The parameters have the following meaning, range of values and
representation:
Parameter
Permitted range of values
Value in
Job type
0 to 7 where:
0: cancel job or
no job active
1: every minute
2: every hour
3: every day
4: every week
5: every month
6: every year
7: once
BCD format
Seconds
1/100 seconds
Minutes
Hours
Weekday
Day of month
1)
Month
Year
0 to59
0
0 to 59
0 to 23 or 1 to 12, depending on the
format
0 to 6 for Mon to Sun
1 to 31
1 to 12
0 to 99
BCD format
Format
2)
Format for the hour field with the
following meaning:
Bit 15 = 0:
12 hour clock
Bit 15 = 1:
24 hour clock
(bit 14 = 0)
Bit 14 = 0:
"am"
Bit 14 = 1:
"pm"
–
1) After calling OB 151, the specified value is checked logically that the date is correct
taking into account leap years.
2) For the meaning of "am" and "pm": refer to OB 150 in the previous section:
"format" must match the form specified when setting the system time with OB 150.
Data field in the flag area
If you set up the data field in a flag area, you must take into account
the following assignment of the data field words to the flag bytes. "x"
is the parameter ’number of the 1st data field word’ which must be
written to ACCU-1-L when OB 151 is called.
Bit no. 15
8 7
0
Data field word 1
Flag byte x
Flag byte x+1
Data field word 2
Flag byte x+2
Flag byte x+3
Data field word 3
Flag byte x+4
Flag byte x+5
Data field word 4
Flag byte x+6
Flag byte x+7
OB 151: Set/Read Time for Clock-Controlled Interrupt
CPU 948 Programming Guide
6 - 44
C79000-G8576-C848-04
Summary of Contents for CPU 948
Page 10: ...Contents CPU 948 Programming Guide 1 2 C79000 G8576 C848 04 ...
Page 32: ...Contents CPU 948 Programming Guide 2 2 C79000 G8576 C848 04 ...
Page 72: ...Data Blocks CPU 948 Programming Guide 2 42 C79000 G8576 C848 04 ...
Page 74: ...Contents CPU 948 Programming Guide 3 2 C79000 G8576 C848 04 ...
Page 154: ...Contents CPU 948 Programming Guide 4 2 C79000 G8576 C848 04 ...
Page 200: ...Contents CPU 948 Programming Guide 5 2 C79000 G8576 C848 04 ...
Page 308: ...Contents CPU 948 Programming Guide 7 2 C79000 G8576 C848 04 ...
Page 324: ...Examples of Parameter Assignment CPU 948 Programming Guide 7 18 C79000 G8576 C848 04 ...
Page 326: ...Contents CPU 948 Programming Guide 8 2 C79000 G8576 C848 04 ...
Page 370: ...Addressable System Data Area CPU 948 Programming Guide 8 46 C79000 G8576 C848 04 ...
Page 372: ...Contents CPU 948 Programming Guide 9 2 C79000 G8576 C848 04 ...
Page 486: ...Contents CPU 948 Programming Guide 11 2 C79000 G8576 C848 04 ...
Page 522: ...PG Functions via the S5 Bus CPU 948 Programming Guide 11 38 C79000 G8576 C848 04 ...
Page 524: ...Contents CPU 948 Programming Guide 12 2 C79000 G8576 C848 04 ...
Page 538: ...Contents CPU 948 Programming Guide 13 2 C79000 G8576 C848 04 ...
Page 546: ...List of Key Words CPU 948 Programming Guide Index 6 C79000 G8576 C848 04 ...