73 / 244
Siemens
Standard application AHU
CE1P3977en_02
Building Technologies
Functions
01.02.2010
Master Index > Unit > Temp control > Heat recovery > Frost
Parameter
Range
Function
Controller
0...100 [%]
Present value for the frost controlled. Go to con-
troller settings page.
Setpoint
-64...64 [°C]
For temperature frost protection only!
For one setpoint: Present setpoint for the frost
controller.
Fan stage 1 stpt
0...5000 [Pa]
For air-side frost protection only!
Setpoint for the controller at fan stage 1.
Fan stage 2/3 stpt
0...5000 [Pa]
For air-side frost protection only!
Setpoint for the controller at fan stage 2 and 3.
5.8 Heating / Heating 2
5.8.1 General
Heating / heating 2 is enabled and preconfigured in configuration 1, configuration 2
and configuration I/Os.
Main Index > Configuration > Configuration 1
Parameter
Range
Function
Heating /
Heating 2
– No
– Yes
– Yes+Preheat
– No (additional) heating register.
– (Additional) heating register without preheating.
– (Additional) heating register with preheating.
Main Index > Configuration > Configuration 2
Parameter
Range
Function
Htg frost protect /
Heating 2 frost
– No
– sensor
– Sensor2Spv
– Detector
– Snsr+Dtctr
– 2Spv+Dtctr
– No frost protection.
– Frost protection using a sensor.
– Frost protection using a sensor and 2 setpoints.
– Frost protection using a detector.
– Frost protection using a sensor and detector.
– Frost protection using a sensor, 2 setpoints and
detector.
Heating pump /
Heating 2 pump
– No
– Yes
– Yes+Kick
– No heating register pump.
– Heating register pump without pump kick.
– Heating register pump with pump kick.
Htg pump alarm /
Heating 2 pump alm
– No
– Alarm
– Fdbk
– Both
– Pump without alarm or feedback.
– Pump with alarm.
– Pump with feedback.
– Pump with alarm and feedback.
Heating 2 control
– StandAlone
– InSequence
– Not integrated in sequence.
– Integrated in sequence.
The hot ware registers can be operated with pump (pump kick, alarm, feedback) or
without pump. Frost detection and controlled frost protection is integrated. The ad-
ditional heating register can be operated as a separate register with its own set-
point. The heating register is forced off if:
– Night unoccupied (temperaturstart) cool
– Summer night cooling
– Combicoil at summer (only heating, not heating2)
A maximum of one of the two additional registers Heating 2 or El heating 2 can be
integrated into the temperature control sequence.
Parameter
Prerequisite
Enable heating group
Configuration
Function
Note
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 73