background image

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-034200-9

2

Any or all of the CDC-4 circuits may be programmed to operate with Alarm Verifica-
tion. This allows the automatic verification of alarm conditions caused by smoke
detectors in order to prevent nuisance alarms. For further information, refer to the
FireFinder-XLS Manual, P/N 315-033744.

When upgrading the firmware in the CDC-4, be sure to check the PC board version.

Version 2.0 and above firmware are only compatible with PC board P/N 580-034888.

If version 2.0 or above firmware is uploaded into the older version of the CDC-4, the

PMI/PMI-2/PMI-3 displays “ROM SW Version Error”.  The PC board revision number is

printed on the back of the CDC-4 board.

Controls and Indicators

The front panel of the CDC-4 contains one reset switch, sixteen LEDs, and three
HNET address switches as shown in Figure 1.

A reset switch is located on the top of the front panel. Pushing the reset switch re-
initializes the CDC-4 operation (similar to a cold boot).

The LEDs follow the reset switch and their functions are defined as follows:

POWER

(Green)

Normally ON. When illuminated, indi-
cates that power for the CDC-4 is applied
to the card.

CARD FAIL

(Yellow)

Normally OFF. When illuminated, indi-
cates that the card microprocessor has
failed.

HNET FAIL

(Yellow)

Normally OFF. When illuminated, indi-
cates that the HNET communication with
the CDC-4 has terminated and the card
goes into degrade mode (applicable only
when card resides in the HNET network).

GND FAULT

(Yellow)

Normally OFF. When illuminated, indi-
cates that the CDC-4 has detected either
a negative or positive ground fault.

ZONE 1 ALARM

(Red)

Normally OFF. When illuminated indi-
cates that an alarm condition has been
detected in Zone 1. It will stay on
continuously until the system is reset.

ZONE 1 TROUBLE

(Yellow)

Normally OFF. When illuminated, indicates
that a trouble condition has been de-
tected in Zone 1. It will stay on continu-
ously until the condition is cleared.

ZONE 1 CLASS A OPEN

(Yellow)

Normally OFF. When illuminated, indi-
cates that there is a break in the Class A
wiring in Zone 1.

ZONE 2 ALARM

(Red)

Normally OFF. When illuminated indi-
cates that an alarm condition has been
detected in Zone 2.  It will stay on
continuously until the system is reset.

Summary of Contents for CDC-4

Page 1: ... functions to operate Any circuit in an alarm or trouble condition is displayed on the PMI PMI 2 PMI 3 The CDC 4 is designed to function in a local degrade mode during failure of the FireFinder XLS main processor or during the loss of the system communication network While in the degrade mode the CDC 4 can report both alarm and trouble conditions and can activate local outputs on other modules wit...

Page 2: ...e reset switch and their functions are defined as follows POWER Green Normally ON When illuminated indi cates that power for the CDC 4 is applied to the card CARD FAIL Yellow Normally OFF When illuminated indi cates that the card microprocessor has failed HNET FAIL Yellow Normally OFF When illuminated indi cates that the HNET communication with the CDC 4 has terminated and the card goes into degra...

Page 3: ...LE Yellow Normally OFF When illuminated indicates that a trouble condition has been de tected in Zone 4 It will stay on continu ously until the condition is cleared ZONE 4 CLASS A OPEN Yellow Normally OFF When illuminated indi cates that there is a break in the Class A wiring in Zone 4 Three rotary dial switches at the bottom of the front panel are used to set the HNET network address of the CDC 4...

Page 4: ... without conduit may also be used The CDC 4 may be connected to existing device loops that have a 3 9K or 4 7K end of line resistor 1 4W 5 or a 50uF 50V end of line capacitor installed Always use a 50uF 50V end of line capacitor for new installations and whenever practical in existing detector loops for all detector models except the Siemens PBA 1191 which requires a 4 7K end of line resistor as s...

Page 5: ...or List for the maximum number of detectors per zone 5 Do not mix smoke detectors with the PBA 1191 6 Do not mix different manufacturer s smoke detectors on the same zone 7 Max resistance 70 ohms circuit 40 ohms circuit if accessories relay audible bases are used 8 Do not use shorting devices on circuits with accessories on them 9 Only one device accessory per circuit is guaranteed to activate on ...

Page 6: ...p the system and verify that the CDC 4 power LED turns ON INITIATING DEVICES Refer to the UL Compatible Two Wire Detector List for the number of detectors that may be used on a CDC 4 zone Refer to Figure 3 for initiating device wiring All circuits are power limited to NFPA 70 per NEC 760 Each detector or group of detectors must use a two wire circuit of at least 18 AWG thermoplastic fixture wire e...

Page 7: ... a B V 4 2 0 t n e r r u C V 4 2 l a n i m r e T w e r c S y r o s i v r e p u S x a m e n o z r e p A m 8 A m 0 1 1 y r o s i v r e p u S x a m e n o z r e p A m 8 A m 0 1 1 m r a l A x a m e n o z r e p A m 0 2 3 A m 0 1 1 m r a l A x a m e n o z r e p A m 0 8 2 A m 0 1 1 t n e r r u C e n a l P k c a B V 2 6 x a m A m 0 5 1 t n e r r u C y b d n a t S V 4 2 y r o s i v r e p u S x a m e n o z r...

Page 8: ...T 4 B D S T 4 B D F T 4 B D 0 3 0 3 Y s n e m e i S 6 I D 6 I D S T 4 B D F T 4 B D S T 4 B D F T 4 B D 0 3 0 3 Y s n e m e i S 5 3 1 P 3 T D 5 3 1 P 3 T D S 3 B D S 3 B D d e t i m i l n U Y s n e m e i S 1 1 T D 1 1 T D 1 1 B D T P D A w S 3 B D 1 1 B D S 3 B D 0 3 0 3 Y s n e m e i S 1 2 1 I H 1 2 1 I H E 1 1 B D 1 1 B D E 1 1 B D 1 1 B D 0 3 0 3 Y Y s n e m e i S 1 2 1 H O 1 2 1 H O E 1 1 B D ...

Page 9: ... 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 0 2 1 8 6 5 4 0 2 2 1 8 6 5 4 7 2 2 1 8 6 5 4 0 3 2 1 8 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 3 0 3 5 2 5 2 5 2 0 3 N o l l o p A 0 8 3 0 0 0 5 5 0 8 3 0 0 0 5 5 0 0 2 1 8 6 5 4 0 2 2 1 8 6 5 4 7 2 2 1 8 6 5 4 0 3 2 1 8 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 0 2 1 8 6 5 4 0 2 2 1 8 6 5 4 7 2 2 1 8 6 5 4 0 3 2 1 8 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 2...

Page 10: ...c e l E L S E T C 9 2 4 A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T F A C 1 1 5 A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T F A C 8 1 5 A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T X B B 1 2 5 F F O 1 w S w A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T X R C 1 2 5 F F O 1 w S w A 1 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T X B B 8 2 5 F F O 1 ...

Page 11: ...2 4 S N 0 2 2 6 S N 3 B H 5 1 5 1 Y Y i k i h c o H 4 2 J I S 3 D H 4 2 2 4 S N 4 2 2 6 S N 5 B H 5 1 5 1 Y Y i k i h c o H F 4 2 K L S H F 4 2 K L S 3 D H D 2 2 S H 2 2 M A B Y 3 B H 3 B H 0 2 0 2 Y Y i k i h c o H F 4 2 K L S H F 4 2 K L S 3 D H D 4 2 2 S H 4 2 2 M A B Y 5 B H 5 B H 0 2 0 2 Y Y i k i h c o H F 4 2 K L S H F 4 2 K L S 3 D H 4 2 2 B S H 3 5 B H 0 2 0 2 Y N i k i h c o H F 4 2 K L ...

Page 12: ...4 B 1 0 4 B B 6 0 4 B d n a A 5 2 Y r o s n e S m e t s y S K R B H D 1 5 4 1 A 0 0 4 H D A 5 2 N r o s n e S m e t s y S K R B 1 5 1 2 A d n a P L 0 1 1 B P L 6 1 1 B A 5 2 Y r o s n e S m e t s y S K R B T 0 0 3 2 A A N A N 5 2 N r o s n e S m e t s y S K R B 0 0 4 2 A A N A N 5 2 Y r o s n e S m e t s y S K R B H T 0 0 4 2 A A N A N 5 2 Y r o s n e S m e t s y S K R B 1 5 4 2 A B 1 0 4 B 1 0 4 ...

Page 13: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 14: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 034200 9 Document ID A6V10239127 ...

Reviews: