59 / 244
Siemens
Standard application AHU
CE1P3977en_02
Building Technologies
Functions
01.02.2010
5.5 Temperature control
5.5.1 General
Displays only the functions enabled in configuration 1 or configuration 2. All other
functions are hidden. General there is a mix of use of exhaust and return air
sensor!
Main Index > Unit > Temp control
Parameter
Function
Act controlled tmp
Present temperature used for control. Eight supply air, room or return tempera-
ture depending on the setting and control type.
Tmp setpoints
Go to setpoint page with all setpoints affected by temperature control, e.g. com-
fort, economy, cascade min max, deviation alarm, summer-winter compensation.
Cascade controller
Displays heating and cooling setpoint. Go to cascade controller page with de-
tailed settings.
Min/max ctrlr sply
Go to page for min/max ctlr sply to parameterize the minimum and maximum limit
controller. You can use the existing supply air sensor to limit the minimum or
maximum allowable supply air temperature if purely room or return air control is
active.
Hrec damper
Present value of the mixed aid damper control. Go to parameter page for mixed
air damper control.
Heat recovery
Present value for heat recovery control. Go to parameter page for heat recovery
control.
Heating
Present value for heating register control. Go to parameter page for heating regis-
ter control.
Electrical heating
Present value for electrical heating register control. Go to parameter page for
electric heating register control.
Cooling
Present value for cooling register control. Go to parameter page for cooling regis-
ter control.
Heating 2
Present value for heating register control for an additional register. Go to parame-
ter page for heating register control.
El Heating 2
Present value for electric heating register control for an additional register.
Go to parameter page for electric heating register control.
Cooling 2
Present value for cooling register control for an additional register. Go to parame-
ter page for cooling register control.
Fan heating
Present value of the fan heating sequence. Go to parameter page for fan heating
sequence.
Fan cooling
Present value of the fan cooling sequence. Go to parameter page for fan cooling
sequence.
Fan compensation
Present value of the fan temperature compensation. Go to parameter page for
fan temperature compensation.
Prerequisite
Parameterization
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 59