Chapter 4 - Parameters and Menu Structure
Parameters (M3)
50 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.3.17
Preset Freq 6
Hz
Parameter
1.8 or P3.3.1
Parameter
1.9 or P3.3.2
40
129
Defines the frequency to be used
when the following occurs:
1. PresetFreqMode (P3.3.10) is set to
Binary Coded &
Preset Freq Sel0 (P3.5.1.15) is de-
activated.
Preset Freq Sel1 (P3.5.1.16) is
activated.
Preset Freq Sel2 (P3.5.1.17) is
activated.
P3.3.18
Preset Freq 7
Hz
Parameter
P1.8 or
P3.3.1
Parameter
P1.9 or P3.3.2
50
130
Defines the frequency to be used
when the following occurs:
1. PresetFreqMode (P3.3.10) is set to
Binary Coded &
Preset Freq Sel0 (P3.5.1.15) is
activated.
Preset Freq Sel1 (P3.5.1.16) is
activated.
Preset Freq Sel2 (P3.5.1.17) is
activated.
P3.3.19
PresetAlarmFreq Hz
Parameter
P1.8 or
P3.3.1
Parameter
P1.9 or P3.3.2
25
183
Defines the frequency to be followed
when fault responses (found in
Protections [P3.9]) are defined for
Alarm + Preset Freq.
AI Low Fault (P3.9.1)
FieldbusComm Flt (P3.9.19)
P3.3.20
MotPot Ramp
Time
Hz/s
0.1
500
10
331
Rate of change in the motor
potentiometer reference when
increased or decreased.
P3.3.21
MotPot Reset
No Reset
Powered down
Stop State
367
Motor potentiometer frequency
reference reset logic
0 = No Reset
1 = Reset if stop state
2 = Reset if powered down
Understanding Preset Frequencies
Preset frequency mode (P3.3.10)
You can use the preset frequency parameters to define certain frequency references in advance. These references
are then applied by activating/deactivating the digital inputs connected to parameters Preset frequency selection 0
(P3.5.1.15), Preset frequency selection 1 (P3.5.1.16) and Preset frequency selection 2 (P3.5.1.17). Two different
logics can be selected:
Table 27: Preset Frequency Logic.
Selection
number
Selection name
Note
0
Binary coded
Combine activated inputs according to the table below to choose
the Preset frequency needed.
1
Number (of inputs
used)
You can apply the
Preset frequencies 1 to 3, depending on how
many of the inputs assigned for
Preset frequency selections are
active.