Chapter 4 - Parameters and Menu Structure
Monitor Menu (M2)
31 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
through the list of items until the desired value to be monitored is highlighted. Items with a checkmark are already
actively displayed in the multimonitor display. With an item chosen, press the
button again to add to the
display field.
Basic (M2.2)
The basic monitoring values are the actual values of selected parameters and signals as well as statuses and
measurements. Different applications may have different statuses and different numbers of monitoring values.
NOTE:
Only Standard I/O board statuses are available in the Monitor menu. Statuses for all
I/O board signals can be found as raw data in the I/O and Hardware (M5) menu.
The basic monitoring values are presented in the following table:
Table 6: Monitoring Menu Items.
Structure
Parameter
Unit
ID
Description
M2.2.1
Output Frequency
Hz
1
Displays the actual output frequency.
M2.2.2
FreqReference
Hz
25
Displays the actual frequency reference (setpoint).
M2.2.3
Motor Speed
rpm
2
Displays the actual motor speed.
M2.2.4
Motor Current
A
3
Displays the actual motor current.
M2.2.5
Motor Torque
%
4
Displays the calculated motor torque.
M2.2.7
Motor Power
%
5
Total power consumption of the drive in %
M2.2.8
Motor Power
hp
73
Total power consumption of the drive in kW or hp
M2.2.9
Motor Voltage
V
6
Voltage feed to the motor
M2.2.10
DC-Link Voltage
V
7
Voltage available on the DC Link
M2.2.11
Unit Temperature
ºF
8
Heat sink temperature
M2.2.12
MotorTemperature
%
9
Calculated motor temperature
M2.2.13
Analog Input 1
%
59
Signal of used range in %
M2.2.14
Analog Input 2
%
60
Signal of used range in %
M2.2.15
Analog Output 1
%
81
Signal of used range in %
M2.2.16
Motor PreHeat
1228
0 = Off
1 = Heating (feeding DC current)
M2.2.17
DriveStatusWord
43
Bit coded status of the drive
B1 = Ready
B2 = Run
B3 = Fault
B6 = Run Enable
B7 = Alarm Active
B10 = DC Current (in stop)
B11 = DC Brake Active
B12 = Run Request
B13 = Motor Regulator Active
M2.2.18
Last ActiveFault
37
Fault code of last activated fault that has not been reset.
See Fault Codes.