167 / 244
Siemens
Standard application AHU
CE1P3977en_02
Building Technologies
Configuration
01.02.2010
15.3 Configuration I/Os
15.3.1 Start page
In Configuration I/Os, the required I/Os, previously set in Configuration 1 and Con-
figuration 2 by the selected functions, are assigned to hardware.
Moreover, the parameterization of the required conversion for the sensors takes
place here (e.g. Ni1000; Pt1000; 0-10 V = 0-1000 Pa).
•
Basis controller: All single-digit positions, e.g. X1.
•
Extension module 1: All positions X1x, DI1x, DO1x, AO1x, e.g. X11, DO14.
•
Extension module 2: All positions X1x, DI1x, DO1x, AO1x, i.e., for example,
X11, DO14.
The I/Os on the extension modules are available, if the module was enabled in
Configuration 1.
Configuration 1 and Configuration 2 completed with one reset each.
As required:
Start page > Password Enter
then:
Main Index > Configuration > Configuration IO’s
Parameter
Range
Function
Temperatures
Go to hardware configuration page for all temperature sensors.
Pressures / flows
Go to hardware configuration page for all pressure and flow sensors.
Humidity
Go to hardware configuration page for all humidity sensors.
Digital inputs
Go to hardware configuration page for all digital inputs without alarm
function.
Digital alarms
Go to hardware configuration page for all digital inputs with alarm
function.
Other
Go to hardware configuration page for air quality sensor and the ex-
ternal setpoint adjuster.
Outputs damper
Go to hardware configuration page for supply, exhaust air and fire
dampers.
Output fans
Go to hardware configuration page for fans.
Outputs tmp control
Go to hardware configuration page for heating, cooling heat recovery,
etc.
Outputs humidifier
Go to hardware configuration page for the humidifier.
Outputs auxiliary
Go to hardware configuration page for auxiliary functions.
Outputs alarm
Go to hardware configuration page for both alarm outputs.
Configuration IOs
This parameters enable the plant after successful parameterization.
Enable occurs when Configuration 1, Configuration 2 and Configura-
tion I/Os are completed, i.e. when each has the value "done".
NotDone
Plant locked against switching on.
Done
The plant is unlocked after complete parameterization, i.e. it can be
switched on.
Reset Required !!
Passive
Execute
Reset required after successful parameterization in Configuration
I/Os. Assumes the appropriate presettings for Configuration I/Os.
After reset, value automatically goes from execute to passive.
Task
Distribution to basis con-
troller and extension
modules.
Note
Prerequisite
Start
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 167