Siemens Building Technologies
CA2N5241E / 11.1998
Landis & Staefa Division
3/4
After start-up (or after a reset), it is also possible to set a daily switch programme with
12 switching operations (6 On and 6 Off) by setting the actual times only, without
pressing d for the day of the week.
The daily programme is indicated by the arrow above 1 –> 7 .
Since during programming no days need to be entered, programme entry starts with the
switching times.
To display the programmed ON and OFF settings, press Prog.
Press
after a review of these settings.
Recall the command by pressing Prog. and change it by pressing h , m and, if
necessary, d .
Alternatively, clear the displayed command by pressing h + m simultaneously.
Press
after completing the changes.
A holiday programme can be used to suspend the automatic programme for a period of
1 ... 45 days. Hold down the h key throughout the entry procedure. Press
repeatedly, counting the number of holiday days individually.
After 45 (days) the display will revert to 0. The holiday programme will start at 00:00 on
the following day, and is indicated by H
OFF
.
Christmas holiday:
24 December to 2 January inclusive
Total days:
10 (Enter on 23 December)
Press h to display the stored or remaining number of holiday days. Simultaneously
press h and
to extend the holiday programme, or to reset it to 0 to continue with
the automatic programme sequence.
These options can be carried out before or during the holiday period.
Press
to toggle between ON and OFF.
This manual operation will be overridden by the next programmed switching sequence.
This facility is not available during a holiday period.
Press
and m simultaneously to set automatic operation to "Permanent ON" or
"Permanent OFF". This continuous control function is indicated by a bullet symbol above
the ON or OFF indicator in the display and may be initiated during a holiday period 1).
Note that in this case, whichever permanent state has been invoked will
remain in operation after expiry of the holiday period.
To change or exit from a permanent state hold down the m key and press
repeatedly to toggle between the states "Permanent ON", "Permanent OFF" and "Auto"
(bullet disappears).
+ 1 hour:
press d + h simultaneously
– 1 hour:
press d + m simultaneously
+ = Press
simultaneously
/ = Press
consecutively
d + m +
+
= Reset / clear
+ d / h / m
= Set clock (day and time)
+ h / m
= Set clock (time only)
= Clock operation
d + h
= + 1h (summer time)
d + m
= - 1h (winter time)
Prog / d /
/ h / m = Programme / Correction
Prog / h + m
= Delete programme
h +
= Holiday (max. 45 days)
m +
= Mode selection: On / Off / Auto
Daily programme
Recall
Changing or clearing
a command
Holiday programme
Example 2
Recalling / changing /
clearing
a holiday programme
Override
Permanent control
Daylight savings
change-over
Summary