Chapter 4 - Parameters and Menu Structure
Parameters (M3)
93 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Figure 25: Dead band.
Sleep frequency limit 1 (P3.12.2.7), Sleep delay 1 (P3.12.2.8), and Wake-up level 1 (P3.12.2.9)
This function puts the drive into sleep mode if the frequency stays below the sleep limit for a longer period than
that set with the Sleep Delay (P3.12.2.8). This means that the start command remains on, but the run request is
turned off. When the actual value goes below or above the wake-up level depending on the set acting mode, the
drive will activate the run request again, if the start command is still on.
11105.emf
Dead band (P3.12.1.9)
Reference
Dead band delay (P3.12.1.10)
Output locked
Actual value