instabus EIB

 

Technical Product Information 

September 2001 

Binary Input N 260  

5WG1 260-1AB01 

 

4 x 230 V AC 

Product and Applications Description 

Siemens AG 

N 260, 4 pages 

Technical Manual 

 

 

 
The binary input N 260 is a N-system DIN-rail mounted 
device with four inputs for AC 230 V switching or keying 
signals from separate external outside lines (L1, L2, L3) 
with a shared reference potential (N). 
Each of the inputs can be assigned various tasks  
depending on the application program used, i.e. the 
binary input N 260 consists of the device (hardware) and 
its application programs (software). 
Appropriate application programs are available for 
the different tasks the binary input N 260 can handle; 
e.g. sending of on/off telegrams at different edges of the 
input signal either event-controlled or cyclic with 
parametrisable repetition intervals. 
With the ETS (

EIB

 Tool Software) the application 

program is selected, its parameters and addresses are 
assigned appropriately, and downloaded to the binary 
input N 260. 
 
 

Applikationsprogramme 

 

12 S4 BinCycl 240505 

• 

4 binary inputs 

• 

each input allows switching on/off or toggling at 
leading or trailing edge 

• 

allows cyclic sending 

• 

allows sending at bus voltage recurrence 

• 

sending condition can be set 

 

12 S2 On-off-toggle/Dim/Shu 220703 

• 

4 binary inputs  

• 

allows configuration for dimmer/shutter or 
on/off/sending value 

• 

switching at leading edge or at leading and trailing 
edge 

• 

switching short/long key depression 

• 

sending value at leading edge or at leading and 
trailing edge 

• 

duration of long key depression can be set  

• 

used type of contacts can be set 

 

11 S4 BinVal 240A01 

• 

4 binary inputs  

• 

each input allows to send values at leading edge 
and/or at leading and trailing edge 

• 

allows cyclic sending 

• 

allows delay 

• 

allows interlocking 

 
 

Example of Operation 

in

st

ab

us

 E

IB

binary input N 260

switching /
keying signals

load circuit

AC 230/400V

L1

bu

s c

oup

lin

g

 un

it

L2 L3 N

channel A

channel B

channel C

N

channel D

2

4

3
6

1

5

 

Installation Instructions 

 

• 

The device may be used for permanent interior 
installations in dry locations within distribution boards. 

 
 

V

 WARNING

 

• 

The device may be built into distribution boards 
(230/400 V) if VDE-certified devices are used 
exclusively and must be mounted and commissioned 
by an authorised electrician. 

• 

A safety disconnection of the device must be possible. 
Especially if the device is connected to different 
phases. 

• 

Free DIN rail areas must be covered with covers, 
order no. 5WG1 192-8AA01. 

• 

The prevailing safety rules must be heeded. 

• 

The device must not be opened. A device suspected 
faulty should be returned to the local Siemens office. 

 

Automation and Drives Group 

 

 

Electrical Installation Technology 

 Siemens AG 2001 

Update: http://www.siemens.de/installationstechnik 

P.O.Box 10 09 53, D-93009 Regensburg 

Subject to change without prior notice 

 

 

2.7.1.3/1 

Summary of Contents for Binary Input N 260

Page 1: ...or dimmer shutter or on off sending value switching at leading edge or at leading and trailing edge switching short long key depression sending value at leading edge or at leading and trailing edge duration of long key depression can be set used type of contacts can be set 11 S4 BinVal 240A01 4 binary inputs each input allows to send values at leading edge and or at leading and trailing edge allow...

Page 2: ...mm flexible conductor with terminal pin crimped on gas tight 0 5 1 5 mm flexible conductor with connector sleeve 1 0 and 1 5 mm plain flexible conductor V WARNING When looping through the shared N conductor connection blocks 3 and 6 take care that the maximum connection current of 2 A as governed by the maximum permissible printed conductor load is not exceeded bus line pressure contacts on data r...

Page 3: ...es Figure 2 Slide the device B1 onto the DIN rail B2 and swivel back the device until the slide clicks into place audibly Dismounting DIN rail devices Figure 2 Remove all connected wires press down the slide C3 with a screw driver and swivel the device C1 from the DIN rail C2 B1 C1 C2 C3 B2 Figure 2 Mounting and dismounting a DIN rail device Connecting input circuits Figure 3 The load circuits are...

Page 4: ...am Dimensions in mm b 90 44 55 45 b 2 SU 1 Spacer unit SU 18mm Notes Technical Manual N 260 4 pages Siemens AG Automation and Drives Group Update http www siemens de installationstechnik Siemens AG 2001 Electrical Installation Technology Subject to change without prior notice P O Box 10 09 53 D 93009 Regensburg 2 7 1 3 4 ...

Reviews: