background image

 

 

Siemens 

 

A6V11974867_en--_b 

Smart Infrastructure 

 

2021-08-30 

 

Screw terminals for wire cross sections up to 

Max. 2.5 mm

2

 (14 AWG) 

Internal fusing 

2.5 A irreversible / non-replaceable 

External supply line fusing (EU) 

Non-renewable fuse max. 10 A slow 
or  
circuit breaker max. 13 A 
Tripping characteristic B, C, D per EN 60898 
or 
Power supply with current limitation of max. 10 A 

 

Power consumption (for transformer planning) 

 

Power consumption AC 

16 VA 

Power consumption DC 

8 W 

 

Function data 

 

Hardware information 

Processor 

NXP i.MX8 DualX 

Storage 

2 GB RAM 
8 GB eMMC 

 

 

Data backup in the event of power failure 

Super cap to support real-time clock (7 days). 

 

Interfaces 

 

Ethernet interfaces 

Plug 

3 x RJ45, shielded 

Interface type 

10Base-T / 100Base-TX, IEEE 802.3 compatible 

Bit rate 

10/100 Mbps, autosensing 

Protocol 

BACnet on UDP/IP and HTTPs on TCP/IP 

Cabling, cable type 

10 Mbps: Min. CAT3, shielded cable is recommended 
100 Mbps: Min. CAT5, shielded cable is recommended 

Cable length 

Max. 100 m (330 ft) 

 

 

Screw terminals, plug-in 

Cu-wire or Cu-strand with wire end sleeve 

1 x 0.6 mm 

 to 2.5 mm

2

 (22 to 14 AWG) 

or 2 x 0.6 mm 

 to 1.0 mm

2

 (22 to 18 AWG) 

Cu-strand without wire end sleeve 

1 x 0.6 mm 

 to 2.5 mm

2

 (22 to 14 AWG) 

or 2 x 0.6 mm 

 to 1.5 mm

2

 (22 to 16 AWG) 

Stripping length 

6...7.5 mm (0.24...0.29 in) 

Screwdriver 

Slot screws, screwdriver size 1 with shaft ø = 3 mm 

Max. tightening torque 

0.6 Nm (0.44 lb ft) 

 

Summary of Contents for CXG3.X200

Page 1: ...aces USB interface for 4G dongles Operating voltage AC 24 V or DC 24 V Mounting on standard rails or on the wall Plug in screw terminal blocks Multi site management depending on firmware Remote operation monitoring depending on firmware Alarm treatment depending on firmware Remote tool access update and configuration via Siemens Cloud Services de pending on firmware A6V11974867_en _b Smart Infrast...

Page 2: ... trolled monitored devices such as controllers sensors and actuators in the building The device integrates common BACnet IP or Modbus TCP devices and systems as well as Siemens fire system protocols It securely transmits data to the cloud over cable networks or over mobile networks e g 4G With a router 4G USB Dongle support is available in addition see Accessories Type summary Type Order number De...

Page 3: ... 3 Green Continuously ON Continuously OFF Flashing Link active No connection Network traffic Yellow Continuously ON Continuously OFF Link 100 Mbps Link 10 Mbps RUN Green Continuously ON Continuously OFF Flashing Device operational Device not operational Start up or program halted Red Continuously OFF Continuously ON Rapid flashing OK HW or SW fault power off and on the X200 Firmware or application...

Page 4: ...fety regulations may result in personal injury and property damage Observe national provisions and comply with the appropriate safety regulations Mounting position and ambient temperature The devices can be snapped onto standard rails or screwed onto a flat surface Plug in screw terminals connect power and interfaces except for Ethernet Ambient temperature 5 50 C 23 122 F Ambient temperature 5 45 ...

Page 5: ... a 4G dongle Reboot the device after a 4G dongle has been connected For details see 4G Dongle Setup A6V12059208 Disposal The device is considered an electronic device for disposal in accordance with European Directive and may not be disposed of as domestic waste Use only designated channels for disposing the devices Comply with all local and currently applicable laws and regulations Technical data...

Page 6: ...ower failure Super cap to support real time clock 7 days Interfaces Ethernet interfaces Plug 3 x RJ45 shielded Interface type 10Base T 100Base TX IEEE 802 3 compatible Bit rate 10 100 Mbps autosensing Protocol BACnet on UDP IP and HTTPs on TCP IP Cabling cable type 10 Mbps Min CAT3 shielded cable is recommended 100 Mbps Min CAT5 shielded cable is recommended Cable length Max 100 m 330 ft Screw ter...

Page 7: ...x load 500 mA Max cable length 5 m Conformity Ambient conditions and protection classification Classification as per EN 60730 Automatic action Control function Degree of pollution Overvoltage category Type 1 Class A 2 III Design Suitable for use in protection class I or II systems Degree of protection of housing to EN 60529 Front parts in DIN cut out Terminal part IP30 IP20 Climatic ambient condit...

Page 8: ... accord ance with the instructions may cause harmful interference to radio communications Howev er there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be de termined by turning the equipment off and on the user is encouraged to try to correct the in terference by one or more...

Page 9: ...stallation side with the building grounding system PE USB USB interface for 4G dongles Term on off Switch for bus termination Polar on off Switch for polarization 65 66 67 COM1 Interfaces EIA 485 68 69 70 COM2 Warranty Technical data on specific applications are valid only together with Siemens products listed under Equipment combinations Siemens rejects any and all warranties in the event that th...

Page 10: ... A6V11974867_en _b Smart Infrastructure 2021 08 30 124 4 88 117 4 61 110 4 33 129 5 08 4 1 0 1 6 144 5 67 26 5 1 04 45 1 77 69 5 2 73 74 5 2 93 4 0 16 21 5 0 85 11 0 43 45 1 77 21 5 0 85 11 0 43 35 5 1 40 49 1 91 ...

Page 11: ......

Page 12: ... Global Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2021 Technical specifications and availability subject to change without notice Document ID A6V11974867_en _b Edition 2021 08 30 ...

Reviews: