Parameter
Range
Function
sor. Limited control of the heating setpoint occurs if the
supply air temperature > Supply tmp min.
Supply tmp min stpt
-64.0 …99.0 [°C]
Lowest allowable supply air temperature for a cascade
control.
Supply tmp max stpt
-64.0 …99.0 [°C]
Highest allowable supply air temperature for a cascade
control.
Draught htg max dev
0.0…64.0 [°C]
Maximum difference between supply air and room tem-
perature for heating when the room draught limit is en-
abled (configuration 2).
Draught clg max dev
0.0…64.0 [°C]
Maximum difference between supply air and room tem-
perature for cooling when the room draught limit is en-
abled (configuration 2).
Fan htg deadzone
0…20 [°C]
Controller dead zone: Setpoint = Supply air heating set-
point – dead zone.
Fan clg deadzone
0…20 [°C]
Controller dead zone: Setpoint = Supply air heating set-
point – dead zone. Or if sequence is placed last: Supply
air cooling se dead zone.
Fan comp tmp stpt
0…99 [°C]
Setpoint for room related fan compensation. See Fan
compensation; Function: Increase/decrease fan setpoint
based on room temperature.
Fan comp tmp functn
Increase
Decrease
See Fan compensation; Function: Increase/decrease fan
setpoint based on room temperature.
Summer comp
---
Present value for summer compensation. Go to parameter
page for summer compensation.
Winter comp
---
Present value for winter compensation. Go to parameter
page for winter compensation.
Sply tmp dev alarm
---
Present state for the setpoint/actual value monitoring of
the supply air pressure:
14. Passive: No alarm.
15. Active: Pending alarm.
Go to parameter page for supply air temperature monitor-
ing.
Room tmp dev alarm
---
Present state for the setpoint/actual value monitoring of
the room temperature:
16. Passive: No alarm.
17. Active: Pending alarm.
Go to parameter page for room temperature monitoring.