e1901a
4
Fire & Security Products
Siemens Building Technologies Group
06.2001
2.1
Algo-Parameter sets for DOT1151A-Ex
AlgoRex smoke sensitivity index (1)
Parameter set
Operating state
Without temperature
influence
With full temperature
influence
Response time
when testing with
test gas (~seconds)
APS083S
present
for danger level 3 with
smoke
3.5
60
APS083S
absent
1.3
3.5
60
2) 3)
!
special
no response to smoke
(only temperature
actuation)
present
APS005S
absent
1
2
110
(Default)
special
no response to smoke
(only temperature
actuation)
APS082S
for China only: Similar as APS005S, but thermal behaviour changed according
to chinese standards.
present
APS015S
absent
1
2
85
APS015S
special
no response to smoke
(only temperature
actuation)
present
60
APS006S
absent
1
2.5
40
APS006S
special
no response to smoke
(only temperature
actuation)
present
75
APS085S
absent
1.4
4.3
45
APS085S
special
no response to smoke
(only temperature
actuation)
present
APS084S
absent
1.5
2
240
2) 3)
!
special
no response to smoke
(only temperature
actuation)
present
APS009S
absent
2
4
110
APS009S
special
no response to smoke
(only temperature
actuation)
present
APS019S
absent
2
4
85
APS019S
special
no response to smoke
(only temperature
actuation)
present
60
APS007S
absent
2
5
40
APS007S
special
no response to smoke
(only temperature
actuation)
present
60
APS081S
absent
4
8 *
30
APS081S
special
no response to smoke
(only temperature
actuation)
present
APS080SH
absent
5.5
12
15
1) 2)
!
special
no response to smoke
(only temperature
actuation)
present
Test mode
absent
2
5
5
With the exception of test mode, the parameter sets listed here are arranged in order of
sensitivity (APS080SH is the most sensitive).
*
Comment: Slightly corrected values compared to those noted in the help of
AlgoWorks EP5 (SR1) update 2.