperature where the controller will switch 

from cooling to heating mode. Used only in applications with 

SUPPLY TEMP. 

CLG P GAIN 

63 

All 

except

 

2597 

 

The proportional gain value for the cooling temperature 

control loop. 

CLG l GAIN 

64 

All 

except

 

2597 

 

The integral gain value for the cooling temperature control 

loop. 

CLG D GAIN 

65 

All 

except

 

2597 

 

The derivative gain value for the cooling temperature control 

loop. 

CHK OUT 

66 

All  

The procedure tests all of the necessary I/O and ensures the 

controller has the ability to operate within the set airflow 

range, between CLG FLOW MIN and CLG FLOW MAX. 

HTG P GAIN 

67 

All 

except

 

2560, 2597

 

The proportional gain value for the heating temperature 

control loop. 

HTG l GAIN 

68 

All 

except

 

2560, 2597

  The integral gain value for the heating temperature control 

loop. 

HTG D GAIN 

69

 

All 

except

 

2560, 2597

  The derivative gain value for the heating temperature control 

loop. 

CHK STATUS 

70 

All  

Displays the results of CHK OUT.  

FLOW P GAIN 

71 

All 

except

 

2597 

 

The proportional gain value for the flow control loop. 

FLOW l GAIN 

72 

All 

except

 

2597 

 

The integral gain value for the flow control loop. 

FLOW D GAIN 

73 

All 

except

 

2597 

 

The derivative gain value for the flow control loop. 

FLOW BIAS 

74 

All 

except

 

2597 

 

The biasing of the flow control loop. 

Summary of Contents for BACnet ATEC

Page 1: ...Siemens Industry Inc 125 5050 Rev AA Siemens BACnet ATEC Owner s Manual ...

Page 2: ...and in the subject thereof By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him ...

Page 3: ...e at their own expense Service Statement Control devices are combined to make a system Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation Siemens Industry Inc branch offices and authorized distributors offer Technical Support Programs that will ensure continuous trouble free system performance For further information con...

Page 4: ...enna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help To the Reader Your feedback is important to us If you have comments about this manual please submit them to mailto Sbt_technical editor us sbt siemens com Credits AP...

Page 5: ...tion 15 Heating and Cooling Switchover 15 Modulate Damper During Heating Mode optional 16 Hot Water Reheat 16 Electric Reheat 16 Notes 16 Application 2860 VAV Cooling Only 17 Application 2861 VAV Cooling or Heating 17 Application 2862 VAV with Electric Reheat or Baseboard Radiation 17 Baseboard Radiation 18 Electric Heat Interlock 18 Application 2863 VAV with Hot Water Reheat 18 Application 2864 V...

Page 6: ...l 125 5050 Rev AA 4 20 2010 Using the Controller as a Point Extension Device 22 Chapter 3 Point Database 24 Chaper 4 Troubleshooting 30 Basic Service Information 30 Preventive Maintenance 30 Safety Features 31 Controller LEDs 31 Glossary 32 Index 35 ...

Page 7: ...er a problem when using the BACnet VAV Actuator For issues not covered in this chapter consult your local Siemens Industry representative The Glossary describes the terms and acronyms used in this manual The Index helps you locate information presented in this manual Manual Conventions The following table lists conventions to help you use this manual in a quick and efficient manner Convention Exam...

Page 8: ...table lists the safety symbols used in this manual to draw attention to important information Symbol Meaning Description NOTICE CAUTION Equipment damage may occur if a procedure or instruction is not followed as specified For online documentation the NOTICE displays in white with a blue background CAUTION Minor or moderate injury may occur if a procedure or instruction is not followed as specified...

Page 9: ...of the controller and the mounting bracket Table 1 lists the BACnet ATEC products that are covered Table 1 BACnet ATEC Electronic Output Applications Application Number Application Description 2860 VAV Cooling Only 2861 VAV Cooling or Heating 2862 VAV with Electronic Reheat or Baseboard Radiation 2863 VAV with Hot Water Reheat 2864 VAV Series Fan Powered with Electric Reheat 2865 VAV Series Fan Po...

Page 10: ...Rev AA 4 20 2010 Siemens BACnet ATEC Hardware Inputs Analog Air Velocity Sensor AVS Duct temperature sensor optional Application 2861 Room temperature sensor RTS Room temperature setpoint dial optional Digital Night mode override optional Wall switch optional Hardware Outputs Analog None ...

Page 11: ... or 2 position heating valve 2862 Stage 1 electric reheat 2864 2866 Stage 2 electric reheat optional 2862 2864 2866 Stage 3 electric reheat optional 2862 Valve actuator 2865 2867 Power Wiring The controller is powered by 24 Vac Power wiring connects to the two screw terminals on the controller labeled C Common and H Hot on the terminal block labeled 24 VAC No earth ground connection is required Se...

Page 12: ...gure Siemens BACnet ATEC Controller LEDs LED Type Label if present LED Number Indication DO LED 3 LED 5 3 5 Indicates the ON OFF status of the DO associated with it A glowing LED indicates that the DO is energized Transmit TX 0 Indicates when flashing that the controller is transmitting information to the field panel Receive RX 1 Indicates when flashing that the controller is receiving information...

Page 13: ...or RJ 11 plug in connector Duct Temperature Sensor An optional duct temperature sensor provides duct air temperature sensing inputs to the controller For more information about temperature sensors contact your local Siemens Industry representative Related Equipment Autozero Module optional 540 200 Relay Module Damper Actuator s Duct Temperature Sensor optional Room Temperature Sensor Contact your ...

Page 14: ...le Control Temperature Setpoints The controller maintains a specified temperature setpoint based on Day Night mode or the heating cooling mode or the setpoint dial if used Day Night Mode The controller maintains the specified day setpoint temperature during daytime hours and the specified night setpoint at night Night Mode Override Switch If the ROOM TEMPERATURE SENSOR has an override switch it ca...

Page 15: ...hot water valve if used is done by briefly commanding the valve closed Application 2863 2865 2867 Damper Status Operation It is possible after a period of operation for the calculated damper position to differ from the actual physical damper position If this occurs the controller will automatically compensate for any difference by readjusting the calculated damper position This calculated position...

Page 16: ...closed The heating loop modulates the heating valve s to warm up the room In cooling mode the heating valve is closed Electric Reheat CAUTION Verify that the equipment is supplied with safeties by others to ensure that there is airflow across the heating coils when they are to be energized The heating loop controls up to three stages of electric reheat to warm up the room The electric reheat is ti...

Page 17: ...In Application 2861 the controller modulates the supply air damper of the terminal box for cooling and heating In order for it to work properly the central air handling unit must provide cool supply air in cooling mode and warm air during heating mode See the following figure Application 2862 VAV with Electric Reheat or Baseboard Radiation In Application 2862 the controller modulates the supply ai...

Page 18: ...mum to less than 5 otherwise the electric heat interlock will be disabled The electric heat stages will be disabled turned off when the electric heat airflow is less than the defined minimum Application 2863 VAV with Hot Water Reheat In Application 2863 the controller modulates the supply air damper of the terminal box for cooling and controls a hot water valve or baseboard radiation for heating W...

Page 19: ... supply air damper Application 2864 has a series fan for air circulation In order for the terminal box to work properly the central air handling unit must provide supply air See the following figure Fan Operation CAUTION On series fan powered terminal boxes the terminal box fan must be controlled interlocked to start either before or at the same time as the central air handler Failure to do so may...

Page 20: ...owered terminal boxes the terminal box fan must be controlled interlocked to start either before or at the same time as the central air handler Failure to do so may cause the terminal box fan to rotate backwards and cause consequent damage at start up In day mode the fan is ON all the time In night mode the fan cycles on when heating or cooling is required Application 2866 VAV Parallel Fan Powered...

Page 21: ...Water Reheat In Application 2867 the controller modulates the supply air damper of the terminal box for cooling and modulates a hot water valve for heating When in heating the terminal box either maintains minimum airflow or modulates the supply air damper Application 2867 has a parallel fan that re circulates the room air In order for the terminal box to work properly the central air handling uni...

Page 22: ...er parameters CTLR ADDRESS APPLICATION etc A controller in default state can also be used as a point extension device by unbundling spare I O points at the field panel Using Auxiliary Points It is possible to have extra points available on a BACnet VAV Controller Electronic Output in addition to the ones used by the current application that is running in the controller If these extra points are to...

Page 23: ... control a motor as shown in the example NOTE If using either a motor or DOs as auxiliary points be sure to set MTR SETUP to the correct value If using a pair of DOs to control a motor then the DOs cannot be unbundled Only MTR COMD can be unbundled to control the motors Contact your local Siemens Industry representative for other combinations of DOs and motors ...

Page 24: ...TPT 08 All except 2597 The temperature setpoint in degrees that the controller maintains during the night periods in cooling mode NGT HTG STPT 09 All except 2560 2597 The temperature setpoint in degrees that the controller maintains during the night periods in heating mode RM STPT MIN 11 All except 2597 The minimum temperature setpoint in degrees that the controller can use from the setpoint dial ...

Page 25: ...e switch has been pressed and the override timer is active The controller then uses a day mode temperature setpoint This point is only in effect when DAY NGT indicates night mode REHEAT START 22 All except 2560 2561 2597 Determines how the reheat modulation will be sequenced while in heating mode When HTG LOOPOUT is above this value then the reheat modulates upward REHEAT END 23 All except 2560 25...

Page 26: ...tal output 5 controls a 24 Vac load with an ON or OFF status If Motor 3 is enabled DO 5 is coupled with DO 6 to control an actuator DO 5 45 2565 2567 Digital output 5 controls a 24 Vac load with an ON or OFF status HEAT STAGE 3 45 2 2562 2564 2566 This point is a digital output used to control the contact for the third stage of heating and has a status of ON or OFF FAN 46 2564 2565 2566 2567 This ...

Page 27: ...energized EHEAT FLOW 60 2562 The flow required before the electric heat will be enabled COOL TEMP 61 2561 The discharge air temperature where the controller will switch from heating to cooling mode Used only in applications with SUPPLY TEMP HEAT TEMP 62 2561 The discharge air temperature where the controller will switch from cooling to heating mode Used only in applications with SUPPLY TEMP CLG P ...

Page 28: ...ric heat With electric heat this value is equal to HTG LOOPOUT STAGE COUNT STAGE MAX 82 2562 2564 2566 The value in percent which the heating loop must exceed for the electric heat to be ON for the full duty cycle STAGE TIME STAGE FAN 83 2565 2567 The valve must be opened greater than this value before the fan will turn ON STAGE MIN 83 2562 2564 2566 The value in percent which the heating loop mus...

Page 29: ...s of the duct where the air velocity sensor is located This is a calculated value calculated by the field panel or computer being used that depends on duct shape and size It is used in calculating all points in units of CFM CF LPS and L Valid input 025 ft2 002 m2 through 6 375 ft2 5923 m2 LOOP TIME 98 All except 2597 The time in seconds between control loop calculations ERROR STATUS 99 2 All The s...

Page 30: ...ller is to turn OFF the power to the 24 Vac transformer The recommended method of removing power to a controller on a power cable even to service a single controller is to turn OFF the power at the transformer NOTE When removing power to a controller to perform maintenance or service make sure that the person in charge of the facility is aware of this and that appropriate steps are taken to keep t...

Page 31: ...ller will activate safety features present in its fail safe mode Sensor failure Loss of power Upon controller power loss communication with the controller is also lost The controller will appear as failed F at the field panel Controller LEDs NOTE The TX and RX LEDs indicate communication over the FLN To determine if the controller is powered up and working verify that the Basic Sanity Test BST Lig...

Page 32: ...e an output value AVS Air Velocity Sensor centralized control Type of control offered by a controller that is connected by means of Field Level Network FLN cfm Cubic Feet per Minute control loop PID algorithm that is used to control an output that is based on a setpoint and an input reading from a sensor DDC Direct Digital Control DO Digital Output Physical output point that sends a two state sign...

Page 33: ...ws you to communicate with a field panel or equipment controller override switch Button on a room temperature sensor that an occupant can press to change the status of a room from unoccupied to occupied or from night to day for a predetermined time pressure independent Variable Air Volume VAV room temperature control system in which the temperature drives an airflow setpoint PID Proportional Integ...

Page 34: ...nic Output that house the applications software used to control terminal units such as heat pumps VAV terminal boxes fan coil units unit ventilators etc UI Universal Input Can be used as an AI or DI An AI input is a point receiving a signal that represents a condition that has more than two states A DI input is a physical input point that receives a two state signal unbundle Term used to describe ...

Page 35: ...rawing 19 electric heat 20 electric heat interlock 20 overview 19 application 2863 control drawing 20 overview 20 application 2864 overview 21 application 2865 overview 22 Application 2865 fan operation 22 application 2866 overview 23 application 2867 overview 23 Application 2897 overview 24 using controller as point extension device 24 applications calibration 17 27 control loops 16 control tempe...

Page 36: ... H hardware autozero module 17 fan 11 13 21 22 23 24 LEDs 14 power wiring 13 relay module 15 temperature sensors 15 L Light Emitting Diodes LEDs 32 BST 32 RX and TX 32 loopout 34 O override switch 34 P PID 34 point database overview 25 power wiring 13 preventive maintenance 31 R related equipment 15 relay module 15 RTS 34 RX LED 32 S safety features 32 service information basic 31 SI units 34 stan...

Page 37: ...Index 37 Siemens Industry Inc BACnet ATEC Owner s Manaul 125 5050 Rev AA 4 20 2010 W wiring communication wiring 14 power wiring 13 ...

Page 38: ...eerfield Parkway Buffalo Grove IL 60089 USA Tel 1 847 215 1000 2010 Copyright Siemens Industry Inc Technical specifications and availability subject to change without notice Document ID 125 5050 Rev AA Manual Siemens BACnet ATEC Owner s Manual Edition 4 20 2010 Register ...

Reviews: