Performance Data
B2–10
CP 343-5 for PROFIBUS / Manual Part B2
Release 11/2002
C79000-G8976-C160-02
Table 4-2
, Fortsetzung
Component /
FB
Job Complete without
Errors in ms (last call)
Job Active in ms
(next call)
Job Trigger in ms
(first call)
FB
Number
REPORT
FB 4
8.0
0.2
1.8
STATUS
FB 5
1.8
0.2
2.2
WRITE
FB 6
7.6
0.2
2.0
Further Notes on FMS
Please note the following:
In FMS server mode, the CP occupies an unconfigured communication bus
connection on the S7 CPU.
Note that the S7 CPU 314 supports a maximum of 4 (newer CPU types a
maximum of 12) unconfigured K bus connections! If, for example, you operate a
PG and an OP with the S7 CPU, two unconfigured K bus connections are still free.
Note
To allow module replacement without a PG, settings on the CPU must be
modified. Open the Properties dialog of the CPU in HW Config; in the “Monitoring
time for...” box in the “Startup” tab, check and, if necessary, increase the following
values:
– “Transfer of parameters to modules”
Depending on your system (station configuration), you may need to increase the
following parameter:
– “Ready message from modules”