28/36
Siemens
Climatix HMI-DM
CB1P3916en02
Building technologies
Functions and operations
2015-07-02
The online trend page supports max. 2 trend lines, which will be displayed
alternately every 5 seconds. The current trend is displayed with an arrow. If users
select more than two data points, the trend of oldest data will be phased out.
4.11 Graphical time scheduler
HMI-DM and HMI-TM have graphical time scheduler functionality. This function is
available with BSP 10.xx or above. Other HMI types have only text time scheduler
(e.g. HMI-IB, HMI4Web).
1. Define the name for time scheduler (e.g. “Enumeration Scheduler” or “Set
point Scheduler”) in SCOPE as follows.